International Comfort Products ENH4X Installation Manual

INSTALLATION INSTRUCTIONS
Cased N Coil, Horizontal
ENH4X
NOTE: Read the entire instruction manual before starting
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1........................
INTRODUCTION 2...................................
INSTALLATION 2....................................
Horizontal Right and Left with Pan Extension 3......
Furnace Attachment 3............................
Horizontal Attic 4................................
Horizontal Crawl Space 4.........................
Refrigerant Lines 4..............................
Connect Refrigerant Liquid and Suction Lines 4......
Connect Condensate Drain Line 5.................
Waste Line Connection 5.........................
Model Number Identification 6.....................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Use quenching cloths for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the current editions of the National Electrical Codes (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol
instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
NOTE: Nitrogen can leak out through the needle pierce hole in the plugs. This does not indicate a leaking coil nor warrant return of the coil.
. When you see this symbol on the unit and in
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying or servicing system, always turn off main power to system. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
!
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
This coil contains Nitrogen precharge of 15 PSIG. Release of this pressure through the center of the rubber plugs is required before removing the plugs.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
484 01 3700 01 December 2011
INTRODUCTION
The ENH4X is a horizontal, multi--use furnace coil (see Figure 1). With the use of field--supplied transition duct, these furnace coils can also be applied to other similar horizontal furnaces on the market. The ENH4X is available in sizes 24 through 60. All models are equipped with a factory--installed TXV and are used with R--410A refrigerant systems.
NOTE: Models with tin--plated copper coils, “T” in the 8th position of the model number, are installed the same as standard copper coils.
INSTALLATION
This coil is not designed to be installed with furnaces that measure wider than the coil itself.
These units can be installed in multiple configurations. Before installation, there are several performance requirements that must be considered because poor installation can negatively alter performance. This section will briefly discuss those factors.
Ductwork
Coil
Furnace
Airflow
Airflow
Shipping Brace
Pan Extension
Figure 1 -- Model ENH4X Furnace Coil
Furnace
Filler Plate
Furnace
Airflow
Filler Plate
Coil
Coil
Remove 2 Screws
Ductwork
Ductwork
A06031
Filler Plate
Ductwork
CoilDuctwork
Coil
Furnace
Airflow
Filler Plate
Furnace
Airflow
Filler Plate
A08065
Figure 2 -- Horizontal--Left Installation with Filler Plate
Filler Plate
Furnace
Coil
Airflow
Ductwork
A08066
Figure 3 -- Horizontal--Right Installation with Filler Plate
Airflow
Airflow amount and distribution are vital to adequate system performance. In addition, heat pump applications require airflow in a particular direction for best performance. See decal on front of coil for correct direction. Problems that can be experienced with incorrect airflow include:
S low system performance S restricted TXV S frosted coil S poor humidity control S water blow--off
When attaching the coil and building the plenum, pay special attention to the effect these details will have on airflow. After system start--up, check the cfm to insure that it is correct. (Generally, the cfm should be 350 to 400 cfm/ton during normal cooling operation.)
TXV
A thermal expansion valve is utilized in this coil design to optimize performance and comfort throughout the entire operating range of the system. Special attention needs to be taken to the TXV when installing the coil
S Do not overheat valve. Temperatures that exceed 212_F
(100_C) can harm valve performance. Use a wet cloth or heat sink when brazing.
2 484 01 3700 01
S Place liquid filter dryer near ID unit to reduce the risk of
debris clogging the valve.
S Make sure TXV bulb is securely fastened and wrapped in
the indentation on vapor line tube. ENH4X Models: These coils have a factory--installed hard--shutoff TXV
designed only for use with R--410A refrigerant. Use only with outdoor units designed for R--410A.
NOTE: All TXV’S have preset superheat settings and are not field--adjustable.
Cabinet Sweating
If this unit is installed in a garage, attic, or other unconditioned space, special attention needs to be given to the potential of cabinet sweating. A 6 inch (152 mm) wide piece of insulation should be wrapped around the coil casing and supply duct connection point.
Condensate Management
With proper installation, these coils will manage the condensate without blow--off into the duct work. The 60 size coil requires the addition of a pan extension for both horizontal left and horizontal right position, which is supplied with the coils. See detailed instructions for more info. Also, refer to Connect Condensate Drain Line section of this instruction.
!
CAUTION
Pan Extension
Supply Plenum
Figure 4 -- Horizontal--Left Installation of Pan Extension
3. For horizontal--right installation, install pan extension onto right end of horizontal--condensate pan. Pan extension is slotted to fit onto condensate pan edge and will extend into supply plenum. See Figure 5.
Condensate Pan
A06032
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
When installing over a finished ceiling and/or living area, install a field--fabricated secondary condensate pan under the entire unit.
HORIZONTAL--RIGHT AND HORIZONTAL--LEFT WITH PAN EXTENSION (5 Ton Size Only)
1. There are two separate pan extensions shipped with the unit. For horizontal left installations, use the pan attached to the left shipping bracket. For horizontal right installations, use the pan attached to the right shipping bracket. Be sure to use the correct pan extension for the application. There should not be any gaps between the plastic condensate pan and the pan extension. All condensate should flow from the pan extension to the plastic condensate pan and not leak into the coil cabinet or duct.
NOTE: Discard the pan not used along with both shipping brackets.
2. For horizontal--left installation, install pan extension onto left end of horizontal-- condensate pan. Pan extension is slotted to fit onto condensate pan edge and will extend into supply plenum. See Figure 4.
A09084
Figure 5 -- Horizontal--Right Installation of Pan
Extension
Installation Configurations
These units can be installed on a work platform, secured to roof trusses in the attic, suspended from hangers on floor joists in the crawl space, or installed on blocks. See proper section and figures for detailed installation instructions.
NOTE: Pan extension is needed for both horizontal left and right applications. DO NOT DISCARD.
FURNACE ATTACHMENT
Attach coil to furnace
The attachment plates (3) and filler plate (1) are packaged together and placed in the coil carton. Remove these items, verifying the number of pieces. Use the following procedure to attach ENH4X horizontal coil to furnace.
NOTE: Remove shipping brace from both ends of casing prior to installation. Also remove corrugated shipping block from inside the right end of casing prior to installation.
1. Three attachment plates are used to attach coil to furnace. Application determines which end of the coil will be attached to the furnace.
2. Use self-- tapping screws to mount attachment plates to coil casing. See Figure 6.
484 01 3700 01 3