International Comfort Product HMD Series, HMD-163, HMD-179, HMD-124, HMD-146 Installation Instructions And Homeowner's Manual

...
Models :
Save these instructions for future reference.
Printed in Canada
DNS
-
0450 Rev A
OIL FIRED HOT
WATER BOILER
Manufactured by :
International Comfort Product
Division of UTC Canada Corporation 3400, Industriel blvd, Sherbrooke, Qc, Canada
Caution : Do not tamper with the unit or its controls. Call a qualified service technician.
2003/05/06 X40014 Rev. E
PART 1
INSTALLATION
WARNING
This boiler has been designed to provide you with comfort, savings and reliability for many years to come. Its performances, however, depends on the appliance being installed, brought on-line, and maintained correctly in accordance with the instructions provided in this manual.
This boiler is equipped with a burner designed to burn only No.2 fuel oil (furnace oil). Never attempt to burn used motor oil or any oil containing gasoline.
Make sure that the boiler and system are filled with water and that all air has been bled before attempting to start the burner.
Never operate the burner above the maximum temperature indicated on the boiler nameplate.
Never attempt to start the burner when the combustion chamber contains excess oil, is overheated, or when a strong smell of oil permeates the appliance.
Close oil valves if the boiler has not to be used for extended period of time.
Never store garbage or combustibles near the boiler.
Never burn garbage or paper in your boiler.
DO NOT TAMPER WITH THE UNIT OR THE
CONTROLS.
We recommend that you have a qualified technician install your boiler.
1) UNIT IDENTIFICATION
It is very important that you consult the figure 1 to recognise the characteristics of the “HMD” serie.
HMD boiler with potable hot water stainless steel tank­in-tank and with a flue-pipe of 7 inches diameter. The models are identified HMD-124, HMD-135, HMD-146, HMD-163 and HMD-179 and are available with Riello burner.
2) DELIVERY
Check carefully your boiler upon delivery for any evidence of damage that may have occurred during shipping and handling. Any claims for damages or lost parts must be made with the transport company.
3) INSTALLATION
Your unit must be installed according to regulations set down by competent authorities. See CSA B139 installation code.
3.1) Location
Your boiler must be installed in a clean and dry area, as close as possible to a chimney. These boilers are not approved for installation on combustible floor.
3.2) Clearances
The following minimum clearances from combustible surfaces must be observed.
Top : 24 inches Flue-pipe : 9 inches First side : 3 inches Other side : 24 inches Front (from the cabinet): 24 inches Rear : 24 inches
4) WIRING
The boiler must be connected to a 15 amp. @ 120 Vac protected circuit. The installer must wire the boiler according to the electrical diagram figure 2. All wiring must be done in accordance with the “Canadian Electrical Code CSA C22.1/ Part I”.
WARNING
The use of a triple action / relay aquastat is necessary whit the « HMD » boiler.
If more than 1 circulator is used, we recommend the use of a RC-02 circulator control.
3
5) OIL SUPPLY
The oil tank and lines must be installed in accordance with local codes and regulations. The burner can be hooked up with a one pipe system if the oil level in the tank is always over the burner level. For an outside aboveground fuel tank hook up, ideally use a one pipe system with nominal dimension of 12 mm (1/2”) diameter, and be sure to have the oil filter and at least 3 meters (10 ft) of piping installed inside, to allow the fuel oil to warm up before reaching the burner in very cold weather. The following configurations must be respected regarding the oil pump by-pass plug. With Riello burner, remove the by-pass plug for one pipe system.
The installation must include an oil filter and shutoff valve. Make sure the piping has no leaks or stoppages. Oil lines shall include no couplings. Never use compression fittings. For a 2 pipes system, use the same diameter for both the suction and the return lines and set them at the same depth in the oil tank. Additional information can be found in the burner installation brochure that came with your boiler.
6) CHIMNEY
6.1) Chimney draft
Chimney draft must be strong enough to ensure safe, reliable operation of your unit.
