International comfort products F8MVL, G8MVL Installation Instructions Manual

INSTALLATION INSTRUCTIONS
80% TwoStage, Variable Speed
Category I, Gas Furnace
F8MVL & G8MVL 'B2' Series
These instructions must be read and understood completely before attempting installation.
DANGER, WARNING, CAUTION, and NOTE Signal Words in Manuals
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product.
DANGER Immediate hazards which will result in severe person- al injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may result in minor personal injury or product or property damage.
NOTE − Used to highlight suggestions which will result in en- hanced installation, reliability, or operation.
The signal word WARNING is used throughout this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures or product labels.
Safetyalert symbol
When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 3..............................
INTRODUCTION 4........................................
CODES AND STANDARDS 4...............................
SAFETY 4................................................
GENERAL INSTALLATION 5................................
COMBUSTION AND VENTILATION AIR 5....................
DUCT SYSTEMS 5........................................
ACOUSTICAL LINING AND FIBROUS GLASS DUCT 5.........
GAS PIPING AND GAS PIPE PRESSURE TESTING 5.........
ELECTRICAL CONNECTIONS 5............................
VENTING 5..............................................
LOCATION 5.............................................
MINIMUM FREE AREA REQUIRED 7........................
AIR FOR COMBUSTION AND VENTILATION 8................
INSTALLATION 10..........................................
OPENING DIMENSIONS 12.................................
AIR DUCTS 13.............................................
GAS PIPING 17............................................
ELECTRICAL CONNECTIONS 18............................
24V WIRING 20...........................................
ACCESSORIES 20.........................................
VENTING 20..............................................
CHIMNEY INSPECTION CHART 25...........................
STARTUP, ADJUSTMENT, AND SAFETY CHECK 31...........
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org .
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with proper tools and test instruments. Installation must conform with local building codes and with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI Z223.1, and National standards of Canada CAN/CSAB149.1 and .2 Natural Gas and Propane Installation Codes.
INSTALLER: Affix these instructions on or adjacent to the furnace. CONSUMER: Retain these instructions for future reference.
Portions of the text and tables are reprinted from NFPA 54 /ANSI Z223.1−2012©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washing- ton, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
Printed in U.S.A. 441 01 2122 01 5/2/2016
Figure 1 Dimensional Drawing
VENT
NOTES:
1. Two additional 7/8-in. (22 mm) diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle. b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle. c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
Table 1 – Dimensions − In. (mm)
A B C E VENT
CABINET
WIDTH
FURNACE SIZE
0451412B 143/16 (360) 129/16 (319) 95/16 (237) 1211/16 (322) 4 (102) 107 (49) 0701716B 171/2 (445) 157/8 (403) 11 9/16 (294) 16 (406) 4 (102) 126 (57) 0902116B 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 140 (64) 1102122B 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 152 (69) 1352422B 241/2 (622) 227/8 (581) 151/16 (383) 23 (584) 4 (102)* 163 (74)
* 135 size furnace require a 5 in. or 6 in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack.
2 441 01 2122 01
IN. (mm)
OUTLET
WIDTH
IN. (mm)
Specifications are subject to change without notice.
TOP AND BOTTOM
FLUE COLLAR
IN. (mm)
BOTTOM INLET
WIDTH
IN. (mm)
CONNECTION
SIZE
IN. (mm)
SHIP WT.
LB (KG)
SAFETY CONSIDERATIONS
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factoryauthorized and listed kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and
qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic
maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with furnace and other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Wear safety glasses, protective clothing and work gloves. Have fire extinguisher available during startup and adjustment procedures and service calls.
This is the safetyalert symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety−alert
WARNING
!
CAUTION
!
CAUTION
. When you see this symbol
symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify hazards which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as spe­cified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the fur­nace space as specified in “Air for Combustion and Ventil­ation” section.
4. Combustion products must be discharged outdoors. Con­nect this furnace to an approved vent system only, as spe­cified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s inten­ded temperature−rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start−Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating out­side the space containing the furnace. See “Air Ducts” sec­tion.
8. A gas−fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these in­structions.
10. These Multipoise GasFired Furnaces are CSA (formerly A.G.A. and C.G.A.) designcertified for use with natural and propane gases (see furnace rating plate) and for in­stallation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed accessory gas conversion kit is required to convert furnace for use with propane gas.
