International Comfort Products DNPWREXH030A01, DNPWREXH022A01, DNPWREXH023A01 Installation Manual

Installation Instructions
ACCESSORY VERTICAL POWER EXHAUST, GAS HEATING/ELECTRIC COOLING,
ELECTRIC COOLING, AND HEAT PUMP UNITS
3 TO 121/2 TON
DNPWREXH030A01, DNPWREXH021A01, DNPWREXH022A01 DNPWREXH023A01, DNPWREXH080A00, DNPWREXH081A00
For Use With Vertical Economizer
TABLE OF CONTENTS
PACKAGE CONTENTS 1............................
UNIT CONFIGURATION TABLE 1....................
PACKAGE USAGE 1................................
SAFETY CONSIDERATIONS 1.......................
GENERAL 1........................................
INSTALLATION 2...................................
Power Exhaust Wiring with Economizer 3.............
Attaching Power Exhaust to the Unit 7................
Install Hinged Door Angle (Small and Large Cabinet) 8...
IMPORTANT: Read these instructions completely before attempting to install the accessory power exhaust.
PACKAGE CONTENTS
QTY CONTENTS
1 Power Exhaust Hood/Fan Assembly
Low Voltage Wiring Harness with plug and 12 in (305mm)
1
gray jumper wire
1 High Voltage Wiring Harness with plug
8 No. 10 x 3/
1 Gasketing Roll
1 Sealing Angle
NOTES:
1. Both wiring harnesses are shipped attached to the power exhaust assembly.
1
in. (19mm) Mounting Screws
4
1
1
UNIT CONFIGURATION TABLE
UNIT
CONFIGURATION
Small Cabinet 46 3/4” x 74 3/8”
Large Cabinet 58 1/2” x 88 1/8”
Extra Large Cabinet 63 3/8” x 115 7/8”
UNIT
FOOTPRINT SIZE
PACKAGE USAGE
UNIT
CONFIGURATION
Small Cabinet
Large Cabinet
Extra Large
Cabinet
NOTE: For 575−v installations, a fieldsupplied and installed transformer (FAST part no. 1171494) must be used with 208/230 V power exhaust.
POWER EXHAUST
PART NUMBER
DNPWREXH030A01
DNPWREXH021A01
DNPWREXH022A01
DNPWREXH023A01
DNPWREXH080A00
DNPWREXH081A00
POWER EXHAUST
VOLTAGE
208/230 V,1 Ph
460 V, 3 Ph
208/230 V, 1 Ph
460 V, 3 Ph
208/230 V, 1 Ph
460 V, 3 Ph
SAFETY CONSIDERATIONS
Installation and servicing of airconditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Recognize safety information. This is the safety−alert symbol . When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
GENERAL
The accessory vertical power exhaust is used in conjunction with the vertical Economizer accessories. For horizontal applications, this power exhaust accessory cannot be used. The horizontal power exhaust accessory must be used for horizontal applications. See Table 1 for Economizer usage. See Fig. 1 for dimensions.
Table 1 – Accessory Vertical Economizer Use
PART NO. DESCRIPTION
DNECOMZR020A02
DNECOMZR021A03
DNECOMZR062A00
Economizer with W7212 controller.
509 06 2302 01 8/22/11
Fig. 1 Dimensions, Economizer with Power Exhaust
X
ECONOMIZER INLET
Y
POWER EXHAUST OUTLET
Z
UNIT
CONFIGURATION
Small Cabinet
Large Cabinet
Extra-Large Cabinet
NOTE: Measurements are in inches (mm)
X
18.5 (470)
26 (660)
28.6 (725)
Y
19.25 (515)
25 (635)
37.75 (960)
Z
7
(11)
16
/
0 (0)
4.5 (115)
INSTALLATION
IMPORTANT: Follow all applicable local and national elec-
trical codes when installing this accessory. Follow all local and NEC (National Electrical Code) codes.
If a single power source is to be used, size the wire to include power exhaust MCA and MOCP. (See Table 2.)
Table 2 – Power Exhaust Electrical Data
POWER EXHAUST
PART NO.
DNPWREXH030A01
DNPWREXH021A01
DNPWREXH022A01 DNPWREXH080A00
DNPWREXH023A01 DNPWREXH081A00
LEGEND MCA - Minimum Circuit Amps MOCP- Maximum Overcurrent Protection N/A - Not Applicable
MCA
(230 v)
N/A 0.9 N/A 15
N/A 1.8 N/A 15
MCA
(460 v)
1.5 N/A 0.64 15
3.3 N/A 1.32 15
MCA
(575 v)
NOTE: For R−410A units, refer to unit nameplate for MCA and MOCP for installed power exhaust. For R22 units, use the calculations detailed below.
