Intermatic PF1102, PF1102M Installation, Operation & Service Manual

Page 1
INSTALLATION
FREEZE PROTECTION FOR POOLS, SPAS AND WATER FEATURES
By
OPERATION &
SERVICE MANUAL
Model: PF1102 FREEZE PROTECTION CONTROL
IN RAINPROOF (TYPE 3R) ENCLOSURE
Model: PF1102M FREEZE PROTECTION CONTROL MECHANISM
SUITABLE FOR POOL/SPA EQUIPMENT CONTROL
INPUT VOLTAGE: 240 VOLT - 60 HZ. ELECTRICAL RATING: 3 HP - 240 VOLT AC.
DANGER! To Reduce the Risk of Injury:
...do not permit children to operate the Control Unit or use the Pool/Spa unless they are closely supervised at all times. ...test GROUND FAULT protection regularly. If it fails to reset, DO NOT USE THE POOL or SPA! Contact a qualified service technician. ...always disconnect electricity before servicing this control or the equipment(s) connected to it. THIS CONTROL IS NOT TO BE USED AS A POWER DISCONNECT.
READ, FOLLOW & SAVE THIS INSTRUCTION MANUAL
GENERAL INFORMATION
Model PF1102 Freeze Protection Control is self-contained in an indoor-outdoor, beige, rainproof
enclosure and designed to be connected to a timing or switching device. Together, they control as well as protect the Pool/Spa equipment and plumbing against freeze damage. The Control, if wired according to instructions, turns ON the Filter Pump when the air temperature (where this Control is located) drops below the temperature set by the thermostat dial (between 32˚F and 45˚F). Nevertheless, the Control is not intended to be a substitute for the insulation, coverings or maintenance.
Model PF1102M is a mechanism only, functions just like Model PF1102 and fits (snaps into) any Intermatic Pool Panel, Models T10000R, T30000R or T40000R Series. Both models are designed to operate on 240 Volt, 60 cycle only.
Page 2
IMPORTANT SAFETY INSTRUCTIONS
When installing and operating this Product and other associated equipment, basic safety precautions should always be
ollowed.
f
. This Control must be installed by a qualified person, according to National and Local Electrical Codes.
1
2. Install this Control not less than 5 feet (3 meters in Canada) from inside edge of pool and 1 foot (30cm) above ground. USE COPPER CONDUCTORS ONLY rated minimum 75˚ C.
3. Do not exceed the maximum ratings of individual components, wiring devices, and current carrying capacity of conductors.
. For Control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680 of the National Electrical Code
4
or Article68 of the Canadian Electrical Code.
5. The Control should not operate any equipment which would cause bodily injury or property damage should it be activated unexpectedly.
INSTALLATION - MODEL PF1102
1. Select the proper
outdoor
location for the Freeze Protection Control and prepare the necessary conduit run(s) required by the installation layout.
2. Hang enclosure on a flat vertical surface or other support, preferably next to the Switching Device, using hardware suitable for the purpose.
3. Properly terminate conduits at both ends and pull-in the
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE INSULATION CLEARS PRESSURE PLATE
CONDUCTOR
conductors as specified by the installation layout.
4. Follow wiring diagram on page 4 of this manu-
al and make LINE and LOAD (Pump) connec­tions as shown. Wiring the Freeze Control, first identify each lead by its color (Line: and
Red
, LOAD:
Blue
and
Yellow
Black
), then make wire connections by using twist on wire connectors.
a. If the control device is an Intermatic 240 Volt
Time Switch, follow diagram on top of page 4 of this manual. Make connections to Time Switch terminal block as shown in the insert above for the proper wire termination.
b. If the control device is a Time Switch made
prior 1984 by Intermatic or made by another manufacturer or it is other than a time switch (air switch, contactor, etc.), first identify the LINE and LOAD terminals (leads) of the control and wire the two devices in
Parallel
,
as shown on bottom of page 4.
5. If the Freeze Protection Control is installed in a location where it is exposed to direct sun most of the day, extend 8 inches of the copper capillary tube of the thermostat into an open ended (plastic or metal) conduit about 10 inches long, installed at bottom of the enclosure.
Handle capillary tube with care!
6. TEST INSTALLATION: a. Turn the thermostat dial to its lowest setting
and place crushed ice (in plastic bag) inside capillary coil of Thermostat.
b. Turn ON power to Control Panel, wait one
minute, then slowly turn thermostat dial counterclockwise until Filter Pump starts.
c. Turn power OFF to Control, remove ice,
and check wiring. Tighten terminal screws if necessary. Reinstall front plate.
d. Turn power ON to Control and set the
Time Switch and the Thermostat. See OPERATION instructions below.
INSTALLATION - MODEL PF1102M
1. Install mechanism in any Intermatic Pool Panel with only one Time Switch by snapping it into the unused mounting bracket, furnished with the Panel.
2. Follow steps 4 to 6 above, complete the installation.
Make sure the installation is properly grounded.
