STEP 2
Check all parts to be sure none are missing. You should have:
QUANTITY DESCRIPTION
1 IG1240RC Panel Protector with a
threaded connector and locking nut.
1 Conduit Nut
STEP 3
Select the mounting for the protector at the panel. If you have a panel that is not
like the diagram (Fig. 3) call (815) 675-7000 for assistance between 8:00 am and
4:00 pm, weekdays, central time.
STEP
4
If you do not have a main power shut “OFF” (master switch) do not attempt the
work. Call a licensed electrician. Turn the main breaker or shut off switch to the
“OFF position). Use the circuit tester or AC voltmeter to be sure the circuits are
off.
STEP
5
Carefully remove the front trim panel. Choose and remove the desired knockout
through which the Protector wiring will enter into the breaker panel. Try to select
a knockout that will allow you to use the shortest
possible length of wire between the protector
and the circuit breakers.
STEP 6
Install the Protector by inserting the wire and the
threaded connector into the hole you knockedout in the breaker panel and secure it with the
locknut provided. If the breaker panel is recess
mounted into the wall use the IG12FMP-3
Flush Mounting Kit to recess the Protector. Follow the
instructions packaged with the flush mounting kit.
STEP 7
Check to assure that the electricity is “OFF”. Aneon circuit tester or AC Voltmeter
(Fig. 2) can be used, if you have one.
When connecting the wires, the green (ground) wire is connected first, then the
white (neutral) wire and the black wires as shown in Figure 3. The black wires
should be connected next to each other to two 15 or 20 ampere circuit breakers.
NOTE: The protector functions best if all bends in the wires are rounded, ideally to a 4” radius. Hard 90˚ bends reduce efficiency. Cut all leads to correct length.
DO NOT COIL EXCESS LEAD.
STEP 8
Route the green wire to the ground bus bar provided in the breaker panel.
Some panels do not have a separate ground bus bar so the green wire must then
be connected to the neutral bus bar mentioned in Step 9. This wire must be connected for safety purposes.
STEP 9
Next, route and connect the white wire to the neutral bus bar provided in the
breaker panel.
STEP 10
The two black wires remaining must be connected to two separate 15 or 20 amp
circuit breakers, not to each other, to insure connection across the full 240 volt
AC incoming power circuit. Use the AC voltmeter or circuit tester across the
black wire connection to be sure the protector is providing full protection to your
panel. Not more than one wire should be connected to circuit breaker. It may be
necessary to add new breakers.
STEP 11
Check to be sure all wires are securely fastened and all screws are tight. You
can confirm that the protector is wired to the correct breakers if you can read
220 to 240 volts AC between the two breakers that the protector is connected
to. If there is no voltage between the two breakers, check to be sure that both
of the breakers and the master breaker are “ON”. If there is still no voltage
between the two breakers, then they are probable on the same leg, and you will
have to select another breaker for one of the black wires. BE SURE TO TURN
OFF THE MAIN BREAKER BEFORE YOU ATTEMPT TO MOVE ANY WIRES.
Replace the front trim panel on the circuit breaker panel. (continued on back...)
(FIG. 3)
(FIG. 2)