MOCP
(for separate
power source)
Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a R22 gas heat, electric cooling,
6ton unit with MCA = 28.9 and MOCP = 35, with DNPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.5 amps = 30.4 amps If the new MCA does not exceed the published MOCP,
then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
NOTE: For 575−v installations, a fieldsupplied and installed transformer (FAST part no. 1171494) must be used with 208/230−v power exhaust. (See Fig. 6.)
The vertical power exhaust can be used with the following type of economizer
S Economizer with controller W7212.
To install the vertical power exhaust, perform the following procedure:
1. Turn off unit power supply and install lockout tag. For gas units, turn off the gas supply.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury and/or death.
Before beginning any modification, be certain the mainline electrical disconnect switch is in the OFF position. Close the main gas supply shutoff valve. Tag disconnect switch and gas valve with suitable warning labels.
NOTE: Before installing, ensure voltage of power exhaust agrees with power supply to the equipment.
2. Remove the power exhaust knockout plugs located on the lower left side of the Economizer. (See Fig. 2.)
Fig. 2 Power Exhaust Knockout Location
509 06 2302 01
ECONOMIZER
POWER EXHAUST KNOCKOUTS
2
3. Remove the RTU unit filter panel to allow access to the inside of the rooftop.
4. The panel covering the horizontal return opening on the unit may also be removed for easier access and installation. Be sure to replace this panel when install­ation is complete.
5. Install the vertical economizer per the instructions provided with the economizer. Do not install the rain­hood shipped with the Economizer. Set aside the alu­minum air filter for use with the power exhaust.
6. Remove fan shield so power exhaust can lay flat without bending the shield or damaging the roof.
7. Remove the shipping blocks from the bottom of the ac­cessory vertical power exhaust. (See Fig. 3.)
Fig. 3 Shipping Block Removal
8. There may be a hinged door panel in place of the filter panel. Open the hinged door, remove the screws and hinges, remove the door and set it aside. Keep all screws and hinges.
9. Place the power exhaust close to the Economizer to allow for wiring harness connection.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be careful to route wires to avoid pinching or cutting during assembly. It can be difficult to protect the wires while attaching the power exhaust to the unit.
10. Follow the wiring instructions specific to the Econom­izer. Be sure power exhaust wiring does not interfere with damper operation.
Power Exhaust Wiring with Economizer
Use these instructions and diagrams if using the vertical power exhaust with Economizer.
1. The 2−wire low voltage harness from the power ex- haust and the 24 or 36 in (610 or 915 mm) low voltage extension harness are plugged together for shipping. Unplug these 2 harnesses for installation.
2. Insert the 2−wire low voltage harness plug from the power exhaust into the top knockout on the econom­izer. (See Fig. 2.)
3. From the rear of the economizer, connect the 24 in (610) long low voltage extension harness plug to the power exhaust harness.
4. Route the other end of the low voltage extension har­ness to the economizer controller. (See Fig. 4.) The harness is connected to the controller by connecting the tan wire to the tan wire 24 VAC COM terminal on the controller. The terminal on the gray wire is connec­ted to terminal EF1 on the controller. See Fig. 5 and 6 for economizer wiring diagrams. Install the gray jumper wire on the controller from the exhaust fan terminal (EF), to the 24 VAC HOT terminals. The gray jumper is shipped wire tied to the control harness.
5. The high voltage harness from the power exhaust and the high voltage extension harness are plugged together for shipping. Unplug these 2 harnesses for installation.
6. Insert the high voltage harness plug from the power exhaust into the bottom knockout on the economizer. (See Fig.2 and 4.)
R410A Rooftop Models Only — For single point wiring application, connect the power exhaust power wire harness to the compressor contactor or indoor fan contactor in the control box. Install the power exhaust power wire harness into the pressure lugs on the compressor contactor or indoor fan contactor, used for the field power wiring also.
Proceed to steps 7 and 8 for details on completing connection and routing.
7. From the rear of the economizer, connect the long high voltage extension harness plug to the power exhaust harness. (See Fig. 4.)
8. Route the other end of the long high voltage extension harness through the HVAC unit to the control box. (See Fig. 5.) The harness must be routed through the grommets provided in the unit. Do not drill routing holes. Be careful not to route the power exhaust harness on top of the indoor coil. Wire the end of the high voltage harness extension to the power exhaust power source. (See Fig. 6 and 7.)
