Intermatic ICUBE Installation And Operation Manual

Spring Grove, Illinois 60081 www.intermatic.com
ICUBE™ Adaptive Defrost Module
Installation and Operation Manual
SAFETY SECTION
WARNING
Risk of Fire or Electrical Shock
• Disconnect the power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• More than one circuit breaker or disconnect switch may be required to de-energize the equipment before servicing.
• Installation and/or wiring must be in accordance with the national and local electrical code requirements.
• Refer to DTAV40 or DDT40 for additional warnings and installation instructions. See www.intermatic.com if needed.
• Only use the Intermatic supplied thermistor probe kit. The probe connection(s) to the DTAV40 and DDT40 control are NOT an isolated Class 2 circuit. Use #18-14 AWG copper conductors for the field supplied wire to the thermistor probe.
• Rotate the timer dial clockwise only, rotating counter-clockwise will damage the timer.
• Do not move the clock hands on the timer. Moving the clock hands manually may damage the timer.
• The thermistor wire may be extended up to 400 ft (122 m) using field-supplied wiring between the DDT40 control and the thermistor probe location.
• This product is only intended to be used with Grässlin™ DTAV40 and DDT40 models.
All trademarks are the property of their respective owners.
NOTICE
PRODUCT DESCRIPTION
The ICUBE™ Adaptive Defrost Module, when added to an existing Grässlin™ DTAV40 - Defrost Control, provides the DTAV40 Control with the ability to skip scheduled defrost events when they are not needed in order to save energy. Up to four thermistor probes may be added to the control in order to monitor multiple evaporator coils. Thermistor probes may be installed up to 400ft (122 m) away from the ICUBE™ module at a remote dedicated or multiplex condensing unit (indoor or outdoor) or within the freezer/cooler box. No changes to the installed defrost control terminal wiring (such as the wiring for fans, defrost heater, or thermostat) is required.
To order additional thermistor probe kits (for example, to connect multiple evaporators to one control), use part number 178GR10K-1.
ICUBE™ Adaptive Defrost Module Contents – Part Number DDFM
The kit includes:
• One 10 ft (3.05 m) thermistor probe, with clip
• One 6 ft (1.83 m) input lead
• Four wire connectors
• One dead front
• One ICUBE™ Adaptive Defrost Module, DDFM
• Four #4-40 ¼" screws
FIG. 1 ICUBE™ Module Kit Contents
Specications
Screw
Rated Input:
120/240 VAC, 50 mA, 60 Hz
INSTALLATION
Note: Refer to WARNINGS on page 1 before proceeding.
Tools Required
• Small flathead or #4-40 TORX head screwdriver
• Needle nose pliers
• Emery cloth or evaporator cleaner
• Wire cutter
Pre-Installation
1. Disconnect all power to the control at the circuit breaker or disconnect switch. More than one circuit breaker or switch may be required to de-energize the control and all connected loads.
2. Plan the length of field-supplied copper wire needed to connect the thermistor probe from the evaporator coil to the input lead. (This wire may be #18-14 AWG shielded or unshielded up to 400 ft (121.92 m) long).
3. The existing control may be installed in an enclosure (as shown in FIG. 3, for example) or secured via a bracket inside the condensing unit control panel (as shown in FIG. 4, for example). The installation of the ICUBE™ module is the same for both instances.
4. If applicable, open the enclosure door.
5. If applicable, remove and discard the existing dead front cover. See FIG. 2.
Thermistor Probe Ratings:
• Thermistor*: Type NTC
• Rating:10 K Ω @ 25° C
• Wire size: 24 AWG
• Working range: -40° F to 152° F (-40° C to 67° C)
• Thermistor probe wire length: 10 ft (3.05 m)
• Connector wire length: 6 ft (1.83 m)
*Thermistor probe connections are not an isolated Class 2 circuit.
*Only use a thermistor probe specified for use with DDFM model.
• Wire stripper
• Fish tape (possibly needed)
• Insulation tape, hose clamp, or wire ties (possibly needed)
FIG. 2 Existing Dead Front
Install the ICUBE™ Module
1. Remove the FM timer from the control board. SeeFIG. 3 or FIG. 4.
Note: The control board does not need to be removed from the enclosure or the bracket.
