International comfort products F8MXN, G8MXN, G8MXL, F8MXL, R8MXL Installation Instructions Manual

INSTALLATION INSTRUCTIONS
80% Single Stage, ECM Motor
Category I, Gas Furnace
F8MXN, G8MXN, F8MXL, G8MXL
These instructions must be read and understood completely before attempting installation.
DANGER, WARNING, CAUTION, and NOTE Signal Words in Manuals
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product.
DANGER Immediate hazards which will result in severe person- al injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may result in minor personal injury or product or property damage.
NOTE − Used to highlight suggestions which will result in en- hanced installation, reliability, or operation.
The signal word WARNING is used throughout this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures or product labels.
Safetyalert symbol
When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 3...............................
INTRODUCTION 4.........................................
CODES AND STANDARDS 4................................
SAFETY 4.................................................
GENERAL INSTALLATION 5.................................
COMBUSTION AND VENTILATION AIR 5.....................
DUCT SYSTEMS 5.........................................
ACOUSTICAL LINING AND FIBROUS GLASS DUCT 5..........
GAS PIPING AND GAS PIPE PRESSURE TESTING 5..........
ELECTRICAL CONNECTIONS 5.............................
VENTING 5...............................................
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE 5.............................
LOCATION 6..............................................
AIR FOR COMBUSTION AND VENTILATION 8.................
INSTALLATION 10..........................................
UPFLOW INSTALLATION 10.................................
DOWNFLOW INSTALLATION 11.............................
HORIZONTAL INSTALLATION 12.............................
FILTER ARRANGEMENT 13.................................
AIR DUCTS 13.............................................
GAS PIPING 16............................................
ELECTRICAL CONNECTIONS 19............................
SERVICE AND MAINTENANCE PROCEDURES 40.............
SEQUENCE OF OPERATION 44.............................
WIRING DIAGRAM 46......................................
TROUBLESHOOTING GUIDE 47.............................
Use of the AHRI Certified TM Mark indic­ates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirect­ory.org .
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with proper tools and test instruments. Installation must conform with local building codes and with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI Z223.1
INSTALLER: Affix these instructions on or adjacent to the furnace. CONSUMER: Retain these instructions for future reference.
Portions of the text and tables are reprinted from NFPA 54 /ANSI Z223.1−2012©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washing- ton, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
Printed in U.S.A. 441 01 1411 04 July 2013
Figure 1 Dimensional Drawing
VENT
NOTES:
1. Two additional 7/8−in. (22 mm) diameter holes are located in the top plate.
2. Minimum returnair openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM16in. (406 mm) round or 14 1/2 x 12in. (368 x 305 mm) rectangle. ....
b. For 1200 CFM20in. (508 mm) round or 14 1/2 x 19 1/2in. (368 x 495 mm) rectangle. ....
c. For 1600 CFM22in. (559 mm) round or 14 1/2 x 22 1/16in. (368 x 560mm) rectangle. ....
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a ....
combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.....
A B C D
FURNACE SIZE
0451408 143/16 (360) 129/16 (319) 95/16 (237) 1211/16 (322) 4 (102) 104 (47) 0701716 171/2 (445) 157/8 (403) 119/16 (294) 16 (406) 4 (102) 126 (57) 0902116 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 140 (64) 1102120 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 152 (69) 1352420 241/2 (622) 227/8 (581) 151/16 (383) 23 (584) 4 (102)* 163 (74)
* 135 size furnaces require a 5 in. or 6 in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack.
2
CABINET WIDTH
IN. (MM)
OUTLET WIDTH
IN. (MM)
Specifications are subject to change without notice.
Table 1 – Dimensions
TOP AND BOTTOM
FLUE COLLAR
IN. (MM)
BOTTOM WIDTH
IN. (MM)
VENT
CONNECTION
SIZE*
IN. (MM)
441 01 1411 04
SHIP WT (LB / KG)
SAFETY CONSIDERATIONS
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use could cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factoryauthorized and listed kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
Recognize safety information. This is the safetyalert symbol
. When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
441 01 1411 04
WARNING
!
CAUTION
Specifications are subject to change without notice.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instruc­tions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature−rise range with a duct system which has an external static pressure within the allow­able range, as specified in the “Start−Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas−fired furnace for installation in a residential gar- age must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION sec­tion of these instructions.
10. These Multipoise GasFired Furnaces are CSA (formerly A.G.A. and C.G.A). designcertified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory−shipped for use with natural gas. A CSA listed accessory gas conversion kit is required to convert furnace for use with propane gas.