3
509 06 2302 01
Fig. 4 Power Exhaust Harness Installation for Economizer with W7212 Controller
COIL
FILTERS
HVAC UNIT
W7212 CONTROLLER
24IN (610mm) LOW VOLTAGE EXTENSION HARNESS
ECONOMIZER Cover panel
over horizontal return
2WIRE LO W VOLTAGE HARNESS
ECONOMIZER/POWER EXHAUST OUTDOOR AIR HOOD
134IN. (3406mm) OR 194IN. (4928mm) HIGH VOLTAGE EXTENSION HARNESS
Fig. 5 Power Line Harness Routing (Top View of Unit Shown)
MAIN POWER
Note 1
KNOCKOUTS
UNIT ROOF CURB
HIGH VOLTAGE HARNESS
ROOF
HIGH & LOW VOLTAGE WIRING HARNESS
ECONOMIZER
Low Voltage Harness
note 1
FILTER
COIL
High Voltage
Harness
INDOOR
FAN
POWER EXHAUST (INSTALLED POSITION)
509 06 2302 01
Field supplied
connectors
RTU CONTROL
BOX
note 1
Note: Ensure main power line, disconnect, and fuse/breaker are sized per National Electric Guide.
4
Fig. 6 Power Exhaust Wiring for Economizer with Controller W7212 — 208/230 V and 575 V Units
FIELD
POWER
SUPPLY
BLK
YEL
BLU
GRN/YEL
To C11 for Small and Large Cabinet To IFC11 for ExtraLarge Cabinet
To C13 for Small and Large Cabinet
To IFC13 for ExtraLarge Cabinet
GRD.
POWER LINE
PLUG
3
1
2
4
OR
FIELD SUPPLIED
2 X 4 JUNCTION BOX
GROUND
FOR 575V POWER SUPPLY
FOR 208/230V SEPARATE POWER SUPPLY
GREEN YELLOW
C1
GREEN YELLOW
BROWN
GRD.
13
4
79
AB
REL AY
NOTES:
1
2
3
4
BL ACK
BL ACK
GREEN
3
BL ACK
1
RED
2
4
3
1
2
4
TO 575V POWER
575V
PRIMARY
SECONDARY
220V
RED
EXH.
FA N #1
TRANSFORMER
No. 1171494 Field Supplied
AND INSTALLED)
BL ACK
BLUE
C2
BL ACK
BL ACK
6
BLUE
EXH.
FAN #2
TO ECONOMIZER
ACTUATOR
BROWN
END
SWITCH
PLUG
TA N
1 2
3
GRAY GRAY
4
TA N
TA N
1 2
3
4
3
Field Supplied Wiring
575 V transformer No. 1171494 is ordered separately from power exhaust.
Economizer actuator and controller are shipped with the Economizer not with power exhaust.
Connections from End Switch plug to Economizer controller are made by installer.
If a single power source is to be used, size wire to include power exhaust MCA and MOCP.
For R410A units, refer to unit nameplate for MCA and MOCP for installed power exhaust.
WHITE
GRAY
BL ACK
RED
POWER EXHAUST ACCESSORY
2
ECONOMIZER CONTROLLER
24 VAC HOT
24 VAC COM
+
EF 1
EF
2
For R22 units, use the following calculations Check MCA and MOCP when power exhaust is powered
through the unit. Determine the new MCA including the
FIELD
SUPPLIED
FUSED
DISCONNECT
power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using an electric cooling, 6ton
R22 unit with MCA + 28.9 and MOCP = 35, with DNPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.5 amps = 30.4 amps If the new MCA does not go over the MOCP published,
then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
C10426
5
509 06 2302 01
Fig. 7 Power Exhaust Wiring for Economizer with Controller W7212 — 460 V Units
FIELD
POWER
SUPPLY
BLK
YEL
BLU
GRN/YEL
To C11 for Small and Large Cabinet To IFC11 for ExtraLarge Cabinet
To C13 for Small and Large Cabinet
To IFC13 for Extra−Large Cabinet
EQUIP
GND
GREEN
GROUND
FIELD
SUPPLIED
FUSED
DISCONNECT
SEPARATE
POWER
SOURCE
BL ACK
RED
WHITE
POWER
FIELD SUPPLIED
2 x 4 JUNCTION BOX
BL ACK
LINE
PLUG
1
2
3
4
OR
GREEN YELLOW
GRAY GRAY
BLUE
BROWN
REL AY #1
3
23
5
6
9
8
B
WHITE
WHITE
GRD
BL ACK
FAN #2
BL ACK
112
4
7
A
4
7
A
1
2
3
4
EXH.
FAN #1
BL ACK
RED GREEN
EXH.
BROWN
5
8
GRAY
GRAY
BLUE
REL AY #2
6
9
B
TA N
GRAY
POWER EXHAUST ACCESSORY
1
END
SWITCH
PLUG
1
4
TO ECONOMIZER
ACTUATOR
TA N
1
22
GRAY
33
GRAY
4
2
Field Supplied Wiring
1
2
3
4
NOTES:
Economizer actuator and controller are shipped with the Economizer
1
not with power exhaust. Connections from End Switch Plug to the Economizer controller are made
2
by installer.
