International Comfort Products G9MVT0401410A, G9MVT0601714A, G9MVT0801716A, G9MVT0802120A, G9MVT1002120A, G9MVT1202422A, F9MVT0601714A, F9MVT0801716A, F9MVT0802120A, F9MVT1002120A, F9MVT1202422A User Manual
SERVICE AND TECHNICAL
SUPPORT MANUAL
Two−Stage, Variable Speed ECM Blower Motor
35” Tall, High Efficiency Condensing Gas Furnace
(F/G)9MVT
Save this manual for future reference.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manual that may
apply to the product.
DANGER− Immediate hazards which will result in
severe personal injury or death.
WARNING− Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout
this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout
this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with
colors and/or pictures or product labels.
Safety−alert symbol
When you see this symbol on the unit and in
instructions or manuals, be alert to the
potential for personal injury.
TABLE OF CONTENTS
START−UP, ADJUSTMENT, AND SAFETY CHECK4...........
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
Printed in U.S.A.440 04 4221 03 Dec. 2011
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory−authorized kits or
accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes,
the current editions of the National Fuel Gas Code (NFCG)
NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC)
NFPA 70.
In Canada refer to the current editions of the National standards
of Canada CAN/CSA−B149.1 and .2 Natural Gas and Propane
Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety−alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety−alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons could
result in equipment malfunction, property damage,
personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with proper tools and test
instruments.
Installation must conform with local building codes and
with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI
Z223.1, and National standards of Canada
CAN/CSA−B149.1 and .2 Natural Gas and Propane
Installation Codes.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one power
switch.
!
WARNING
WARNING
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow safety warnings could result in personal
injury, death, and/or property damage.
This furnace is not designed for use in mobile homes,
trailers or recreational vehicles.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in damage
personal injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
furnaces.
2
Specifications are subject to change without notice.
440 04 4221 03
SERVICE AND TECHNICAL MANUALGas Furnace: (F/G)9MVT
START−UP CHECK SHEET
For Variable Speed Models (F/G)9MVT
(This sheet is optional. Keep for future reference.)
Date of Start−Up:
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Setup Checks
Check the box when task is complete.
Calculated Input (BTU) Rate: (See Checks and Adjustments
Section).
Heating Check
Measured Line Pressure During High Heat:
Measured Manifold Pressure: High Heat
Low Heat
Temperature of Supply Air: High Heat
Low Heat
Temperature of Return Air:
Temperature Rise (Supply − Return): High Heat
Low Heat
In Rise Range (see furnace rating plate)?
Static Pressure (Ducts) High Heat: Supply
Return
All Electrical Connections Tight?
Have hoses been relocated for furnace U/D/H application?
Condensate Drain Connected?
Condensate Drain Trapped?
Manual Gas Shut−off Upstream of Furnace/Drip Leg
Gas Valve turned ON?
Type of Gas: Natural: Propane:
Filter Type and Size:
Shade in Final Furnace Settings Below:
PL9
SW4
3 2 1
O
N
PL4
SW−1
8 7 6 5 4 3 2 1
SW2SW3
OAT
O
N
PL7
Optional Check: CO?
CO2?
Cooling Check
Temperature of Supply Air:
Temperature of Return Air:
Temperature Difference:
Static Pressure (Ducts) Cooling: Supply
Return
Dealer Comments:
O
3 2 1
N
440 01 4221 033
3 2 1
O
N
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVT
START−UP, ADJUSTMENT, AND SAFETY
CHECK
General
1. Furnace must have a 115-v power supply properly
connected and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring.
Control status indicator light flashes code 10 and furnace does
not operate if polarity is incorrect.
2. Thermostat wire connections at terminals R, W/W1, G,
and Y/Y2 must be made at 24-v terminal block on
furnace control.
3. Natural gas service pressure must not exceed 0.5 psig
(14- in. w.c.), but must be no less than 0.16 psig (4.5-in.
w.c.).