11. See Figure 2 for required clearances to combustible con­struction.
12. Maintain a 1in. (25 mm) clearance from combustible ma­terials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on car­peting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s coil model numbers END4X, ENW4X or coil casing model number NAEA. See Figure 2 for clearance to combustible con­struction information.
Specifications are subject to change without notice.
3441 01 2122 01
Figure 2 Clearances to Combustibles
INTRODUCTION
F8MVL & G8MVL 4−way multipoise Category I fan−assisted furnace is CSA (formerly A.G.A. and C.G.A.) design−certified. A Category I fanassisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory−shipped for use with natural gas. This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
Figure 3 Return Air Temperature
80F/27C
This furnace is designed for minimum continuous return−air temperature of 60F (15C) db or intermittent operation down to 55F (13C)db such as when used with a night setback thermostat. Returnair temperature must not exceed 80F (27C) db. Failure to follow these returnair temperature limits may affect reliability of heat exchangers, motors, and controls. (See Figure 3)
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply
with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States, follow all codes and standards for the following:
60F/16C
Safety
NFPA 54/ANSI Z223.12012 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA
A06745
4 441 01 2122 01
Specifications are subject to change without notice.
90B .
General Installation
Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington, DC 20001 (www.AGA.org) .
Combustion and Ventilation Air
Section 9.3 NFPA 54/ANSI Z223.1−2012 , Air for Combustion and Ventilation .
Duct Systems
Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Acoustical Lining and Fibrous Glass Duct
Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
NFPA 54/ANSI Z223.12012 ; chapters 5, 6, and 7 and National Plumbing Codes .
Electrical Connections
National Electrical Code (NEC) NFPA 70−2011.
Venting
NFPA 54/ANSI Z223.12012; chapters 12 and 13.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the fur­nace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily dis­charged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungroun­ded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to pro­tect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungroun­ded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
LOCATION
GENERAL This multipoise furnace is shipped in packaged configuration.
Some assembly and modifications are required when used in any of the four applications shown in Figure 4.
NOTE: For high−altitude installations, the highaltitude conversion kit MUST be installed at or above 5500 ft. (1676 M) above sea level. Obtain highaltitude conversion kit from your area authorized distributor.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
Figure 4 Multipoise Orientations
Specifications are subject to change without notice.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
5441 01 2122 01
This furnace must:
be installed so the electrical components are protec-
ted from water.
not be installed directly on any combustible material
other than wood flooring for upflow applications. Downflow installations require use of a factoryap­proved floor base or coil model numbers END4X, ENW4X or coil casing model number NAEA when installed on combustible materials or wood flooring (refer to SAFETY CONSIDERATIONS).
be located close to the chimney or vent and attached
to an air distribution system. Refer to Air Ducts sec­tion.
be provided ample space for servicing and cleaning.
Always comply with minimum fire protection clear­ances shown on the furnace clearance to combust­ible construction label.
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
Commercial buildings Buildings with indoor pools Laundry rooms Hobby or craft rooms, and Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals Deicing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All fuelburning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the returnair duct to prevent pulling air from the burner area and from draft safeguard opening.
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 in. (457 mm) above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFPA 54/ANSI Z223.12012 . (See
Figure 5)
Figure 5 Installation in a Garage
18IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect returnair ducts to the back of the furnace. (See Figure 6)
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the fullheat or fullcool position.
6 441 01 2122 01
Specifications are subject to change without notice.
!
CAUTION
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may result in premature furnace component failure. This gas furnace may be used for heating buildings under construction provided that:
The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is maintained between 55F (13C) and 80F (27C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value. The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
Figure 6 Prohibit Installation on Back
A02054
Table 2 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors
FURNACE
INPUT
(BTUH)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102) 66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127)
88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152) 110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152) 132,000 66 (42580) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178)
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
Specifications are subject to change without notice.
