Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualied service personnel should install, repair, or service
air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of
replacing lters. All other operations should be performed by trained
service personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags, and labels attached to the
unit, and other safety precautions that may apply.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury. Understand these signal
words; DANGER, WARNING, and CAUTION. These words are
used with the safety-alert symbol. DANGER identies the most
serious hazards which will result in severe personal injury or death.
WARNING signies hazards which could result in personal injury
or death. CAUTION is used to identify unsafe practices which may
result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have a re
extinguisher available. Read these instructions thoroughly and follow
all warnings or cautions included in literature and attached to the
unit. Consult local building codes and current editions of the National
Electrical Code (NEC) NFPA 70. In Canada, refer to current editions
of the Canadian electrical code CSA 22.1.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or
death.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position and install a lockout
tag. There may be more than 1 disconnect switch. Lock out and
tag switch with suitable warning label.
!
CAUTION
!
UNIT PERFORMANCE AND COMPONENT HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airow is 350 to 450
cfm for each 12,000 Btuh of rated cooling capacity. For heating
operation, the airow must produce a temperature rise that falls
within the range stamped on the unit rating plate.
GENERAL
Economizers are recommended for use with only commercial
packaged products that have ECM motors. The Economizer system
utilizes the latest technology available for integrating the use of free
cooling with mechanical cooling for rooftop units. The solid state
control system optimizes energy consumption, zone comfort, and
equipment cycling by operating the compressors when the outdoor-air
temperature is too warm, integrating the compressor with outdoor air
when free cooling is available, and locking out the compressor when
outdoor-air temperature is too cold. Demand ventilation is supported.
The Economizer system utilizes gear-drive technology with a directmount spring return actuator that will close upon loss of power. The
Economizer system comes standard with an outdoor air temperature
sensor, a supply air temperature sensor, and low temperature
compressor lockout switch. Indoor enthalpy sensor, outdoor enthalpy
sensors and CO2 sensors are available for eld installation.
See Table 1 for package contents. See Table 3 for sensor usage.
Table 1 - Package Contents
PART NUMBERQTYDESCRIPTIONS
1Hood Top and Sides
1Aluminum Filter
11#10 Self-Drilling Screw and Washers
4#10 x 1/2” Blunt End Screws
3#10 x 1” Self-Drilling Screws
1Economizer Assembly
1
CPECOMZR010A00
21” 12 x 20 Filter*
1Top Filter Rack
1Bottom Filter Rack
1Replacement Return Chamber Panel
1Compressor Cover Panel
1Extension Harness w/ Plug
2Wiring Diagram Labels
1Installation Instruction
Table 2 - Filter Sizes
Part No.1-IN. Filter Size2-IN. Filter Size
CPECOMZR010A00 2 - 12 X 20 (304.8 X 508MM)
*Unscrew two brackets on the top lter rack to t 2-in. (50.8mm) lters.
Supply Air Temperature Sensor
with Bracket
1 - 10 X 20 (254 X 508MM)
1 - 12 X 20 (304.8 X 508MM)
1
Table 3 - Economizer Sensor Usage
ECONOMIZER WITH OUTDOOR AIR
APPLICATION
Outdoor Air
Dry Bulb
Single
Enthalpy
Differential
Enthalpy
CO2 for
DCV Control
Using a
Wall-Mounted
CO2 Sensor
CO2 for
DCV Control
Using a
Duct-Mounted
CO2 Sensor
*CRENTDIF004A00 accessory is used on many different base units. As such, these kits may
contain parts that will not be needed for installation.
†33ZCSENCO2 and CGCDXSEN004A00 are accessory CO2 sensors.
**33ZCASPCO2 and CGCDXASP00100 are accessory aspirator boxes required for ductmounted applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZVASPCO2
accessories.
33ZCSENCO2 or
CGCDXASP00100†
33ZCASPCO2 or
CGCDXASP00100**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed
HH57AC078
HH57AC078
CRENTDIF004A00*
33ZCSENCO2
CGCDXSEN004A00
and
and
or
CRCBDIOX005A00††
OR
ACCESSORIES LIST
The economizer has several eld-installed accessories available to
optimize performance. Refer to Table 4 for authorized parts.