11. See Figure 2 for required clearances to combustible construction.
12. Maintain a 1in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 inches (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manu­facturer’s coil model numbers END4X, ENW4X or coil casing model number NAEA. See Figure 2 for clear­ance to combustible construction information.
3
INTRODUCTION
F8MXN, G8MXN, F8MXL, and G8MXL, 4way multipoise Category I fan−assisted furnace is CSA design−certified. A Category I fan−assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factoryshipped for use with natural gas.
This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors. This furnace is designed for minimum continuous returnair temperature of 60_F
Figure 2 Clearances to Combustibles
(16_C)db or intermittent operation down to 55_F (13_C) db such as when used with a night setback thermostat. Returnair temperature must not exceed 85_F (29_C) db. Failure to follow these returnair temperature limits may affect reliability of heat exchangers, motors, and controls. (See Figure 3).
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
4
In the United States, follow all codes and standards for the following:
Safety
S USA: National Fuel Gas Code (NFGC) NFPA
Specifications are subject to change without notice.
542012/ANSI Z223.12012 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
441 01 1411 04
Figure 3 Return Air Temperature
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
80_F/27_C
60_F/16_C
General Installation
S Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Associ­ation Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington, DC 20001 (www.AGA.org).
Combustion and Ventilation Air
S NFGC NFPA54/ANSI Z223.1−2012 Section 9.3, Air
for Combustion and Ventilation.
Duct Systems
S Air Conditioning Contractors Association (ACCA)
Manual D, Sheet Metal and Air Conditioning Con­tractors National Association (SMACNA), or Americ­an Society of Heating, Refrigeration, and Air Condi­tioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter 35 or 2004 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Acoustical Lining and Fibrous Glass Duct
S Current edition of SMACNA and NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
S NFGC NFPA54/ANSI Z223.12012; chapters 5, 6,
7, and 8 and National Plumbing Codes.
Electrical Connections
S National Electrical Code (NEC) ANSI/NFPA
702011.
Venting
S NFGC NFPA 54 / ANSI Z223.12012; Chapters 12
and 13.
A06745
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause premature furnace component failure.
Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple discon­nects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Firmly touch the clean, unpainted, metal surface of the fur­nace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do noth­ing to recharge your body with static electricity (for ex­ample; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, un­painted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the fur­nace. Put all used and new controls into containers be­fore touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
441 01 1411 04
Specifications are subject to change without notice.
5
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
Figure 4 Multipoise Orientations
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any of the four applications shown in Figure 4.
This furnace must:
S be installed so the electrical components are protec-
ted from water.
S not be installed directly on any combustible material
other than wood flooring for upflow applications. Downflow installations require use of a factoryap­proved floor base or coil model numbers END4X, ENW4X or coil casing model number NAEA when installed on combustible materials or wood flooring (refer to SAFETY CONSIDERATIONS).
S be located as close to the chimney or vent and at-
tached to an air distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning.
Always comply with minimum fire protection clear­ances shown on the furnace clearance to combust­ible label.
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms, and S Chemical storage areas
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death, and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
WARNING
S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S Water softening chemicals S Deicing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants S Cleaning solvents (such as perchloroethylene) S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid S Cements and glues S Antistatic fabric softeners for clothes dryers S Masonry acid washing materials
6
Specifications are subject to change without notice.
441 01 1411 04
All fuelburning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the returnair duct to prevent pulling air from the burner area and from draft safeguard opening.
Figure 5 Installation in a Garage
18IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC.
!
CAUTION
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause premature furnace component failure.
This gas furnace may be used for heating buildings under construction provided that:
The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is maintained between 55_F (13_C) and 80_F (27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed. −Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS
FURNACE
INPUT
(BTUH)
44,000 22 (14193) 6 (152) 14.7 (9484) 5 (127) 11 (7097) 4 (102) 66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127) 88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152)
110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152)
132,000 66 (42581) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178)
FURNACE
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of Open-
ing and Duct
(sq. in. / sq. mm)
WATER
HEATER
Round Duct
Diameter
(in./mm)
441 01 1411 04
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of Open-
ing and Duct
(sq. In. / sq. mm)
Round Duct
Diameter
(in. / mm)
EXAMPLES: Determining Free Area
TOTAL INPUT
Specifications are subject to change without notice.