7441 01 2122 01
Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
ACH
30 40 50 44 66 88 110 132
Space Volume Ft
FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
3
3
(M
)
0.60 1,050 (29.7) 1,400 (39.6) 1,750 (49.5) 1,100 (31.1) 1,650 (46.7) 2,200 (62.2) 2,750 (77.8) 3,300 (93.4)
0.50 1,260 (35.6) 1,680 (47.5) 2,100 (59.4) 1,320 (37.3) 1,980 (56.0) 2,640 (74.7) 3,300 (93.4) 3,960 (112.1)
0.40 1,575 (44.5) 2,100 (59.4) 2,625 (74.3) 1,650 (46.7) 2,475 (70.0) 3,300 (93.4) 4,125 (116.8) 4,950 (140.1)
0.30 2,100 (59.4) 2,800 (79.2) 3,500 (99.1) 2,200 (62.2) 3,300 (93.4) 4,400 (124.5) 5,500 (155.7) 6,600 (186.8)
0.20 3,150 (89.1) 4,200 (118.9) 5,250 (148.6) 3,300 (93.4) 4,950 (140.1) 6,600 (186.8) 8,250 (233.6) 9,900 (280.3)
0.10 6,300 (178.3) 8,400 (237.8) 10,500 (297.3) 6,600 (186.8) 9,900 (280.3) 13,200 (373.7) 16,500 (467.2) 19,800 (560.6)
0.00 NP NP NP NP NP NP NP NP
NP = Not Permitted
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. Installations: Section 9.3 of the NFPA 54/ANSI
Z223.12012 , Air for Combustion and Ventilation
Figure 7 Air for Combustion, Ventilation, and Dilution
for Outdoors
1 SQ IN.
DUCTS
TO
O UTDOORS
PER 4000 BTUH*
and applicable provisions of the local building codes.
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the
12 ″ MAX
1 SQ IN. PER 2000 BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
(305mm)
12 ″ MAX
CIRCULA TING AIR DUCT S
*Minimum dimensions of 3-in. (76 mm).
NOTE: Use any of the following combinations of openings:
A & B C & D D & E F & G
B
AIR DUCTS
C IRCULA TING
A
OF COMB USTION AIR
CLEARANCE IN FRONT
D
VENT THR OUGH R OOF
(76mm)
AT LEAST 3 IN .
OPENINGS SHALL BE
OUTDOORS
C
DUCT
TO
E
12 ″ MAX
(305mm)
F
1 SQ IN .
BTUH*
1 SQ IN .
BTUH*
G
1 SQ IN. PER 4000 BTUH*
12 MAX
PER
4000
OUTDOORS
PER 4000
12 MAX
(305mm)
furnace. Makeup air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of makeup air is available.
Spaces having at least 50 cubic feet per 1,000 Btuh
may use the INDOOR COMBUSTION AIR, STAND­ARD or KNOWN AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent hori-
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
Spaces having less than 50 cubic feet per 1,000 Btuh
require the OUTDOOR COMBUSTION AIR METH­OD.
zontal or vertical duct(s) or opening(s) directly communic­ating with the outdoors or spaces that freely communicate with the outdoors.
2. Figure 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and vent­ilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300
mm) of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Figure 7 and Table 2.
(305mm)
(305mm)
A03174
8 441 01 2122 01
Specifications are subject to change without notice.
c. TWO HORIZONTAL DUCTS require 1 sq. in. (645
sq. mm) of free area per 2,000 Btuh (1,100 mm of combined input for all gas appliances in the space per Figure 7 and Table 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq. in. (645 sq. mm) of free area per 4,000 Btuh (550
2
mm
/kW) for combined input of all gas appliances in
the space per Figure 7 and Table 2.
3. ONE OUTDOOR OPENING requires: a. 1 sq. in. (645 sq. mm) of free area per 3,000 Btuh
(734 mm2/kW) for combined input of all gas appli­ances in the space per Table 2 and
b. Not less than the sum of the areas of all vent con-
nectors in the space.
Figure 8 Air for Combustion, Ventilation, and Dilution
from Indoors
CIRCULATING AIR
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
DUCTS
VENT THROUGH ROOF
12" MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
(152mm)
6" MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
12" MA X
(305mm)
Ü
(305mm)
2
/kW)
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appli­ances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
Table 3 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code
ANSI Z223.12012/NFPA 542012, 9.3.2.2:
1. For other than fanassisted appliances, such as a draft hoodequipped water heater:
Volume
Other
=
21ft ACH
3
I
other
1000 Btu/hr
* Minimum opening size is 100 sq in. (64516 sq. mm)with minimum dimensions of 3 in. (76 mm) † Minimum of 3 in. (76 mm) when type‐B1 vent is used.