Table 4 - Economizer Field-Installed Accessories
DESCRIPTIONPART NUMBER
Outdoor Air Enthalpy SensorHH57AC078
Indoor Air Enthalpy SensorCRENTDIF004A00
Return Air CO2 Sensor (4-20mA)CRCBDIOX005A00
CO2 Room Sensor (4-20mA)
Aspirator Box for Duct Mount
CO2 Sensor (4-20mA)
Space Temperature and CO2 Room Sensor
with Override (4-20mA)
Space Temperature and CO2 Room Sensor
with Override and Set Point (4-20mA)
Heat Pump Relay PackageCPRLYKIT001A00
33ZCSENXO2 or
CGCDXSEN004A00
33ZCASPCO2 or
CGCDXASP001A00
33ZTCT56CO2
33ZCT56CO2
INSTALLATION
Economizer - See Fig. 2 for Economizer component locations. To
install the vertical Economizer perform the following procedure:
1. Turn off unit power supply and install lockout tag.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or
death.
Before installing or servicing system, always turn off main power
to system and tag. There may be more than one disconnect switch.
Turn off accessory heater power switch if applicable.
2. Remove the compressor access panel and unit side panel. See Fig.
3.
3. Remove the return air duct cover to aid in the installation.
4. Install the top lter rack in the HVAC unit next to the indoor coil.
Bend ange by hand at 90 degrees - Fig.1. Screw left side of rack in
to 4th hole down on coil frame. Use only 1/2” (12.7mm) long blunt
end screws. Make sure the bracket is level ant the right side of lter
bracket is pushed back against the coil then screw bent ange to unit
side panel using 1” long self-drilling screw provided. If using 2”
(50.8mm) lter the lter spacer must be removed.
NOTE: The lters are accessible through the access panel above the
hood.
Install the bottom lter rack. Bend ange 90 degrees - Fig.1. Screw
left side of rack to the coil frame. Use only 1/2” (12.7mm) long blunt
end screws. Make sure the bracket is level ant the right side of the
lter bracket is pushed back against the coil then screw bent ange
to unit side panel using 1” long self drilling screw.
Top lter rack
Evaporator
Coil
Screw rack
to coil frame
here
Screw rack
to coil frame
here
Bottom rack
Bend ange
at 900 and
screw to
divider with
1” long screw
Fig. 1 - Filter Rack
5. Most new 3 Phase HVAC units will have an economizer plug in
the return air chamber which runs back to the control box. If the unit
has the economizer harness/plug, rst remove the jumper plug from
the end of the harness to allow the plug from the economizer to be
connected.
NOTE: The jumper plug should be saved for future use in the event
that the economizer is removed from the unit. The jumper plug is not
needed as long as the economizer is installed.
In the event that your HVAC unit does not have a factory installed
harness for the economizer, the extension harness shipped with the
economizer must be installed in the unit. Route the extension harness
through the HVAC unit as shown in Fig. 8 & 10. Connect extension
harness per wiring diagrams in this booklet. The plug end of the harness
extension will connect to the economizer plug in the return chamber
and the other end will be routed to and connect in the control box.
2
HH63AW001
Economizer
Controller
Economizer
Actuator
HH18HA286
Low ambient
Compressor
Lockout switch
(HH57AC080)
Adjustable Dry
Bulb Outside
Air Sensor
Economizer Plug
Fig. 2 - Component Locations
Compressor
Compartment
Outside Air
Damper
Hood Top
Cleanable
Aluminum Filter
Fig. 5 - Filter Installation
7 15/16”
(202mm)
21 9/16”
(548mm)
Divider in
HVAC Unit
Filter Clip
Outside Air
Replacement
Panel Shipped
with Economizer
Economizer
Cover Panel
Side Panel shipped with HVAC
unit. Remove and Discard
NOTE: Units with base rails will
have a 2 piece panel. Discard the
panel covering the return air
chamber and reuse the panel
covering the compressor section.
Fig. 3 - Panel Removal
17 1/2”
(445mm)
21”
(533mm)
1/2 in. (38.1mm)
above the
top of the left side
of the return duct
opening use 1” self
drilling to screw
thru unit back panel
and into the top
rear corner of
economizer
assembly
Indoor
Blower
Panel
Compressor
Panel
Fig. 6A
Gasketing
4 Sides
Caulk these corners
after economizer
is installed
Screw
into base
(572mm)
Fig. 6 - Economizer Installation
HVAC Unit
Filter Door
21 9/16”
(548mm)
Screw
22 1/2”
Replacement
Panel
Economizer
Panel
16 1/4”
(413mm)
Aluminum
Filter
Remove Screw from base pan. Install
economizer then re-insert screw through
slot in economizer into basepan.