4. Blower door must be in place to complete 115-v electrical
circuit to furnace.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
These furnaces are equipped with a manual reset limit
switch in burner assembly. This switch opens and shuts
off power to the gas valve if an overheat condition (flame
rollout) occurs in burner assembly. Correct inadequate
combustion−air supply or improper venting condition
before resetting switch. DO NOT jumper this switch.
To set the desired cooling airflow:
1. Remove blower door.
2. Locate A/C setup switches on furnace control.
3. Determine air conditioning tonnage used.
4. Configure the switches for the required cooling airflow.
NOTE: Excessive airflow caused by improper A/C switch setup
may cause condensate blow-off in cooling mode.
5. Replace blower door.
Continuous Fan (CF) Setup Switches (SW3)
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low-cooling
airflow for two-speed cooling units. This setup feature allows
continuous fan airflow or low-cooling airflow to be adjusted. To
set desired continuous fan airflow or low-cooling airflow:
1. Remove blower door.
2. Locate CF setup switches on furnace control.
3. Determine desired continuous fan airflow or low-cooling
airflow.
4. Configure the switches for the required continuous fan or
low−cooling airflow.
5. Replace blower door.
Setup Switch (SW4)
Setup switches SW4 are used for applications using a
communicating wall control and to adjust airflow. Refer to the
communicating wall control instructions for configuration of
SW4 for communications. Refer to Figure 5 for configuration of
SW4 airflow options.
Prime Condensate Trap with Water
Before operating furnace, check flame rollout manual reset
switch for continuity. If necessary, press button to reset switch.
EAC-1 terminal is energized whenever blower operates. HUM
terminal is only energized when blower is energized in heating.
Select Setup Switch Positions
There are four sets of setup switches on the furnace control
board. These switches configure the furnace for correct
application requirement. They also select the airflow settings for
Air Conditioning and Continuous Fan CFM.
The Setup Switch locations are shown and described on
Figure 4, Figure 5 and Table 5.The setup switches are also
shown on the unit wiring label.
Setup Switches (SW1)
The furnace control has 8 setup switches that may be set to
meet the application requirements. To set these setup switches
for the appropriate requirement:
SRemove blower door.
SLocate setup switches on furnace control.
SConfigure the set-up switches as necessary for the
application.
SReplace blower door.
NOTE: If a bypass humidifier is used, setup switch SW1-3
(Low Heat Rise Adjust) should be in ON position. This
compensates for the increased temperature in return air
resulting from bypass.
Air Conditioning (A/C) Setup Switches (SW2)
The air conditioning setup switches are used to match furnace
airflow to cooling unit used.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may
not occur. The condensate trap has two internal chambers
which can ONLY be primed by pouring water into the
inducer drain side of condensate trap.
1. Remove upper and middle collector box drain plugs
opposite of the condensate trap. (See Figure 1)
2. Connect field-supplied 1/2-in. (13 mm) OD tube to upper
collector box drain connection.
3. Insert field-supplied funnel into tube.
4. Pour one quart of water into funnel/tube. Water should
run through collector box, overfill condensate trap, and
flow into open field drain.
6. Connect field-supplied 1/2-in. (13 mm) OD tube to middle
collector box drain port.
7. Pour one quart of water into funnel/tube. Water should
run through collector box, overfill condensate trap, and
flow into open field drain.
8. Remove funnel and tube from collector box and replace
collector box plug.
4440 04 4221 03
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVT
Figure 1Priming Condensate Drain
Representative drawing only, some models may vary in appearance.
L11F065
Purge Gas Lines
If not previously done, purge the lines after all connections
have been made and check for leaks.
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
WARNING
Adjustments
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result
in excess overfire and heat exchanger failures.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
DO NOT redrill orifices. Improper drilling (burrs,
out−of−round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. This can result in flame
impingement of heat exchangers, causing failures. (See
Figure 2)
WARNING
!
CAUTION
Figure 2Orifice Hole
BURNER
ORIFICE
A93059
For proper operation and long term reliability the furnace input
rate must be within +/− 2 percent of input rate on furnace rating
plate.
The gas input rate on rating plate is for installation at altitudes
up to 2000 ft. (610 M).
In the U.S.A., the input rating for altitudes above 2000 ft. (610
M) must be reduced by 2 percent for each 1000 ft. (305 M)
above sea level refer to Table 1.
