International Comfort Products DNPWREXH030A01, DNPWREXH022A01, DNPWREXH023A01 Installation Manual

Installation Instructions
ACCESSORY VERTICAL POWER EXHAUST, GAS HEATING/ELECTRIC COOLING,
ELECTRIC COOLING, AND HEAT PUMP UNITS
3 TO 121/2 TON
DNPWREXH030A01, DNPWREXH021A01, DNPWREXH022A01 DNPWREXH023A01, DNPWREXH080A00, DNPWREXH081A00
For Use With Vertical Economizer
TABLE OF CONTENTS
PACKAGE CONTENTS 1............................
UNIT CONFIGURATION TABLE 1....................
PACKAGE USAGE 1................................
SAFETY CONSIDERATIONS 1.......................
GENERAL 1........................................
INSTALLATION 2...................................
Power Exhaust Wiring with Economizer 3.............
Attaching Power Exhaust to the Unit 7................
Install Hinged Door Angle (Small and Large Cabinet) 8...
IMPORTANT: Read these instructions completely before attempting to install the accessory power exhaust.
PACKAGE CONTENTS
QTY CONTENTS
1 Power Exhaust Hood/Fan Assembly
Low Voltage Wiring Harness with plug and 12 in (305mm)
1
gray jumper wire
1 High Voltage Wiring Harness with plug
8 No. 10 x 3/
1 Gasketing Roll
1 Sealing Angle
NOTES:
1. Both wiring harnesses are shipped attached to the power exhaust assembly.
1
in. (19mm) Mounting Screws
4
1
1
UNIT CONFIGURATION TABLE
UNIT
CONFIGURATION
Small Cabinet 46 3/4” x 74 3/8”
Large Cabinet 58 1/2” x 88 1/8”
Extra Large Cabinet 63 3/8” x 115 7/8”
UNIT
FOOTPRINT SIZE
PACKAGE USAGE
UNIT
CONFIGURATION
Small Cabinet
Large Cabinet
Extra Large
Cabinet
NOTE: For 575−v installations, a fieldsupplied and installed transformer (FAST part no. 1171494) must be used with 208/230 V power exhaust.
POWER EXHAUST
PART NUMBER
DNPWREXH030A01
DNPWREXH021A01
DNPWREXH022A01
DNPWREXH023A01
DNPWREXH080A00
DNPWREXH081A00
POWER EXHAUST
VOLTAGE
208/230 V,1 Ph
460 V, 3 Ph
208/230 V, 1 Ph
460 V, 3 Ph
208/230 V, 1 Ph
460 V, 3 Ph
SAFETY CONSIDERATIONS
Installation and servicing of airconditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Recognize safety information. This is the safety−alert symbol . When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
GENERAL
The accessory vertical power exhaust is used in conjunction with the vertical Economizer accessories. For horizontal applications, this power exhaust accessory cannot be used. The horizontal power exhaust accessory must be used for horizontal applications. See Table 1 for Economizer usage. See Fig. 1 for dimensions.
Table 1 – Accessory Vertical Economizer Use
PART NO. DESCRIPTION
DNECOMZR020A02
DNECOMZR021A03
DNECOMZR062A00
Economizer with W7212 controller.
509 06 2302 01 8/22/11
Fig. 1 Dimensions, Economizer with Power Exhaust
X
ECONOMIZER INLET
Y
POWER EXHAUST OUTLET
Z
UNIT
CONFIGURATION
Small Cabinet
Large Cabinet
Extra-Large Cabinet
NOTE: Measurements are in inches (mm)
X
18.5 (470)
26 (660)
28.6 (725)
Y
19.25 (515)
25 (635)
37.75 (960)
Z
7
(11)
16
/
0 (0)
4.5 (115)
INSTALLATION
IMPORTANT: Follow all applicable local and national elec-
trical codes when installing this accessory. Follow all local and NEC (National Electrical Code) codes.
If a single power source is to be used, size the wire to include power exhaust MCA and MOCP. (See Table 2.)
Table 2 – Power Exhaust Electrical Data
POWER EXHAUST
PART NO.
DNPWREXH030A01
DNPWREXH021A01
DNPWREXH022A01 DNPWREXH080A00
DNPWREXH023A01 DNPWREXH081A00
LEGEND MCA - Minimum Circuit Amps MOCP- Maximum Overcurrent Protection N/A - Not Applicable
MCA
(230 v)
N/A 0.9 N/A 15
N/A 1.8 N/A 15
MCA
(460 v)
1.5 N/A 0.64 15
3.3 N/A 1.32 15
MCA
(575 v)
NOTE: For R−410A units, refer to unit nameplate for MCA and MOCP for installed power exhaust. For R22 units, use the calculations detailed below.