16 1/4”
(413mm)
Fig. 4 - Hood AssemblyFig. 7 - Economizer Installed in HVAC Unit
3
Economizer
Economizer Harness from
Actuator and controller
Economizer
Rainhood
Indoor
Blower
Compressor
Fig. 8 - Routing Harness Extension and
Mounting SAT Sensor
Supply Air Temperature
Sensor (SAT)
Indoor
Blower
Main 24V
Splice Box
Economizer
Harness
Supply Air Temperature
(See Fig. 8A)
Economizer
Hood
Economizer
Plug
Economizer
Harness
Self-Drilling
Screw
SAT Sensor
on Bracket
Indoor
Blower
Panel
Indoor
Blower
Fig. 8A - SAT Mounting for Units with
Upper Block Off Panel
Economizer
Filter
Indoor Fan
Control
Box
Fig. 9 - SAT Location for Units without
Block Off Panel
Indoor
Blower Panel
Fig. 11 - Indoor Blower Panel
Compressor
4
To SAT Sensor
Fig. 10 - Routing Harness (Top View)
Economizer
Harness
6. Remove the panel on the HVAC unit covering the indoor blower.
See Fig. 11. The (provided) Supply Air Temperature (SAT) sensor,
which looks like and eyelet terminal, must be installed in the blower
section. Attach the (2) pink wires from the economizer harness (or
extension harness) to the SAT.
The SAT sensor is shipped attached to a small bracket. If the HVAC
unit has an upper block off panel, attach the sensor / bracket as shown
in Fig. 8A using a #10 x 5/8” self-drilling screw. If the unit does not
have an upper block off panel, remove the bracket from the SAT and
screw the SAT to the side of the indoor blower, using a #10 x 5/8”selfdrilling screw, as shown in Fig. 9.
7. Replace the panel covering the indoor blower.
NOTE: For heat pump units, an additional relay package, factory kit
part number CPRLYKIT001A00, or eld provided relays must be
installed in the blower section. See heat pump diagram for details.
Installation of Heat Pump Relays
When this economizer is used on heat pump HVAC units, relays must
be added for proper operation.
The relays, which are shown on the attached diagrams, can be eld
supplied, or relay kit CPRLYKIT001A00 can be ordered. Field
provided relays must be:
•SPDT, one pole normally open and one normally closed. Same
polarity.
•Minimum 124 VA inrush.
Acceptable relays include:
•Honeywell: R8222B117
•Honeywell: R422B1124
•White Rodgers: 91-103001-13002
•White Rodgers: 91-102006-13302
Relay Installation:
A. If the optional relay kit CPRLYKIT001A00 is used, it will mount
underneath the indoor blower as shown in Fig. 12 & 13. Follow
instructions sent with the package.
B. If relays are eld provided and installed, they can be mounted
above the upper block off panel, as shown in Fig. 12. Use caution to
ensure screws do not interfere with blower operation, Blunt end screws
are recommended.
C. If no upper block off panel is present mount relays on compressor
partition below indoor blower on left as shown in Fig. 12.
D. Wire the relays per diagram in this instruction.
Upper Block-off
panel (some units)
COMPRESSOR
NOTE 1: Field provided
relays can be mounted
on upper block off
panel, if applicable
Fig. 12 - Relay Kit Location
INDOOR
BLOWER
INDOOR
BLOWER
SEE
NOTE 1
CONTROL
SECTION
Location for heat
pump relay package
number
CPRLYKIT001A00
8. This step applies to units without base rails only. If the unit does
not have a wrap around compressor access panel install the supplied
replacement panel (Fig. 7).
9. Install the 5/8” gasketing on the duct side anges of the economizer,
see Fig. 6. Remove the right of the two screws on the lip of the basepan
(Fig. 7). Turn the economizer on its side (Fig. 6.) Slide economizer
into cabinet and as far to the left as possible. The economizer will set
against the left side of the HVAC unit. Use the screw just removed
from the basepan to screw through the slot in the bottom ange of the
economizer into the basepan where the screw was removed. Caulk as
required.
10. Remove lter access panel. Install the replacement return chamber
panel over the economizer assembly and underneath the drip ange on
the HVAC unit. Line up the bottom left hole on the panel with the hole
in the bottom left of the economizer and the mating hole in the base of
the HVAC unit. Insert screw, which will hold all parts in place. Insert
screws on bottom right of panel as well. Install lters and then reinstall
the lter access panel. See Fig. 6.
11. At a location 1/2 in. (12.7mm) above the top of the left side of the
return duct opening use 1” self drilling to screw thru unit back panel
and into the top rear corner of economizer assembly (Fig. 6).
Screw
CPRLYKIT001A00
relay kit
Fig. 13 - Relay Kit Installation
5
12. Caulk or gasket the back side of the hood mating anges. Install
assembled hood over the economizer opening in the replacement return
chamber panel. Screw in place through pre-punched holes. Make sure
all seams are watertight.