In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft. (610 M) to 4500 ft. (1372 M) above sea
level.
To adjust manifold pressure to obtain the proper input rate, first,
determine if the furnace has the correct orifice installed. At
higher altitudes or different gas heat contents, it may be
necessary to change the factory orifice to a different orifice.
Tables have been provided in the furnace Service and
Technical Manual to match the required orifice to the manifold
pressure to the heat content and specific gravity of the gas. to
do this:
a. Obtain average yearly gas heat value (at installed
altitude) from local gas supplier.
b. Obtain average yearly gas specific gravity from local
gas supplier.
c. Find installation altitude in Table 3.
d. Find closest natural gas heat value and specific
gravity in Table 3.
e. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low−and high−heat
manifold pressure settings for proper operation.
f. Check and verify burner orifice size in furnace.
NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.
g. Replace orifice with correct size, if required by
Table 3. Use only factory−supplied orifices. See
EXAMPLE.
EXAMPLE: 0 - 2000 ft. (0 - 609.6M) altitude
Heating value = 1050 Btu/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 44
Manifold pressure: 3.4-in. w.c. for high heat, 1.4-in. w.c. for low
heat
* Furnace is shipped with No. 44 orifices. In this example, all
main burner orifices are the correct size and do not need to be
changed to obtain proper input rate.
440 04 4221 035
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVT
Table 1Altitude Derate Multiplier for U.S.A.
ALTITUDE
FT. (M)
0–2000
(0−610)
2001–3000
(610−914)
3001–4000
(914−1219)
4001–5000
(1219−1524)
5001–6000
(1524−1829)
6001–7000
(1829−2134)
7001–8000
(2134−2438)
8001–9000
(2438−2743)
9001–10,000
(2743−3048)
* Derate multiplier factors are based on midpoint altitude for altitude range.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (610 to
1372 M), use USA altitudes of 2001 to 3000 ft. (610 to 914
M)
NOTE: If orifice hole appears damaged or it is suspected to
have been redrilled, check orifice hole with a numbered drill bit
of correct size. Never redrill an orifice. A burr−free and squarely
aligned orifice hole is essential for proper flame characteristics.
1. Adjust manifold pressure to obtain low fire input rate.
(See Figure 3)
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device
to manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup SW1—2 on furnace control to ON
position to lock furnace in low−heat operation. (See
Figure 4 and Figure 5)
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on
control to start furnace. (See Figure 4)
h. Remove regulator adjustment cap from low heat gas
valve pressure regulator (See Figure 3) and turn
low−heat adjusting screw (3/16 or smaller flat−tipped
screwdriver) counterclockwise (out) to decrease input
rate or clockwise (in) to increase input rate.
NOTE: DO NOT set low−heat manifold pressure less than
1.3−in. w.c. or more than 1.7−in. w.c. for natural gas. If manifold
pressure is outside this range, change main burner orifices.
i. Install low−heat regulator adjustment cap.
j. Move setup switch SW1−2 to off position after
completing low−heat adjustment.
k. Leave manometer or similar device connected and
proceed to Step 2.
2. Adjust manifold pressure to obtain high fire input rate.
(See Figure 3)
a. Jumper R to W/W1 and W2 thermostat connections
on furnace control. This keeps furnace locked in
high−heat operation.
b. Remove regulator adjustment cap from high−heat
gas valve pressure regulator (See Figure 3) and turn
high heat adjusting screw (3/16−in. or smaller
PERCENT
OF DERATE
01.00
4−60.95
6−80.93
8−100.91
10−120.89
12−140.87
14−160.85
16−180.83
18−200.81
DERATE MULTIPLIER
FACTOR*
flat−tipped screwdriver) counterclockwise (out) to
decrease input rate or clockwise (in) to increase input
rate.