TWO OPENINGS OR VERTICAL
Free Area of
Opening and Duct
(sq. In. / sq. mm)
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Round Duct
Diameter
(In./mm)
7
Table 3 – Minimum Space volumes for 100% combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN−ASSISTED TOTAL
ACH
0.60 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300
0.50 1,260 1,680 2,100 1,320 1,980 2,640 3,300 3,960
0.40 1,575 2,100 2,625 1,650 2,475 3,300 4,125 4,950
0.30 2,100 2,800 3,500 2,200 3,300 4,400 5,500 6,600
0.20 3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900
0.10 6,300 8,400 10,500 6,600 9,900 13,200 16,500 19,800
0.00 NP NP NP NP NP NP NP NP
ACH = Air Changes/Hour NP = Not Permitted
(1,000’S BTUH GAS INPUT RATE
30 40 50 44 66 88 110 132
Space Volume (ft.3)
FAN ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
AIR FOR COMBUSTION AND
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect returnair ducts to the back of the furnace. (See Figure 6)
Figure 6 Prohibit Installation on Back
WARNING
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
S U.S. installations: Section 9.3 of the NFGC
NFPA54/ANSI Z223.1−2012, Air for Combustion and Ventilation, and applicable provisions of the local building codes.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Makeup air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of makeup air is available.
WARNING
A02054
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the fullheat or full−cool position.
8
Specifications are subject to change without notice.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000
Btuh require the OUTDOOR COMBUSTION AIR METHOD.
S Spaces having at least 50 cubic feet per 1,000 Btuh
may use the INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR INFILTRATION
METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combus­tion, ventilation, and dilution of flue gases using per­manent horizontal or vertical duct(s) or opening(s) dir­ectly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Figure 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12−in. (300
mm) of the ceiling and the second opening MUST commence within 12−in. (300 mm) of the floor.
b. Size openings and ducts per Figure 7 and Table 2.
441 01 1411 04
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm
2
/kW) of combined input for all gas appliances in the space per Figure 7 and Table 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Figure 7 and Table 2.
3. ONE OUTDOOR OPENING requires: a. 1 square inch of free area per 3,000 Btuh (734
2
mm
/kW) for combined input of all gas appliances in
the space per Table 2 and
b. Not less than the sum of the areas of all vent connect-
ors in the space.
The opening shall commence within 12” (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1” (25 mm) from the sides and back and 6” (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Figure 7 Air for Combustion, Ventilation, and Dilution
from Outdoors
1 SQ IN.
E
12 ″ MAX
(305mm)
1 SQ IN. PER 4000 BTUH*
PER 4000 BTUH*
F
1 SQ IN .
BTUH*
1 SQ IN .
BTUH*
G
12
(305mm)
MAX
PER
4000
OUTDOORS
PER 4000
12
(305mm)
MAX
A03174
DUCTS
TO
O UTDOORS
(305mm)
12 ″ MAX
1 SQ IN. PER 2000 BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
(305mm)
12 ″ MAX
CIRCULA TING AIR DUCT S
*Minimum dimensions of 3 in. (76 mm). NOTE: Use any of the following combinations of openings:
A&B, C&D, D&E, F&G
B
AIR DUCTS
C IRCULA TING
A
OF COMB USTION AIR
CLEARANCE IN FRONT
D
VENT THR OUGH R OOF
(76mm)
AT LEAST 3 IN .
OPENINGS SHALL BE
C
DUCT
TO
OUTDOORS
Indoor Combustion Air NFPA & AGA Standard and KnownAirInfiltration Rate Methods Indoor air is permitted for combustion, ventilation, and
dilution, if the Standard or KnownAirInfiltration Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas ap­pliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space. Table 3 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.12012/NFPA 54−2012, 9.3.2.2:
1. For other than fanassisted appliances, such as a draft hoodequipped water heater:
Volume
Other
=
21ft ACH
3
I
other
1000 Btu/hr
A04002
2. For fanassisted appliances such as this furnace:
Volume
Fan
=
15ft ACH
3
I
fan
1000 Btu/hr
A004003
If: Iother = combined input of all other than fan−assisted appliances in Btuh/hr Ifan = combined input of all fanassisted appliances in Btuh/hr ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closeable doors between rooms. b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.
2
mm
/kW) of the total input rating of all gas appliances
in the space, but not less than 100 in.
2
/1,000 Btuh (2,000
2
(0.06 m2). One opening shall commence within 12” (300 mm) of the ceiling and the second opening shall commence with-
441 01 1411 04
Specifications are subject to change without notice.
9
in 12” (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Figure 8)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in.
2
mm
/kW) of total input rating of all gas appliances.
2
/1,000 Btuh (4,400
Figure 8 Air for Combustion, Ventilation, and Dilution
from Indoors
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combus­tion Air Method below and,
2. Outdoor openings shall be located as required in the Outdoor Combustion Air Method mentioned previ­ously and,
3. Outdoor openings shall be sized as follows: a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air Meth­od below.
Figure 9 Removing Bottom Closure Panel
CIRCULATING AIR
DUCTS
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
2
*Minimum opening size is 100 in. *Minimum of 3 in. (76 mm), when type B1 vent is used.
