International Comfort Products DNECOMZR052A00, DNECOMZR053A00 Installation Manual

Installation Instructions
DNECOMZR052A00 and DNECOMZR053A00
Vertical and Horizontal Economizer IV Accessory
Medium Rooftop Units 15 to 25 Tons
TABLE OF CONTENTS
PACKAGE USAGE 1..............................
PACKAGE CONTENTS 1..........................
GENERAL 2.....................................
ACCESSORIES LIST 2............................
HORIZONTAL INSTALLATION 6...................
CONFIGURATION 8..............................
OPERATION 12..................................
TROUBLESHOOTING 13..........................
IMPORTANT: Read these instructions completely before attempting to install the accessory Economizer IV.
PACKAGE USAGE
UNIT SIZE PART NUMBER
15, 17.5, 20 Ton DNECOMZR052A00
25 Ton DNECOMZR053A00
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National Standards of Canada CAN/CSA-B149.1 and .2 Natural Gas and Propane Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used
Specifications subject to change without notice.
to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service and maintenance operations on unit, turn off main power switch to unit. If gas unit, shut off gas supply before shutting off main power.
TAG DISCONNECT SWITCH WITH A SUITABLE LOCK AND WARNING LABEL.
UNIT QTY CONTENTS
1 Damper Assembly
1 Upper End Economizer Panel
Bottom Panel w/Relief Damper (for
1
vertical only)
1 Bottom Panel #2 (for horizontal only)
Side Replacement Panel (for
1
horizontal only)
4 Hood Angles
DNECOMZR052A00
DNECOMZR053A00
2 Hood Side Plates
1 Hood Top
2 Side Filter Supports
2 Side Drip Angles
2 Top Hood Diverters
1 Supply Air Temperature Sensor (SAT)
60 Screws
1 Seal Strip
1 Damper Assembly
1 Upper End Economizer Panel
Bottom Panel w/Relief Damper (for
1
vertical only)
1 Bottom Panel #2 (for horizontal only)
1 Hood Angles
4 Hood Side Panels
2 Hood Top
1 Outdoor Air Screens
4 Side Filter Supports
2 Side Drip Angles
2 Top Hood Diverters
1 Supply Air Temperature Sensor (SAT)
60 Screws
1 Seal Strip
513 06 2401 01 March 2010
Table 1 Economizer IV Sensor Usage
Economizer IV WITH OUTDOOR AIR
APPLICATION
Outdoor Air Dry Bulb None. The outdoor air dry bulb sensor is factory installed.
Single Enthalpy AXB078ENT
Differential Enthalpy AXB078ENT and DNENTDIF004A00*
CO2 for DCV Control using a DuctMounted CO2 Sensor DNCBDIOX005A00
* DNENTDIF004A00 and DNTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.
a. For units with two position damper installed,
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury and/or death.
Disconnect power supply and install lockout tag before attempting to install the accessory.
remove the outside air hood. Unplug the damper actuator and remove assembly from unit.
b. For units with manual damper installed, remove
the manual damper and hood.
3. Remove the upper panel and bottom panel (provided with the HVAC unit) on the end of the unit to expose the return section. (See Figure 1) Save the screws for use later when replacing the panel. The panels can be discarded.
DRY BULB SENSOR
Accessories Required
GENERAL
!
The Economizer IV system utilizes the latest technology available for integrating the use of free cooling with mechanical cooling for packaged rooftop units. The solid-state control system optimizes energy consumption, zone comfort, and equipment cycling by operating the compressors when the outdoor-air temperature is too warm, integrating the compressor with outdoor air when free cooling is available, and locking out the compressor when outdoor-air temperature is too cold. Demand ventilation is supported.
The Economizer IV system utilizes gear-drive technology with a direct-mount spring return actuator that will close upon loss of power. The Economizer IV system comes standard with an outdoor air temperature sensor, supply air temperature sensor, and low temperature compressor lockout switch. indoor enthalpy and outdoor enthalpy sensors are available for field installation. Field-installed CO
Barometric relief dampers provide natural building pressurization control. Barometric relief dampers are built into the design and are standard. An optional power exhaust system is available for applications requiring even greater exhaust capabilities. The power exhaust set point is adjustable at the Economizer IV controller.
See Package Contents and Package Usage tables for more information. See Table 1 for sensor usage.
sensors are available.
2
ACCESSORIES LIST
The Economizer IV has several field-installed accessories available to optimize performance. Refer to Table 2 for authorized parts.
Table 2
Power Exhaust 208230 v 3 Ph DNPWREXH068A00
Power Exhaust 460 v 3 Ph DNPWREXH069A00 Power Exhaust 575 v 3 Ph DNPWREXH070A00
Outdoor Air Enthalpy Sensor AXB078ENT
Indoor Air Enthalpy Sensor DNENTDIF004A00
Return Air CO2 Sensor (4 to 20 mA) DNCBDIOX005A00
Economizer IV FieldInstalled Accessories
DESCRIPTION PART NUMBER
VERTICAL INSTALLATION
These economizers are designed to work in both a vertical and horizontal applications. These instructions are for a vertical installation.
1. Turn off unit power supply and install lockout tag.
2. Prepare the unit for economizer installation:
2
Specifications subject to change without notice.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and damage to unit.
Cover the duct opening as a precaution so objects cannot fall into the return duct opening. Be sure to remove the cover when installation is complete.