Figure 3
1/2” NPT Inlet
1/8” NPT Inlet
Pressure Tap
Redundant Automatic Gas Control
Valve (2−Stage)
ON/OFF Switch
Regulator Seal Cap
Regulator Adjustment
Regulator Seal Cap under Cap
1/8” NPT Manifold
Pressure Tap
1/2” NPT Outlet
A11152
NOTE: DO NOT set high−heat manifold pressure less than
3.2−in. w.c. or more than 3.8 in. w.c. for natural gas. If manifold
pressure is outside this range, change main burner orifices to
obtain manifold pressure in this range.
c. When correct input is obtained, replace caps that
conceal gas valve regulator adjustment screws. Main
burner flame should be clear blue, almost
transparent. (See Figure 14)
d. Re−install manifold pressure tap plug to gas valve.
e. Remove jumpers R to W/W1 and R to W2.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Re−install manifold pressure tap plug in gas valve to
prevent gas leak.
3. Verify natural gas input rate by clocking meter.
a. Turn off all other gas appliances and pilots served by
the meter.
b. Move setup switch SW1−2 to ON position. This
keeps furnace locked in low−heat operation.
c. Jumper R to W/W1.
d. Run furnace for 3 minutes in low−heat operation.
e. Measure time (in sec) for gas meter to complete 1
revolution and note reading. The 2 or 5 cubic feet dial
provides a more accurate measurement of gas flow.
f. Refer to Table 2 for cubic ft. of gas per hr.
g. Multiply gas rate cu ft./hr by heating value (Btuh/cu
ft.) to obtain input. If clocked rate does not match
required input from Step 1, increase manifold
pressure to increase input or decrease manifold
pressure to decrease input. Repeat steps b through e
until correct low−heat input is achieved. Re−install
low heat regulator seal cap on gas valve.
h. Move setup switch SW1−2 to OFF position and
jumper R to W/W1, and W2. This keeps furnace
locked in high−heat operation. Repeat items d
through g for high−heat operation.
6440 04 4221 03
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVT
24-V THERMOSTAT
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
HARNESS CONNECTOR
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS AND COMM
LED LIGHTS
SW1 SETUP
SWITCHES AND
DELAY
MODEL PLUG
CONNECTOR
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
F) AIRFLOW
SETUP SWITCHES
OUTDOOR
IR TEMP
CONNECTOR
HUMIDIFIER
TERMINAL (24
VAC
0.5 AMP MAX.
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
SW4 SETUP
SOFTWARE
VERSION
PART NUMBER AND
DATE CODE WWYY
Figure 4Example of Variable Speed Furnace Control for ECM Blower Motor
BLOWER OFF-
TERMINALS
(C
A
SWITCHES
-
AND ECM BLOWER
L11F062
440 04 4221 037
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVT
NOTE: Blower door must be installed when taking temperature
rise reading. Leaving blower door off will result in incorrect
temperature measurements.
NOTE: Temperature rise can be determined for low−heat
operation by placing setup switch SW1−2 on furnace control in
ON position. For high−heat operation, place setup switch
SW1−2 in OFF position and jumper R−W2 on furnace control.
DO NOT forget to return setup switch to OFF position and
remove R−W2 jumper upon completion of testing.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in:
SOverheating the heat exchangers or condensing
flue gases in heat exchanger areas not designed
for condensate.
SShortened furnace life.
SComponent damage.
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.
When setup switch SW1−4 is ON, operation will be near the
high end of the rise range for improved comfort.
Furnace must operate within ranges of temperature rise
specified on the furnace rating plate. Determine air temperature
rise as follows:
a. Place thermometers in return and supply ducts as
near furnace as possible. Be sure thermometers do
not see heat exchanger so that radiant heat does not
affect readings. This practice is particularly important
with straight−run ducts.
b. When thermometer readings stabilize, subtract
return−air temperature from supply−air temperature to
determine air temperature rise.
10440 04 4221 03
Specifications subject to change without notice.
c. This furnace is capable of automatically providing
proper airflow to maintain the temperature rise within
the range specified on furnace rating plate. If
temperature rise is outside this range, proceed as
follows:
(1.) Check gas input for low− and high−heat
operation.
(2.) Check derate for altitude if applicable.
(3.) Check all return and supply ducts for excessive
restrictions causing static pressure greater than
0.5−in. w.c.