If a single power source is to be used, size wire to include power exhaust
3
MCA and MOCP. For R410A units, refer to the unit nameplate for MCA and MOCP for
installed power exhaust. For R22 units use the following calculations Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using an electric cooling, 6ton R22 unit with MCA = 28.9 and MOCP = 35, with DNPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.5 amps = 30.4 amps If the new MCA does not go over the MOCP published, then MOCP would
not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is OK. If “MCA NEW” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
BL ACK
WHITE
TA N
ECONOMIZER CONTROLLER
RED
24V HOT
24V COM
+
EF
1
EF 1
C10427
509 06 2302 01
6
Attaching Power Exhaust to the Unit
1. Make sure all power exhaust harnesses are connected as indicated in the previous steps. See Fig. 6 and 7 for Economizer.
2. Make sure all wiring is secure. Use field−supplied wire ties if necessary. Be sure that wiring does not interfere with operation of the HVAC unit, economizer, or power exhaust.
3. For units with a standard filter panel (i.e., no hinged door): Install the gasketing (provided) on the back of power exhaust side mating flanges. (See Fig. 8)
NOTE: This step does not apply to units with a hinged door.
Fig. 8 Gasketing Location Detail (Standard Filter Panel Only)
UNIT CORNER POST
GASKETING
POWER EXHAUST
4. Lift power exhaust and install over economizer using the #10 x 3/4 in. long screws provided. Make sure wir­ing harnesses are properly secured. (See Fig. 9)
Fig. 9 Power Exhaust Installed on Unit
ALUMINUM
CONTROLLER
FILTER
POWER EXHAUST
5. Locate the aluminum filter shipped with the econom­izer. Open the filter clips under the top hood of the power exhaust. Slide aluminum filter into the outside air opening of the power exhaust. Filter will slide past filter clips. Close filter clips, which will lock filter in place.
6. Reinstall the fan shield.
7. Return power to unit and remove lockout tag.
8. Test power exhaust operation by setting the power ex­haust set point on the economizer controller to 0%. Power exhaust performance is shown in Fig. 10.
9. Adjust the power exhaust set point on the Economizer controller to the desired activation point per unit schematic.
10. For units with a standard filter access panel, reinstall the unit filter access door.
For units with a hinged access door (Small & Large Cabinet), install the hinged door seal angle included in the power exhaust kit using the instructions in this instruction. Do not proceed unless the sealing angle is installed. Units with a hinged door that do not have a sealing angle may not have a watertight seal.
Fig. 10 Power Exhaust Performance
5000
4000
3000
EXHAUST
2000
AIRFLOW (cfm)
1000
0
0 0.1 0.2 0.3 0.4 0.5
RETURN DUCT STATIC PRESSURE (in wc)
Small Cabinet
Large and Extra-Large Cabinet
7
509 06 2302 01
Install the Hinged Door Angle (Small and Large Cabinet)
Follow these instructions if the unit has a hinged panel instead of a standard filter panel. Hinged Door Angle DNPECONV003A00 is for 3 to 5 ton units and DNPECONV004A00 is for 6 to 10 ton units.
1. Find the sealing angle and three screws provided in the power exhaust kit.
2. Attach the sealing angle to the top of the power ex­haust hood using the screws provided. Refer to Fig.
14. Note that the gasketing flange will be facing out.
3. If there are NO predrilled holes in the Power Exhaust hood: Lay the hinged panel, insulation side up, on top of the hood so that the hinge screw holes align with the pre−drilled screw holes in the sealing angle. (For hoods with predrilled holes, skip to Step 7.)
4. Check the alignment of the hinged door with the side of the filter opening to be sure it will close properly.
5. Use a pencil to mark the hood where the screw holes will be.
6. Remove the hinged door and drill four (4) 11/64 in. holes where the marks are.
Fig. 11 Power Exhaust Installation
Fig. 12 Install Sealing Angle
SEE NOTE
SEE NOTE
GASKETED FLANGE
SEALING ANGLE
Fig. 13 ReInstall the Hinged Door
SEALING ANGLE
POWER EXHAUST HOOD
SCREW ANGLE TO HOOD (3)
HINGED DOOR
GASKET LOCATION (STANDARD FILTER PAN E L ONLY)
POWER EXHAUST SIDE FLANGES
GASKET LOCATION
NOTE: The sealing angle will be in place; use the holes in it as a guide.
7. Place the door and hinges back on the unit. Screw through the door hinges and sealing angle into the flanged top of the hood using the 4 screws set aside when the hinged door was removed. (See Fig. 13.)
8. Close the hinged door and adjust handles if necessary.
509 06 2302 01
8
Loading...