Intermatic UG30, UG28 User Manual

UG28 & UG 30 MODULAR SYSTEMS
INSTALLATION INSTRUCTIONS
and
OPERATIONS MANUAL
TURN OFF POWER TO THE ELECTRIC SERVICE OR PANEL AND TO EQUIPMENT TO BE PROTECTED
BEFORE INSTALLING ANY SURGE PROTECTION DEVICE. ALL WIRING SHOULD COMPLY WITH THE
NATIONAL ELECTRIC CODE AND LOCAL ELECTRIC CODES.
UNPACKING and INSPECTION
2. Remove the unit and the mounting brackets from the shipping carton. Inspect for obvious shipping damage.
3. If any shipping damage is observed, immediately file a claim with the shipping agency and notify your distributor.
INSTALLATION
1. TEST and verify system voltage to assure proper selection of the Surge Protection Device (SPD) in accordance with the wiring diagrams shown on page 2. Turn off the electric power to the panel.
2. CONFIRM that the Surge Protection Device is the proper voltage configuration for this installation. Refer to the installation diagrams for additional information.
3. SELECT a location to mount the UG Modular cabinet. Mount as close as possible to the electric panel or individĀ­ual piece of equipment to be protected. The UG Modular device should be mounted on a flat vertical surface that can support the weight of the device. Consideration should be given to the available knockout positions in the panel when deciding where to locate the UG Modular device. All wire leads should be kept as short as possible to insure optimum operation.
4. The internal 100 KAIC fuses are the prime current protection devices for the UG Modular device. While the lead wires may be connected to either a bus bar or a multi-pole breaker, installation to a 30 amp breaker with the appropriate number of poles is preferred. Circuit breakers will not trip from transient surge activity due to their inherent slow response.
MOUNTING
1. Attach the upper and lower mounting rails to the UG Modular Cabinet using the screws provided.
2. Pre-drill holes in the surface on which the UG Modular Cabinet will be mounted. Use at least four (4) appropriate size mounting screws or bolts.
3. Select and remove the proper size knockout from the UG Modular Cabinet cabinet. Install conduit, sealtite or other proper wire protection between the panel and the UG Modular device.
WIRING
1. For installations using less than three feet of wire for each lead, use 10 AWG stranded wire.
2. Measure and cut all leads to proper length, keeping in mind that leads should be as short and straight as possible.
3. Tape all wires together to minimize inductive coupling.
4. Route the wire lead bundle through the conduit to the panel.
5. Connect the GROUND (green) lead to the ground bus in both the UG Modular unit and the electric panel.
6. If used, connect the NEUTRAL (white) to the neutral fuse terminal in the UG Modular unit and the neutral bus in the electric panel. If installing at the main distribution panel, the neutral and ground leads could terminate at a common bus bar in the panel.
7. Connect the phase leads to the fuse block terminals in the UG Modular unit. Connect each phase lead to the appropriate breaker or bus connections in the electric panel. NOTE: For HIGH LEG DELTA, make certain that the high leg is connected to the middle fuse terminal position.(Refer to Figure 3) For GROUNDED PHASE DELTA, make certain that the grounded phase is connected to the middle fuse terminal position in the UG Modular unit.(Refer to Figure 4)
8. CHECK all connections for tightness or torque. Observe the suggested torque values published by the device manufacturer when breakers or disconnect switches are used.
CAUTION:
WIRING DIAGRAMS
120/240 VAC Single Phase
120/208 VAC Three Phase Wye
277/480 VAC Three Phase Wye
480 VAC Three Phase Delta
120/240 VAC Three Phase High Leg Delta
240 VAC Three Phase Delta 240 VAC Grounded Phase Delta
UG28A2401S UG30A2401S
UG28A2403D UG30A2403D
UG28A2083Y UG30A2083Y
UG30A2403G
UG28A4803D UG30A4803D
UG28A4803Y UG30A4803Y
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
N
G
L1
L2
L3
G
L1
L2
L3
G
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK -Note 2
BLACK
GREEN
BLACK
BLACK
BLACK
GREEN
BLACK
RED
BLACK
WHITE
GREEN
BLACK
BLACK
WHITE
GREEN
Figure 1
Figure 6
Figure 3
Figure 5
Figure 2
Figure 4
2
NOTE:
Use a 30 amp breaker with both the U28 and UG30 Series units. (2) L2 will be grounded in a 240 VAC Grounded Phase or Corner Grounded Delta.
UG MODULAR SYSTEM
UG MODULAR SYSTEM
UG MODULAR SYSTEM
UG MODULAR SYSTEM
UG MODULAR SYSTEM
UG MODULAR SYSTEM