A03175
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air NFPA & AGA Standard and KnownAirInfiltration Rate Methods Indoor air is permitted for combustion, ventilation, and
dilution, if the Standard or KnownAirInfiltration Method is used.
Specifications are subject to change without notice.
A04002
2. For fanassisted appliances such as this furnace:
Volume
Fan
=
15ft ACH
3
I
fan
1000 Btu/hr
A04003
If: Iother = combined input of all other than fanassisted appliances
in Btuh/hr
Ifan = combined input of all fanassisted appliances in Btuh/hr ACH = air changes per hour (ACH shall not exceed 0.60.) The following requirements apply to the Standard Method and
to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms. b. Combining spaces on same floor level. Each open-
ing shall have free area of at least 1 in.2/1,000 Btuh (2,000 mm appliances in the space, but not less than 100 in.
2
/kW) of the total input rating of all gas
2
(0.06 m2). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Figure 8)
9441 01 2122 01
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in. (4,400 mm
2
/kW) of total input rating of all gas appli-
2
/1,000 Btuh
ances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to out­doors having free area of at least 1−in.
2
/4,000 Btuh of total
input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combus­tion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight construction, ad­ditional air MUST be provided using the methods de­scribed in the Outdoor Combustion Air Method section.
4. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gas­keted or sealed and
b. Doors and openable windows are weatherstripped
and
c. Other openings are caulked or sealed. These in-
clude joints around window and door frames, between sole plates and floors, between wall−ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combus­tion Air Method below and,
2. Outdoor openings shall be located as required in the Out­door Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume di-
vided by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus
the Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The min­imum dimension of air openings shall be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. This panel MUST be in place when only side return air is used.
Figure 9 Removing Bottom Closure Panel
BOTTOM CLOSURE PANEL
BOTTOM FILLER PANEL
NOTE: Side return−air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side returnair openings in DOWNFLOW configuration.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used. (See Figure 10) Install fieldsupplied, 5/16 X 11/2 in. (8 X 38 mm) (max) corrosionresistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Figure 10)
Figure 10 Leveling Legs
5/
16
(8mm)
(8mm)
5/
16
1 3 / 4 ″
(44mm)
3
/ 4 ″
1
(44mm)
(8mm)
5
/
16
(8mm)
5/
16
1
(44mm)
3/
4 ″
3/
1
4 ″
A89014
(44mm)
2. For each leg, install nut on bolt and then install bolt with nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
10 441 01 2122 01
Specifications are subject to change without notice.
5. Reinstall bottom closure panel if removed.
DOWNFLOW INSTALLATION NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following two accessories are used:
Downflow combustible floor subbase Coil model numbers END4X or ENW4X Coil casing model number NAEA
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Figure 11.
3. Construct plenum to dimensions specified in Table 4 and Figure 11.
4. If downflow subbase is used, install as shown in Figure 12. If coil model numbers END4X, ENW4X or coil casing model number NAEA are used, install as shown in
Figure 13.
NOTE: It is recommended that the perforated supplyair duct
flanges be completely folded over or removed from furnace when installing the furnace on a factorysupplied cased coil or coil casing. To remove the supplyair duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Figure 14)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLATION
!
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return−air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawlspace on either the lefthand (LH) or righthand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non−combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Figure 15 and Figure 16) Secure angle iron to bottom of furnace as shown. Heavy−gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x in. screws into the side and 2 #8 x in. screws in the bottom of the furnace casing for each strap. (See Figure 15 and Figure 16)
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace
WARNING
Specifications are subject to change without notice.
sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. (See Figure 3 and Figure 17) For furnaces with 1−in. (25 mm) clearance requirement on side, set furnace on noncombustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
Figure 11 Floor and Plenum Opening Dimensions
A
B D
C
A96283
RollOut Protection
Provide a minimum 173/4in. X 22in. (451 X 559 mm) piece of sheet metal for flame rollout protection in front of burner area for furnaces closer than 12in. (305 mm) above the combustible deck or suspended furnaces closer than 12−in. (305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1in. (25 mm)with the door removed.