2
Page 3
OPERATION
CLOCK
DIAL
TIME
POINTER
O
FF
T
RIPPER
MANUAL
LEVER
O
N
T
RIPPER
TO SET THERMOSTAT, turn dial, pointing to desired temperature between 32˚F and 45˚F, marked on the plate. Remember, many variables, such as the location of the Freeze Protection Control, the location of equipment and the pool or spa, the location and insulation of the plumbing, etc., must be considered before selecting the “turn ON” temperature of the filter Pump. Your local pool service professional is the best source of information. The Thermostat is factory set to turn OFF the Filter Pump when the ambient temperature rises 5˚F above its set point.
TO SET TIME SWITCH, if Intermatic, follow instructions on the right. If other than Intermatic, follow instructions inside enclosure cover. The length of the daily filtration/heating cycle depends on many variables such as size, shape, and geographic location of the pool, water chemistry, type of pool equipment usage and season of year. If not sure, contact your local pool service professional for advice.
TIME SWITCH OPERATING INSTRUCTIONS
1. TO SET "ON" AND "OFF" TIMES:
Hold TRIPPERS against edge of CLOCK-DIAL, pointing to time (AM or
M) when ON and OFF operations
P are desired. Tighten tripper screws firmly.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
• TO OPERATE SWITCH MANUALLY: Move MANUAL
LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not affect the next operation.
• FOR MORE THAN ONE DAILY ON-OFF OPERATION:
Place additional tripper pairs on CLOCK-DIAL (order 156T1978A).
• IN CASE OF POWER FAILURE: Reset CLOCK-DIAL
to proper time of day. See step 2 above.
SYMPTOM CAUSE(S) CORRECTIVE ACTION
1. Time Switch will not keep 1a. Frequent power outages Reset dial time - dial is turning. 1b. Wrong voltage/cycle Change clock motor
2. Time Switch Dial stops 2a. Loose tripper Check/change tripper at ON or OFF tripper. 2b. Bent dial Check/change mechanism
Load is ON at all times--
3. dial is turning. 3b. Two ON-trippers on dial Change tripper
Dead clock motor
4.
. (Clock
motor gears do not rotate.) coil due to lightning or surge)
Filter Pump will not start 5a. Defective thermostat Replace thermostat
5. when temp. is below 32˚F
.
TROUBLESHOOTING
1c. Loose clock motor connections Check connections
2c. Defective motor Change clock motor
elded contacts
3a. W
3c. Defective mechanism
4a. Defective clock motor (open
4b. Loose clock motor connections
rong voltage
4c. W
5b. Defective relay 5c. Faulty wiring Check wiring 5d. Power outage Install stand-by power
3
Change mechanism
Change mechanism
Change clock motor
Check connections Change clock motor
Replace relay
Page 4
240 VOLT WIRING
Interconnecting wiring diagram between Model PF1102 or PF1102M Freeze
Protection Control and a 240 volt Time Switch and 240 volt Filter Pump
If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace at its sole
LIMITED ONE YEAR WARRANTY
option, the unit free of charge. This warranty applies only to the original purchaser and is not transferable. This warranty does not apply to: (a) damage caused by accident, abuse, mishandling, dropping, acts of God, or any negligent use; (b) units which have been subject to unauthorized repair, opened, taken apart, or
wise modified; (c) units not used in accor
other damages, so the for state. INTERMA OR IMPLIED W P THE W This war of pur Spring Gr damage.
TIC INCORPORA
TICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONL
AR
ARRANTY PERIOD ST
ranty ser
chase, postage pr
ove, IL 60081-9698/T
egoing limitation may not apply to you. This war
ARRANTIES. ALL IMPLIED W
TED WILL NOT BE LIABLE FOR INCIDENT
TED ABOVE.
vice is available by either (a) r
A
epaid to the authorized ser
elephone: 815-675-7000 http://www/inter
dance with instr
ARRANTIES, INCLUDING THE W
eturning the product to the dealer from whom the unit was purchased, or (b) mailing the product, along with proof
vice center listed below. This warranty is made by: Intermatic Incorporated/After Sales Service, 7777 Winn Rd.,
uctions; (d) damages exceeding the cost of the pr
ranty gives you specific legal rights and you may have other rights that var
AL OR CONSEQUENTIAL DAMAGES.
ARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A
Y AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS
matic.com Please be sure to wrap the product securely when mailing to avoid shipping
Because of our commitment to continuing research and improvements, Intermatic Incorporated reserves the right to make changes, without notice, in the specifications and material contained herein and shall not be responsible for any damages, direct or consequential, caused by reliance on the material presented
158PF12525
.
IINNTTEERRMMAATTIICC IINNCCOORRPPOORRAATTEEDD,
4
,
SPRING GROVE, IL 60081-9698
oduct. Some states do not allow a limitation of
THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS
om state to
y fr
Loading...