Figure 1 Upper and Bottom Panel on End of Unit
Upper End Panel
Shipped on Base Unit
Bottom Panel
Shipped on Base Unit
4. Remove the unit's left side corner post and left side panel from the unit to allow for easy econom izer installation. (See Figure 2)
5. Install economizer, as shown in Figure 2, into the return air section of the unit. Be careful not to pinch the wires during installation. Bottom of eco nomizer will rest on the base of the unit. (See Figure 5)
6. Reinstall the left side corner post on to the unit. Note the corner post will sit behind the economizer flange. (See Figure 3) Screw through the corner post and through the economizer. (See Figure 3 and Figure 4)
7. Insert provided screw through the bottom left rear of the economizer and into the unit base. (See Figure 5) Reinstall the unit's left side panel.
8. Before the economizer is secured in place on the right hand side, remove and save the 12-pin jump er plug from the unit wiring harness. (See Figure 6) Insert the economizer plug into the unit wiring harness plug.
NOTE: The 12-pin jumper plug should be saved for future use in the event that the Economizer IV is removed from the unit. The jumper plug is not needed as long as the Economizer IV is installed.
CAUTION
Indoor-fan Panel
C09327
513 06 2401 01
Figure 2 Unit Left Side Panel and Corner Post
Unit's Left Left Corner Post
Economizer IV
Side Panel
C09328
Figure 3 Top View
9. Remove the indoor-fan motor access panel. (See Figure 1)
10. Install the supply air temperature sensor (SAT). The sensor looks like and eyelet terminal with 2 attached wires, and is shipped in the economizer hardware bag. The sensor is located on the “crimped” end and is sealed for moisture. Mount the SAT to the indoor blower housing. (See Figure 7) Use the provided screw to secure in place. Attach the PINK and VIOLET wires in the unit to the sensor.
11. Replace the indoor-fan motor access panel.
12. Install the bottom panel with the relief damper at tached on the unit. (See Figure 8) Screw panel in place.
NOTE: Remove the bottom screw holding the relief blade closed.
13. Install the upper end economizer panel over the economizer's outside air damper, and above the bottom panel. Screw panel in place and screw panel into economizer in two places. (See Figure 8)
Figure 6 Unit Wiring Harness
Figure 4 Front Left View
Economizer Outside Air Damper
Insert Screw
Left Front Corner Post
Insert Screw
Figure 5 Side View
C09329
C09330
C09332
513 06 2401 01
C09331
Specifications subject to change without notice.
3
Figure 7 Blower Housing
V
C09333
Figure 8 End View of Unit
Insert (2) screws thru panel and into economizer
Provided Upper Panel
Economizer Outside Air Damper
Provided Bottom Panel with Relief
Relief Damper
Remove shipping screw
C09334
Figure 9 Economizer IV Component Locations
Outside Air Damper
Economizer Actuator
Low Temp. Lockout
Economizer I Controller
Wiring Harness
g. Install the side filter supports using the screws
provided.
h. Install the side drip edge angles using the
screws provided.
i. Run a continuous length of seal strip across
the hood covering the engagement hole in the lower hood.
j. Install top diverter using screws provided.
15. Install the hood assembly on to the unit. (See Figure 11 and Figure 12)
16. Through the outdoor air hood, review and adjust the Economizer IV controller settings. See “Opera tion” section of this manual for details.
a. The standard Economizer IV controller has a
factory setting of 63 F for the outdoor air tem perature changeover and 55F (fixed) for the supply air temperature sensor. The outdoor air temperature changeover setting is adjusted on the sensor by setting the dip switches on the sensor. See Fig 19. The ABCD potentiometer on the controller should be set to the “D” posi tion.
b. The low temperature compressor lockout
switch is fixed at 42F.
c. The minimum position for the outdoor air
damper can be configured for specific job re quirements at the controller. When not using with a CO2 sensor, the DCV Max potentiomet er on the controller must be fully closed (CCW) for the Minimum Position potentiometer to func tion correctly.
d. Settings for the optional outdoor enthalpy
sensor, indoor enthalpy sensor, power exhaust, and CO troller.
sensor can be configured at the con
2
17. Install the hood screens and other approved Economizer IV accessories.
Outside Air Temp (OAT) sensor
Return Air Damper
C09335
14. Assemble the outside air hood per Figure 10 and Figure 11.
a. Install four hood angles to the upper end panel
using the screws provided.
b. Apply seal strip to mating flanges on the side
plates of the hood and the hood top.
c. Secure the hood side plates to the panel using
screws provided.
d. On 44 inch chassis, remove screws across top
cover. Attach hood top to hood side plates (on 44 inch chassis, flange will slide behind flange of top cover).
e. On 44 inch chassis, reinstall the screws previ
ously removed. On the 52 inch chassis, secure top flange using screws provided in kit.
f. Install the front outdoor air screens by sliding
them into the channel formed by the four angles installed previously. Make sure the screens extend across the entire length of the hood.
NOTE: Screens may be left out at this time to allow for Economizer IV adjustments.
4
Specifications subject to change without notice.
513 06 2401 01
Figure 10 Hood Assembly
A
pply Seal Strips to the back of these flanges
2
Seal Strips
Figure 11 Hood Assembly
5
Apply Seal Strip to the front of this flange
6
Apply Seal Strips to the back of these surfaces
7
4
Item # Description Qty 1 Angles 4 2 Side Plates 2 3 Hood 1 4 Outdoor Air Screens 4 5 Side Filter Supports 2 6 Side Drip Angles 2 7 Top Diverters 2
4
1
3
7
4
Apply Seal Strip to the back of this flange
Apply Seal Strip to the front of this flange
4
2
5
6
C09079
C09090
Figure 12 Hood Assembly Installed on Unit
Outdoor Air Hood
Relief Damper
C09338
513 06 2401 01
Specifications subject to change without notice.
5