(4.) Ensure Low Heat Rise Adjust switch SW1−3 on
furnace control is in ON position when a bypass
humidifier is used. (See Figure 4 for switch
location.)
(5.) Make sure proper model plug is installed.
d. Remove thermostat jumpers and release blower door
switch.
e. Repeat Steps a through c as required to adjust for
high heat temperature rise.
f. When correct high heat input rate and temperature
rise is achieved, turn gas valve ON/OFF switch to
OFF.
g. Release blower door switch.
h. Remove manometer or similar device from gas valve.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVT
i. Re−install manifold pressure tap plug in gas valve.
(See Figure 3)
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to
prevent gas leak.
j. Remove thermostat jumper wire from furnace control
board.
k. Turn gas valve ON/OFF switch to ON.
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
mid−point of rise range or slightly above.
l. Proceed to “Set Blower Off Delay” before installing
blower door.
WARNING
!
CAUTION
Adjust Blower Off Delay (Heat Mode)
a. Remove blower door if installed.
b. Turn Dip switch SW−7 or SW−8 ON or OFF for
desired blower off delay. (See Table 4 and Figure 4,
Figure 5)
Table 4Blower Speed Taps
DESIRED HEATING MODE
BLOWER OFF DELAY
(SEC.)
90OFFOFF
120ONOFF
150OFFON
180ONON
SETUP SWITCH (SW1-7 and -8)
POSITION
Adjust Cooling Airflow − High−Speed and
Low−Speed Cooling
The ECM blower can be adjusted for a range of airflows for
low−speed or high−speed cooling. See Table 5−Air Delivery −
CFM (with Filter) and Figure 5. Furnace Setup Switches and
Descriptions. Depending on the model size, the cooling airflow
can be adjusted from 1.5 tons to 6 tons of nominal cooling
based on 350 CFM ton.
NOTE: 6 ton airflow will truncate at 2200 CFM on applicable
models.
The high−speed or single−speed cooling airflow is adjusted by
turning setup switches SW2−1, SW2−2 and SW2−3 either ON
or OFF. Select the required airflow from Table 5. Table 5 is
based on 350 CFM per ton. For other CFM per ton setup switch
selections, see Figure 4, Figure 5 and Figure 16.
The Continuous Fan airflow selection via setup switches SW3
is also the airflow for low−speed cooling when the furnace is
used with a two−speed cooling or heat pump unit. Adjust the
Continuous Fan CFM setup switches SW3 to match the airflow
required for low−speed cooling. Select the required airflow from
Table 5 and Figure 5.
NOTE: The airflow selected via SW3 (low−speed cooling
airflow) cannot exceed the airflow selected via SW2
(high−speed cooling airflow). For other CFM per ton setup
switch selections, see Figure 4 and Figure 5.
NOTE: The airflow settings for SW2 and SW3 airflow
selections are the same for furnaces rated at 1400 CFM of
airflow. See Figure 5− Furnace setup Switches and
Descriptions and a range of airflows for low−speed or
high−speed cooling. See Table 5 − Air Delivery − CFM (with
Filter). The SW3 airflow selections for furnaces rated at 2000
CFM and above can be found in Figure 5.
For a complete explanation of cooling airflow, refer to the
section titled “Sequence of Operation.”
Adjust Continuous Fan Airflow/Low Speed
Cooling Airflow
NOTE: When the furnace is used with a two−speed cooling or
heat pump unit, the airflow selected for Continuous Fan via
setup switch SW3 will also be the airflow used for low−speed
cooling, and vice versa. The Continuous Fan speed can be
further adjusted at a conventional thermostat using the
Continuous Fan speed select function. Changing the
Continuous Fan speed at a conventional thermostat DOES
NOT change the low−speed cooling airflow selected via SW3
at the control board.
NOTE: When the furnace is used with a two−speed cooling or
heat pump unit, adjust the Continuous Fan CFM setup
switches SW3 to match the airflow required for low−speed
cooling.
Select the required Continuous Fan airflow using setup
switches SW3 as shown in Figure 5 and Table 5.
440 04 4221 0311
Specifications subject to change without notice.
Loading...
+ 24 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.