The bottom closure panel on furnaces of widths 17−1/2−in. (445 mm) and larger may be used for flame rollout protection when bottom of furnace is used for return air connection. See
Figure 17 for proper orientation of rollout shield. Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. This panel MUST be in place when side return air inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections (See Figure 20)
11441 01 2122 01
Figure 12 Furnace, Plenum, and Subbase Installed on a
Combustible Floor
Figure 13 Furnace, Plenum, and Coil or Coil Casing In-
stalled on a Combustible Floor
FURNACE
CASING
WIDTH
IN. (mm)
14–3/16
(360)
17–1/2
(445)
21
(533)
241/2
(622)
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Table 4 – Opening Dimensions − In. (mm)
APPLICATION
Upflow Applications on Combustible or Noncombustible
Downflow Applications on Noncombustible Flooring
Downflow Applications on Combustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible
Downflow Applications on Noncombustible Flooring
Downflow Applications on Combustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible
Downflow Applications on Noncombustible Flooring
Downflow Applications on Combustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible
Downflow Applications on Noncombustible Flooring
Downflow Applications on Combustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Flooring (subbase not required)
(subbase not required)
Downflow applications on Combustible Flooring
(subbase required)
Flooring (subbase not required)
(subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
Flooring (subbase not required)
(subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
Flooring (subbase not required)
(subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
PLENUM OPENING FLOOR OPENING
A B C D
12−11/16
(322)
129/16
(319)
1113/16
(284)
125/16
(319)
16
(406)
157/8
(403)
151/8
(384)
151/2
(394)
191/2
(495)
193/8
(492)
185/8
(473)
19
(483)
23
(584)
227/8
(581)
221/8
(562)
221/2
(572)
215/8
(549)
19
(483)
19
(483)
19
(483)
215/8
(549)
19
(483)
19
(483)
19
(483)
215/8
(549)
19
(483)
19
(483)
19
(483)
211/8
(537)
19
(483)
19
(483)
19
(483)
135/16
(338)
133/16
(335)
137/16
(341)
135/16
(338)
165/8
(422)
161/2
(419)
163/4
(425)
161/2
(419)
201/8
(511)
20
(508)
201/4
(514)
20
(508)
235/8
(600)
231/2
(597)
233/4
(603)
231/2
(597)
A08556
221/4
(565)
195/8
(498)
205/8
(600)
20
(508)
221/4
(565)
195/8
(498)
205/8
(600)
20
(508)
221/4
(565)
195/8
(498)
205/8
(600)
20
(508)
221/4
(565)
195/8
(498)
205/8
(600)
20
(508)
12 441 01 2122 01
Specifications are subject to change without notice.
Filter Arrangement
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces. A fieldsupplied accessory external filter rack is required.
Refer to the instructions supplied with the external filter rack for assembly and installation options.
AIR DUCTS General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 10 Air Delivery−CFM (with Filter). When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply and returnduct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment NOTE: Metal duct systems that do not have a 90 degree
elbow and 10 ft. (3 M) of main duct to the first branch take−off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supplyair duct to flanges on furnace supply−air outlet. Bend flange upward to 90 with wide duct pliers. (See Figure 14) The supplyair duct must be connected to ONLY the furnace supply−outlet−air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
NOTE: For horizontal applications, the top most flange may be bent past 90 to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
Figure 14 Duct Flanges
UPFLOW DOWNFLOW HORIZONTAL
120° MIN
90°
YES
YES
NO
Specifications are subject to change without notice.
120° MIN
YES
YES
NO
120°
MIN
90°
YES
YES
NO
A02020
13441 01 2122 01
OUTER DOOR A S SEMBLY
8" (203mm) FOR DOOR REMOVAL
MIN
Figure 15 Horizontal Unit Suspension
1
/
4 " (6mm) THREADED ROD
4 REQ.
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm) ANGLE IRON OR UNI-STRUT MAY BE USED
SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH
3
/4" (19mm) SCREWS
3 #8 x TYPICAL FOR 2 SUPPORTS
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
Figure 16 Horizontal Suspension with Straps
METHOD 2 USE (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS FOR EACH STRAP. THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES.