13. Open the lter clips on the inside of the hood top. Insert the
aluminum lter into the hood and close the clips to hold in place. See
Fig. 5.
14. Remove the lter access panel and install disposable lters in lter
rack. Reinstall the lter access panel. Fig. 1. See Table 2 for lter
sizes.
15. Through the lter access door (horizontal return panel), adjust
the settings on the economizer controller. Review the settings in the
Operation section:
1. The standard economizer controller has a factory setting
of 63OF (17OC) for the outdoor air temperature changeover
and 55O F (13OC) for the supply air (mixed air) temperature
sensor. The outdoor air temperature changeover setting is
adjusted on the sensor by setting the dip switches on the
sensor. See Fig. 15. The ABCD potentiometer on the economizer controller should be set to the “D” position.
2. The low ambient compressor lockout switch setting
is xed at 42O F (6O C).
3. The minimum position for the outdoor air damper can be
congured at the controller. When not using a CO2 sensor,
the DCV Max potentiometer must be completely closed
(CCW) for the Minimum Position potentiometer to
function correctly.
4. Settings for the optional outdoor enthalpy sensor, indoor
enthalpy sensor, and CO2 sensor can also be congured at
the controller.
16. Replace the lter access panel. Screw in place.
17. Install all economizer accessories then power HVAC unit and test
cycle economizer.
CONFIGURATION
Economizer Standard Sensors
OUTDOOR AIR TEMPERATURE (OAT) SENSOR— The outdoor
air temperature sensor (HH57AC080) is a 10 to 20mA device used to
measure the outdoor-air temperature. The outdoor-air temperature is
used to determine when the Economizer can be used for free cooling.
The operating range of temperature measurement is 40O to 100O F
(4O to 38O C). The sensor has 8 selectable temperature changeover
setpoints. The temperature changeover is set using the 3 dip switches
on the sensor. The ABCD potentiometer on the controller should be
set to the “D” position. See Fig. 15.
SUPPLY AIR TEMPERATURE (SAT) SENSOR—The supply air
temperature sensor is a 3 KΩ thermistor located at the inlet of the
indoor fan. See Fig. 8 and 9. This sensor is eld installed. The operating
range of temperature measurement is 0°(-18O C) to 158O F (70O C). See
Table 5 for sensor temperature/resistance values.
The temperature sensor looks like an eyelet terminal with wires
running to it. The sensor is located in the “crimp end” and is sealed
from moisture.
LOW TEMPERATURE COMPRESSOR LOCKOUT
SWITCH—The Economizer is equipped with a low ambient
temperature lockout switch located in the outdoor airstream which
is used to lock out the compressors below a 42O F (6O C) ambient
temperature. See Fig. 2.
Table 5 - Supply Air Sensor Temperature /
Resistance Values
TEMPERATURE (F)CELSIUS (C)RESISTANCE (ohms)
-22-3053,010
-4-2029,091
14-1016,590
3209,795
50105,970
68203,747
77253,000
86302,416
104401,597
122501,080
14060746
15870525
Economizer Control Modes — Determine the Economizer control
mode before set up of the control. Some modes of operation may require
different sensors. Refer to Table 2. The Economizer is supplied from
the factory with a supply air temperature sensor, a low temperature
compressor lockout switch, and an outdoor air temperature sensor.
This allows for operation of the Economizer with outdoor air dry bulb
changeover control. Additional accessories can be added to allow for
different types of changeover control and operation of the Economizer
and unit.
OUTDOOR DRY BULB CHANGEOVER— The standard controller
is shipped from the factory congured for outdoor dry bulb changeover
control. The outdoor air and supply air temperature sensors are
included as standard.
For this control mode, the outdoor temperature is compared to
a selectable setpoint on the sensor. See Fig. 15. If the outdoorair temperature is above the set point, the Economizer will adjust
the outdoor air dampers to minimum position. If the outdoor-air
temperature is below the set point, the position of the outdoor-air
dampers will be controlled to provide free cooling using outdoor
air. When in this mode, the LED next to the free cooling set point
potentiometer will be on. The changeover temperature set point is set
using the switches on the sensor. See Fig. 15 for the corresponding
temperature changeover values.
OUTDOOR ENTHALPY CHANGEOVER—For enthalpy control,
accessory enthalpy sensor (part number HH57AC078) is required.
Replace the standard outdoor dry bulb temperature sensor with the
accessory enthalpy sensor in the same mounting location.
6
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.