International Comfort Products CPMANDPR007A00, CPMANDPR008A00, CPMANDPR009A00 Installation Manual

SMALL PACKAGED PRODUCT (2 - 5 TONS)
B
A
Part Number:
MANUAL HOOD PACKAGE WITH FILTER RACKS
CPMANDPR007A00, CPMANDPR008A00 and CPMANDPR009A00
Installation Instructions
Read these instructions completely before attempting to install the accessory manual outside air packages
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and qualied
personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions
be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and labels attached to or shipped with the unit and other safety precautions that may apply. Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective
clothing, and work gloves. Have re extinguisher available.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Recognize safety information. This is the safety alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal
words: DANGER, WARNING, and CAUTION. These words are used with the safety alert symbol. DANGER identies the most
serious hazards which will result in severe personal injury or death.
WARNING signies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is
used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
General
These accessory manual outside air damper packages can be used in either a horizontal or vertical discharge application. In addition to the
package including the hood / damper, a lter rack is also included. Use caution not to damage indoor coil during installation of the lter racks.
Vertical Return Installation: Hood Package
1. Remove the cover panel shipped on the HVAC unit covering the horizontal return air opening. It can be discarded. NOTE: Some 1
Phase units may not have horizontal cover panels.
2. Caulk or gasket the back of the mating anges on the Replacement
Panel shipped with this package. Install the panel over the horizontal
return air opening on the HVAC unit. Screw in place through pre­punched holes. See Fig. 1.
3. Caulk or gasket the back side of the manual outside air hood. Secure the hood to the Replacement Panel as shown in Fig. 2. Screw in place through pre-punched holes.
4. Set the adjustable damper inside the hood to allow for the desired
outside air intake. Blade will lock in place.
TABLE 1
Part No. A B
CPMANDPR007A00 11 7/16” (289mm) 17 7/16” (447mm)
CPMANDPR008A00 15 9/16” (395mm) 17 5/8” (447mm)
CPMANDPR009A00 15 9/16” (395mm) 17 5/8” (447mm)
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. Disconnect power supply and install lockout tag before attempting to install accessory.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate clothing.
HVAC Unit
Supply Duct Cover (not provided on some HVAC units)
Replacement Panel
Manual outside air hood
Horizontal return opening
Fig. 1 - Hood Installation - Vertical Application
1
Filter Access Door on HVAC Unit
Some units will have a 2 piece panel here
Manual Outside
Air Hood
(Damper inside
hood)
HVAC Unit
Panel
Horizontal supply
duct eld supplied
Horizontal return duct
eld supplied
HVAC Unit
8”X8” (203mmx203mm)
eld cut opening in
horizontal return duct
Horizontal Application:
Access lters through side
panel on HVAC unit
Screen removed
from replacement
panel
Fig. 3 - Hood Installation - Horizontal Application
Fig. 2 - Vertical Application - Side View
Side panel on
HVAC unit
Some units will have a 2 piece panel here
Replacement
Panel
Horizontal Return Installation: Hood Package
1. Install eld provided return air duct over the horizontal return open­ing per HVAC unit instructions. See Fig. 3.
2. Cut 8” x 8” (203mm x 203mm) square opening side of horizontal duct. See Fig. 3.
3. Remove screen from replacement panel shipped with hood package
and screw in place over the cut out in duct. See Fig. 4. The panel can be
discarded.
4. Caulk or gasket the back side of the manual outside air hood. Secure the hood over the cutout with screen. Screw to return duct.
5. Set the adjustable damper inside the hood to allow for the desired
outside air intake. Blade will lock in place.
Screen Removal
for Horizontal
Application
Fig. 4 - Screen Removal Detail
2