A10130
METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS IN BOTTOM).
14 441 01 2122 01
Specifications are subject to change without notice.
A10131
LINE CONT A CT ONL Y PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE T OP AND TW O SIDES OF THE FURNA CE JA CKET AND BUILDING JOISTS , STUDS , OR FRAMING.
EQUIPMENT MANU AL
SHUT -OFF GAS VA LV E
Figure 17 Typical Attic Installation
SHEET MET AL
GAS ENTR Y
17 3 / 4 ″
22
(559mm)
(451mm)
6
M IN
TYPE-B VENT
(152mm)
*
17 3 / 4 ″ 4 3 / 4 ″ 1
(25mm)
EXTEND OUT 12 FR OM FA CE OF DOOR
30-IN . (762mm) MIN WORK AREA
(451mm)
(121mm)
OVERALL
UNDER DOOR
UNDER FURNACE
(305mm)
* WHEN USED W ITH SINGLE W ALL VEN T CONNECTIONS
SEDIMENT
TRAP
UNION
Downflow Furnaces
Connect supplyair duct to supplyair outlet on furnace. Bend flange inward past 90 with wide duct pliers (See Figure 14) The supplyair duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing (when used). When installed on combustible material, supplyair duct must be
Figure 18 Upflow Return Air Configurations and Restrictions
UPFLOW RETURN AIR CONFIGURATIONS AND RESTRICTIONS
5 TONS AND
*
GREATER
2000 CFM AND GREATER AT .6 ESP HI COOLING SPEED
*
A10164
connected to ONLY the accessory subbase or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace casing.
Specifications are subject to change without notice.
15441 01 2122 01
Figure 19 Downflow Return Air Configurations and Restrictions
DOWNFLOW RETURN AIR CONFIGURATIONS AND RESTRICTIONS
5 TONS AND
*
GREATER
* 2000 CFM AND GREATER AT .6 ESP HI COOLING SPEED
Figure 20 Horizontal Return Air Configurations and Restrictions
HORIZONTAL RETURN AIR CONFIGURATIONS AND RESTRICTIONS
5 TONS AND
*
GREATER
* 2000 CFM AND GREATER AT .6 ESP HI COOLING SPEED
16 441 01 2122 01
Specifications are subject to change without notice.
Return Air Connections
!
FIRE HAZARD
A failure to follow this warning could cause personal injury, death and/or property damage.
Never connect returnair ducts to the back of the furnace. Follow instructions below.
Downflow Furnaces
The returnair duct must be connected to returnair opening (bottom inlet) as shown in Figure 1. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow and certain horizontal furnaces. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. (See Figure 19)
Upflow and Horizontal Furnaces
The returnair duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Figure 1. Bypass humidifier may be attached into unused return air side of the furnace casing. (See Figure 18 and Figure 20) Not all horizontal furnace models are approved for side return air connections. (See
Figure 20)
WARNING
GAS PIPING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and a gas leak.
WARNING
WARNING
Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a li­censed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be Thandle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
Refer to Table 5 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. (1.8 M). Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.
Table 5 – Maximum Capacity of Pipe*
NOMINAL
IRON
PIPE SIZE
IN. (MM)
1/2 (12.7)
3/4 (19.0)
1 ( 25.4)
1-1/4
(31.8)
1-1/2
(38.1)
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-In. W.C.) or less and a pressure drop of 0.5-In. W.C. (based on a 0.60 specific gravity gas). Ref: Table 6 and 9.2 NFGC.
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2in. (51 mm) outside the furnace.
INTERNAL
DIA.
IN. (MM)
0.622 (158) 175 120 97 82 73
0.824 (20.9) 360 250 200 170 151
1.049 (26.6) 680 465 375 320 285
1.380 (35.0) 1400 950 770 660 580
1.610 (40.9) 2100 1460 1180 990 900
!
WARNING
!
CAUTION
LENGTH OF PIPE FT (M)
10
(3.0)20(6.0)30(9.1)40(12.1)50(15.2)
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S.
WARNING
Specifications are subject to change without notice.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft. (1.8 M) of furnace. A 1/8in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
17441 01 2122 01
Loading...
+ 38 hidden pages