6.2) Installation
The connecting flue pipe diameter should never exceed that of the chimney and its horizontal runs should have a minimum slope of 1/4” (6.4 mm) per foot (300 mm) of run upward toward the chimney. The use of a damper in the connecting flue pipe is strictly prohibited. If more than one pipe are to be connected to the same chimney, the sectional area of the chimney must be equal to the total of individual
TABLE 1
Chimney draft
Chimney size
Models
Minimum Maximum
HMD-124 @ 146 HMD-163 @ 179
4
inches (mm)
5 (127) 6 (152) 7 (178) 0.035 (0.9) 6 (152) 8 (203) 7 (178) 0.05 (1.3)
Connecting pipe
inches (mm)
sectional areas. The usage of a draft control is compulsory. His omission constitutes sufficient grounds for voiding your warranty.
NOTICE
The formation of condensation on the three outer sides of an outside chimney is a possibility with efficient hot water boilers. Should this happen, a chimney liner or a “SMH” sidewall venting system should be installed.
7) BURNER INFORMATIONS
The burner is shipped in a separate box from the boiler and must be installed following the next steps :
1. Verify the model number on burner box to be match with the one on the boiler nameplate;
2. Install the nozzle supplied and verify the electrodes setting;
3. Install the burner on the boiler using supplied nuts already on the studs. Do not forget the fireproof gasket supplied with the burner. For the Riello burners with an adjustable flange, make sure that the end of the blast tube is flush with the inside surface of the combustion chamber;
4. Connect the oil pipe(s) to the burner pump;
5. Perform electrical connections in accordance with the appropriate diagram (See paragraph 4).
Recommended draft
inches (mm) W.C.
TABLE 2
Model
Capacity
Input
Burner
Nozzle
Pressure
HMD
-
124
124000
1.00 Riello F
-5
0.85-70B 140
HMD
-
135
135000
1.10 Riello F
-5
1.00-70B 125
HMD
-
146
146000
1.20 Riello F
-5
1.00-70B 145
HMD
-
163
163000
1.35 Riello F
-5
1.20-70B 130
HMD
-
179
179000
1.50 Riello F
-5
1.35-70B 125
Burner characteristics - “HMD” boilers
(Btu/hr) (USGPH)
8) COMBUSTION AIR SUPPLY
For a good and reliable operation, every oil heating system must have an adequate and functional air supply. If the boiler must be installed in a confined area, 2 permanent air openings must be provided. Both openings must be sized by allowing 1 ft2 per U.S. gallon of oil to burn (240 cm2/l) per hour. One opening should be located near the ceiling, the other near the floor.
9) GENERAL PLUMBING INFORMATIONS
Satisfying operation of your system greatly depend on your plumbing arrangement. Refer to figures 3 and 4.
In all cases, your installation must include: a. A pressure reducing valve, set at 12 psi (83 kPa),
installed in the boiler cold water supply;
b. An expansion tank pressurised to 12 psi (83 kPa),
present on the piping;
c. An automatic air vent, to eliminate trapped air in
the boiler;
d. A correctly sized water circulator, installed on the
heating loop;
e. Stop valves and threaded unions, installed on
return and supply boiler pipes.
Always use quality pipe sealant on all threaded connections and make sure that these connections are well tightened. Avoid flushing the system when this boiler is a replacement for an existing one, to limit oxygen to come in the system.
Delavan (psi)
10) POTABLE HOT WATER SUPPLY
Before attempting to proceed with the potable hot water supply connections, always check the water quality to avoid premature scaling, which quickly put your installation inefficient. Refer to a specialist and install a water softener if need. Locate the left tapping to use as the potable cold water inlet. The use of the thermostatic mixing valve (provided) is a necessity to get safety and optimum of your installation.
11) THERMOSTAT
The thermostat must be mounted on an inside wall approximately five feet high on the main floor. The location should allow the thermostat to detect temperature variations without exposing it to air currents and sunrays.
12) DRAFT-REGULATOR
A barometric draft-regulator must be installed on the connecting pipe between the chimney and the boiler. It must be located in an easily serviceable location. Please refer to the installation instructions supplied with it.
5
Loading...
+ 7 hidden pages