International Comfort Products ENA4X18L14A, ENA4X19L17A, ENA4X24L14A, ENA4X24L17A, ENA4X30L14A Installation Manual

...
INSTALLATION INSTRUCTIONS
Uncased N Coil, Upflow−Downflow
ENA4X
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
This coil contains Nitrogen precharge of 15 PSI. Release of this pressure through the center of the rubber plugs is required before removing the plugs.
WARNING
!
CAUTION
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
IMPORTANT: Nitrogen can leak out through the hole that the needle pierced in the plugs. This does not indicate a leaking coil nor warrant return of the coil.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 2....................................
INSTALLATION 2.....................................
Inspect Equipment 2................................
Select Installation 3................................
Installation of Evaporator Coil 3......................
Connect Refrigerant Piping 4........................
Connect Refrigerant Liquid and Suction Lines 4........
Condensate Drain Line Connection 5.................
Humidifier Application 6.............................
Table 1
MODEL
NUMBER
ENA4X18L14A 1-1/2
ENA4X19L17A 1-1/2
ENA4X24L14A 2
ENA4X24L17A 2
ENA4X30L14A 2-1/2
ENA4X30L17A 2-1/2
ENA4X31L17A 2-1/2
ENA4X36L17A 3
ENA4X36L21A 3
ENA4X37L17A 3
ENA4X42L21A 3-1/2
ENA4X43L24A 3-1/2
ENA4X48L21A 4
ENA4X48L24A 4
ENA4X60L24A 5
ENA4X61L24A 5
ENA4X Uncased Coil Information
COLLAR SIZE
inches (mm)
Tons
Depth Width Liquid Suction
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
19-3/8
(492)
12-7/8
16-1/4
12-7/8
16-1/4
12-7/8
16-1/4
16-1/4
16-1/4
19-5/8
16-1/4
19-5/8
23-1/8
19-5/8
23-1/8
23-1/8
23-1/8
COIL CONNECTION
(327)
(413)
(327)
(413)
(327)
(413)
(413)
(413)
(498)
(413)
(498)
(587)
(498)
(587)
(587)
(587)
3/8 (10) 5/8 (16)
3/8 (10) 3/4 (19)
3/8 (10) 5/8 (16)
3/8 (10) 5/8 (16)
3/8 (10) 3/4 (19)
3/8 (10) 3/4 (19)
3/8 (10) 3/4 (19)
3/8 (10) 3/4 (19)
3/8 (10) 3/4 (19)
3/8 (10) 7/8 (22)
3/8 (10) 7/8 (22)
3/8 (10) 7/8 (22)
3/8 (10) 7/8 (22)
3/8 (10) 7/8 (22)
3/8 (10) 7/8 (22)
3/8 (10) 7/8 (22)
TUBE SIZE
inches (mm)
Specifications subject to change without notice.
484 01 3801 04 3/28/18
INTRODUCTION
Use this instruction manual to install indoor coils on upflow or downflow furnaces. (See Figure 1) Do not install coil in horizontal position. ENA4X coils have factory−installed thermostatic expansion valves (TXVs) and are used with R410A refrigerant systems.
INSTALLATION
These units can be installed in either upflow or downflow configurations. Before installation, there are several performance requirements that must be considered because poor installation can negatively alter performance. This section will briefly discuss those factors.
Airflow
Airflow amount and distribution are vital to adequate system performance. Problems that can be experienced with incorrect airflow include:
S low system performance S restricted TXV S frosted coil S poor humidity control S water blowoff
When attaching the coil and building the plenum, pay special attention to the effect these details will have on airflow. After system startup, check the cfm to insure that it is correct. (Generally, the cfm should be 350 to 400 cfm/ton during normal cooling operation.)
Condensate Management
With proper installation, these coils will manage the condensate without blowoff into the duct work. See detailed instructions for more info.
Procedure 1 — Inspect Equipment
File claim with shipper if equipment is damaged. The following parts are included with this coil (See Figure 1),
depending on your application different components will be required.
COMPONENT QUANTITY
Support Rails 2
Collar 1
Header Plate 1
Grommets 2
Extension Air Baffles 2
Header Plate 1 pc.
Support Rails 2 pcs.
Extension Air Baffles 2 pcs. (Attached to coil)
Uncased N-coil
Collar 1 pc.
A06362
Figure 1 Uncased NCoil Components
2 484 01 3801 04
Specifications subject to change without notice.
Procedure 2 — Select Installation
Select and follow the installation instruction that best suits your needs:
8QFDVHG 1  &RLO
$SSOLFDWLRQV
5HSODFHPHQW
$SSOLFDWLRQV
&DVHG
&DVHG
$SSOLFDWLRQ
$SSOLFDWLRQV
&DVHG ´ 1 µ
)ROORZ
SURFHGXU H
$
V
3OHQXP
$SSOLFDWLRQV
8QFDVHG ´ $ µ
)ROORZ
SURFHGXU H
%
)LJXUHï 8QFDVHG1ï&RLO$SSOLFDWLRQV
Figure 2 Uncased NCoil Applications
See Table 1 for dimensions and overhang options. Note instructions for placement of coil casing on furnace.
For replacement applications using an existing cased N−coil assembly follow Procedure 3A.
For replacement applications using an existing uncased Acoil plenum installation follow Procedure 3B.
For new applications using a fieldfabricated plenum installation follow Procedure 3C.
Procedure 3 — Installation of Evaporator Coil
!
CAUTION
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Take precautions to ensure Aluminum tubes do not come in direct contact or allow for condensate run off with a dissimilar metal. Dissimilar metals can cause galvanic corrosion and possible premature failure.
1HZ
$SSOLFDWLRQV
3OHQXP
$SSOLFDWLRQV
)ROORZ
SURFHGXUH
&
A06363
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
NOTE: Upflow and downflow applications using an existing A−coil casing is not approved:
N-coils will not properly fit into A-Coil casings and retrofitting is not approved. Only replace an uncased N-coil in a N-coil casing.
3A. Upflow and downflow applications using an existing Ncoil casing.
1. Remove and keep front access and tubing header panel.
2. Remove old Ncoil from casing and discard coil.
3. Slide new Ncoil into casing.
4. Cut holes for liquid, suction and drain connections in
the existing header panel. Use new header plate supplied with coil as template to locate holes. Align header plate to the header panel using the upper hole as indicated in Figure 3.
484 01 3801 04 3
Specifications subject to change without notice.