VENT THROUGH ROOF
12" MAX
(305mm)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
(152mm)
6" MIN
Ü
(FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
with minimum dimensions of 3 in. (76 mm).
12" MA X
(305mm)
A03175
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1−in.
2
/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Meth- od, infiltration should be adequate to provide air for combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight con­struction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section.
Unusually tight construction is defined as construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gas­keted or sealed and
b. Doors and openable windows are weatherstripped
and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole plates and floors, between wallceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
BOTTOM CLOSURE PANEL
BOTTOM FILLER PANEL
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The minim­um dimension of air openings shall be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. This panel MUST be in place when only side return air is used.
NOTE: Side return−air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side returnair openings in DOWNFLOW configuration.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used. (See Figure 10) Install field−supplied, 5/16 x 1−1/2 in. (8 x 38 mm) (max) corrosionresistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom
10
Specifications are subject to change without notice.
441 01 1411 04
closure panel to install leveling legs. To remove bottom closure panel, see Item 1. in Bottom Return Air Inlet section.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Figure 10)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (In­stall flat washer if desired.)
Figure 10 Leveling Legs
5/
16″
(8mm)
(8mm)
5/
16″
1 3/ 4″
(44mm)
Figure 11 Floor and Plenum Opening Dimensions
A
B D
C
3
/ 4″
1
(44mm)
(8mm)
5
/ 16″
(8mm)
5/
16″
1
(44mm)
3/
4″
3/
4″
1
A89014
(44mm)
4. Adjust outside nut to provide desired height, and tight­en inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
DOWNFLOW INSTALLATION NOTE: For downflow applications, this furnace is approved
for use on combustible flooring when any one of the following two accessories are used:
S Downflow combustible floor subbase S Coil model numbers END4X, ENW4X S Coil casing model number NAEA
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Figure 11.
3. Construct plenum to dimensions specified in Table 4 and Figure 11.
4. If downflow subbase is used, install as shown in Figure 12. If coil model numbers END4X, ENW4X or coil casing model number NAEA are used, install as shown in Figure 13.
NOTE: It is recommended that the perforated supply−air duct flanges be completely folded over or removed from furnace when installing the furnace on a factorysupplied cased coil or coil casing. To remove the supply−air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Figure 14)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in this panel when closure panel,
1. Tilt or raise furnace and remove two screws holding
2. Rotate bottom filler panel downward to release holding
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws
441 01 1411 04
bottom returnair opening. Remove and discard
bottom return air is used. To remove bottom
perform the following:
bottom filler panel. (See Figure 9)
tabs.
Specifications are subject to change without notice.
A96283
Figure 12 Furnace, Plenum, and Subbase Installed
on a Combustible Floor
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Figure 13 Furnace, Plenum, and Coil or
Coil Casing Installed on a Combustible Floor
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A08556
11
Table 4 – Opening Dimensions − In. (mm)
FURNACE
CASING
WIDTH
14–3/16
(360)
17–1/2
(445)
21
(533)
241/2
(622)
APPLICATION
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring Coil with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
1211/16
(322)
129/16
(319)
11−13/16
(284)
125/16
(313)
16
(406)
157/8
(403)
151/8
(384)
151/2
(394)
191/2
(495)
193/8
(492)
185/8
(473)
19
(483)
23
(584)
227/8
(581)
221/8
(562)
221/2
(572)
215/8
(549)
19
(483)
19
(483)
19
(483)
215/8
(549)
19
(483)
19
(483)
19
(483)
215/8
(549)
19
(483)
19
(483)
19
(483)
211/8
(537)
19
(483)
19
(483)
19
(483)
135/16
(338)
133/16
(335)
137/16
(341)
135/16
(338)
165/8
(422)
161/2
(419)
163/4
(425)
161/2
(419)
201/8
(511)
20
(508)
201/4
(514)
20
(508)
235/8
(600)
231/2
(597)
233/4
(603)
231/2
(597)
221/4
195/8
205/8
221/4
195/8
205/8
221/4
195/8
205/8
221/4
195/8
205/8
(565)
(498)
(600)
20
(508)
(565)
(498)
(600)
20
(508)
(565)
(498)
(600)
20
(508)
(565)
(498)
(600)
20
(508)
HORIZONTAL INSTALLATION
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return−air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawl space on either the lefthand (LH) or righthand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a noncombustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Figure 15 and Figure 16) Secure angle iron to bottom of furnace as shown. Heavy−gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4in. (19 mm) screws into the side and 2 #8 x 3/4−in. (19 mm) screws in the bottom of the furnace casing for each strap. (See Figure 15 and Figure 16) If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment
12
Specifications are subject to change without notice.
screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. (See Figure 2 and Figure 17) For furnaces with 1−in. (25 mm) clearance requirement on side, set furnace on noncombustible blocks, bricks or angle iron. For crawl space installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
RollOut Protection
Provide a minimum 17−3/4 in. x 22 in. (451 mm x 559 mm) piece of sheet metal for flame rollout protection in front of burner area for furnaces closer than 12 inches (305 mm) above the combustible deck or suspended furnaces closer than 12 inches (305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. (25 mm) with the door removed. The bottom closure panel on furnaces of widths 171/2 in. (445 mm) and larger may be used for flame roll−out protection when bottom of furnace is used for return air connection. See Figure 17 for proper orientation of roll−out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler panel. (See Figure 9)
441 01 1411 04
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws. Side Return Air Inlet
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. This panel MUST be in place when side return air inlet(s) is used without a bottom return air inlet. Not all horizontal furnaces are approved for side return air connections. (See Figure 20).
FILTER ARRANGEMENT
!
CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces.
A field−supplied accessory external filter is required. Refer to the instructions supplied with the external filter rack
for assembly and installation options.
AIR DUCTS General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 5 − AIR DELIVERY−CFM (With Filter). When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. Secure ductwork with proper fasteners for type of ductwork used. Seal supply and returnduct connections to furnace with code approved tape or duct sealer.
WARNING
NOTE: Flexible connections should be used between
ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated and sealed to enhance system performance. When air conditioning is used, a vapor barrier is recommended. Maintain a 1in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment NOTE: Metal duct systems that do not have a 90 degree
elbow and 10 ft. (3 M) of main duct to the first branch take−off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the airstream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supplyair duct to flanges on furnace supply−air outlet. Bend flange upward to 90_ with wide duct pliers. (See Figure 14) The supply−air duct must be connected to ONLY the furnace supply−outlet−air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
NOTE: For horizontal applications, the top−most flange may be bent past 90 degrees to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
Downflow Furnaces
Connect supply−air duct to supply−air outlet on furnace. Bend flange inward past 90_ with wide duct pliers. (See Figure 14) The supplyair duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing (when used). When installed on combustible material, supplyair duct must be connected to ONLY the accessory subbase or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace casing.
441 01 1411 04
Specifications are subject to change without notice.
13
Figure 14 Duct Flanges
UPFLOW DOWNFLOW HORIZONTAL
120°
MIN
90°
YES
YES
NO
120°
MIN
YES
YES
NO
Figure 15 Horizontal Unit Suspension
1
/
4 " (6mm) THREADED ROD
4 REQ.
120°
MIN
90°
YES
YES
NO
A02020
OUTER DOOR A S SEMBLY
8" (203mm) FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
MIN
SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH
3
/4" (19mm) SCREWS
3 #8 x TYPICAL FOR 2 SUPPORTS
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm) ANGLE IRON OR UNI-STRUT MAY BE USED
A10130
14
Specifications are subject to change without notice.
441 01 1411 04
Figure 16 Horizontal Suspension with Straps
METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS IN BOTTOM).
METHOD 2 USE (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS FOR EACH STRAP. THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES.
Figure 17 Typical Attic Installation
LINE CONT A CT ONL Y PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE T OP AND TW O SIDES OF THE FURNA CE JA CKET AND BUILDING JOISTS , STUDS , OR FRAMING.
EQUIPMENT MANU AL
SHUT -OFF GAS VA LV E
SEDIMENT
TRAP
UNION
Return Air Connections
!
WARNING
FIRE HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never connect returnair ducts to the back of the furnace. Refer to the following instructions.
441 01 1411 04
GAS ENTR Y
M IN
6
(451mm)
17 3 / 4
22
(559mm)
SHEET MET AL
Downflow Furnaces
The returnair duct must be connected to returnair opening (bottom inlet) as shown in Figure 21. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow and most horizontal furnaces. (See Figure 21) Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace.
Upflow and Horizontal Furnaces
The returnair duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main
Specifications are subject to change without notice.
TYPE-B VENT
(152mm)
*
30-IN . (762mm) MIN WORK AREA
17 3 / 4 ″ (451mm) 4 3 / 4 ″ (121mm) 1
(25mm)
EXTEND OUT 12 FR OM FA CE OF DOOR
* WHEN USED W ITH SINGLE W ALL VEN T CONNECTIONS
OVERALL
UNDER DOOR
UNDER FURNACE
(305mm)
A10131
A10164
15
Loading...
+ 34 hidden pages