MOCP
(for separate
power source)
Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a R22 gas heat, electric cooling,
6ton unit with MCA = 28.9 and MOCP = 35, with DNPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.5 amps = 30.4 amps If the new MCA does not exceed the published MOCP,
then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
NOTE: For 575−v installations, a fieldsupplied and installed transformer (FAST part no. 1171494) must be used with 208/230−v power exhaust. (See Fig. 6.)
The vertical power exhaust can be used with the following type of economizer
S Economizer with controller W7212.
To install the vertical power exhaust, perform the following procedure:
1. Turn off unit power supply and install lockout tag. For gas units, turn off the gas supply.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury and/or death.
Before beginning any modification, be certain the mainline electrical disconnect switch is in the OFF position. Close the main gas supply shutoff valve. Tag disconnect switch and gas valve with suitable warning labels.
NOTE: Before installing, ensure voltage of power exhaust agrees with power supply to the equipment.
2. Remove the power exhaust knockout plugs located on the lower left side of the Economizer. (See Fig. 2.)
Fig. 2 Power Exhaust Knockout Location
509 06 2302 01
ECONOMIZER
POWER EXHAUST KNOCKOUTS
2
3. Remove the RTU unit filter panel to allow access to the inside of the rooftop.
4. The panel covering the horizontal return opening on the unit may also be removed for easier access and installation. Be sure to replace this panel when install­ation is complete.
5. Install the vertical economizer per the instructions provided with the economizer. Do not install the rain­hood shipped with the Economizer. Set aside the alu­minum air filter for use with the power exhaust.
6. Remove fan shield so power exhaust can lay flat without bending the shield or damaging the roof.
7. Remove the shipping blocks from the bottom of the ac­cessory vertical power exhaust. (See Fig. 3.)
Fig. 3 Shipping Block Removal
8. There may be a hinged door panel in place of the filter panel. Open the hinged door, remove the screws and hinges, remove the door and set it aside. Keep all screws and hinges.
9. Place the power exhaust close to the Economizer to allow for wiring harness connection.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be careful to route wires to avoid pinching or cutting during assembly. It can be difficult to protect the wires while attaching the power exhaust to the unit.
10. Follow the wiring instructions specific to the Econom­izer. Be sure power exhaust wiring does not interfere with damper operation.
Power Exhaust Wiring with Economizer
Use these instructions and diagrams if using the vertical power exhaust with Economizer.
1. The 2−wire low voltage harness from the power ex- haust and the 24 or 36 in (610 or 915 mm) low voltage extension harness are plugged together for shipping. Unplug these 2 harnesses for installation.
2. Insert the 2−wire low voltage harness plug from the power exhaust into the top knockout on the econom­izer. (See Fig. 2.)
3. From the rear of the economizer, connect the 24 in (610) long low voltage extension harness plug to the power exhaust harness.
4. Route the other end of the low voltage extension har­ness to the economizer controller. (See Fig. 4.) The harness is connected to the controller by connecting the tan wire to the tan wire 24 VAC COM terminal on the controller. The terminal on the gray wire is connec­ted to terminal EF1 on the controller. See Fig. 5 and 6 for economizer wiring diagrams. Install the gray jumper wire on the controller from the exhaust fan terminal (EF), to the 24 VAC HOT terminals. The gray jumper is shipped wire tied to the control harness.
5. The high voltage harness from the power exhaust and the high voltage extension harness are plugged together for shipping. Unplug these 2 harnesses for installation.
6. Insert the high voltage harness plug from the power exhaust into the bottom knockout on the economizer. (See Fig.2 and 4.)
R410A Rooftop Models Only — For single point wiring application, connect the power exhaust power wire harness to the compressor contactor or indoor fan contactor in the control box. Install the power exhaust power wire harness into the pressure lugs on the compressor contactor or indoor fan contactor, used for the field power wiring also.
Proceed to steps 7 and 8 for details on completing connection and routing.
7. From the rear of the economizer, connect the long high voltage extension harness plug to the power exhaust harness. (See Fig. 4.)
8. Route the other end of the long high voltage extension harness through the HVAC unit to the control box. (See Fig. 5.) The harness must be routed through the grommets provided in the unit. Do not drill routing holes. Be careful not to route the power exhaust harness on top of the indoor coil. Wire the end of the high voltage harness extension to the power exhaust power source. (See Fig. 6 and 7.)
3
509 06 2302 01
Loading...
+ 5 hidden pages