FM Timer
Control Board
FIG. 3 Remove the FM Timer (Enclosed Model Shown) FIG. 4 Remove the FM Timer
ICUBE™ Adaptive Defrost Module
2
(Salable item DT-B. See DT-B Installation Instructions.)
Screw
FM Timer
Control Board
Bracket
2. Orient the ICUBE™ module as shown in FIG. 5.
Input Lead
3. Install and fasten the ICUBE™ module to the control
board with the screws provided. Be sure to align the ICUBE™ module terminals with the terminal fasteners on the control board when placing. SeeFIG. 5.
Note: Gently tighten screws. Do not over-tighten or
stripping may occur.
4. Install and fasten the FM timer onto the ICUBE™
module with the screws provided. Be sure to align the FM timer terminals with the terminal fasteners on the
ICUBE™ module. SeeFIG. 5 inset.
Install the Thermistor Probe
1. Route the length of field-supplied copper wire needed to connect the thermistor probe from the evaporator coil to the input lead. (This wire may be 18–14 AWG shielded or unshielded up to 400 ft (121.92m) long)
FM Timer
Screw
ICUBE™ Module
Control Board
Terminal Fasteners
Bracket
FIG. 5 Install the ICUBE™ Module (Bracket Shown)
Input Lead Connectors
Note: The field-supplied wires may run along with the
power wires through existing or new conduit.
2. Connect the input lead to the ICUBE™ module as shown in FIG. 6. The input lead may be inserted into any of the four connectors on the ICUBE™ module.
Note: Make sure the input pins are properly aligned with
the input lead connector.
3. Route the input lead above the tab and around the ICUBE™ module as shown in FIG. 7.
4. Cut the input lead to the appropriate length:
– For enclosure installations, cut the input lead length
to ensure the connection is inside the enclosure as shown in FIG. 7.
– For bracket installations, cut the input lead to an
appropriate length inside the condensing unit control panel.
5. Use the provided wire connectors to connect the input lead to the routed 18–14 AWG shielded or unshielded field-supplied wire.
FIG. 6 Attach the Input Lead
Input Lead
Route Lead over Tab
Wire Connector
ICUBE™ Adaptive Defrost Module
Field-Supplied Wire to Thermistor Probe
FIG. 7 Route the Input Lead
3
6. Connect the thermistor probe to the evaporator coil. There are two options for probe placement.
Note: Ensure the copper tube surface area designated
for thermistor probe placement is clean. Use Emery cloth or Evaporator cleaner to clear the surface. A dirty surface could create an insulation barrier which may cause inaccurate temperature readings.
– Insert the probe between the cooling fins, as shown
in FIG. 8. Ensure that the probe makes good contact with one of the evaporator tubes. Then, using needle nose pliers, carefully bend the cooling fins together to hold the probe firmly in place.
– Use the provided clip, or if the clip is the incorrect
size, use another means to fasten the thermistor probe to one of the circuit tubes e.g., hose clamp, insulation tape, zip tie, as shown in FIG. 9. Clip the probe onto one of the lower coils in either the 10 o'clock or 2 o'clock position, making sure that the probe makes good contact with the evaporator tube.
Probe
Cooling Fins
FIG. 8 Insert Thermistor Probe between Evaporator Cooling Fins
Recommended Thermistor Probe Position
The probe should be positioned and fastened wherever frost accumulates most quickly. This is generally 1" to 2" (2.5 cm to 5 cm) from either end, at the bottom quarter and at the discharge side of the evaporator coil. If there is uncertainty about where frost typically accumulates the fastest, put the system into a manual defrost (see "Optional: Manual Defrost" on page 6) and monitor the last area of the evaporator where frost is present prior to a completely frost-free coil. Make sure the probe is not fastened in close proximity to the electric defrost heating element.
7. Route the thermistor probe wires away from the evaporator fans and cooling fins, avoiding pinches and strain. Route the wire through existing or new line voltage conduits. Secure the wires as appropriate for your installation.
8. Use the provided wire connectors to connect the thermistor probe wire to the routed 18–14 AWG field­supplied wire.
9. Use electrical tape to protect all connections against moisture.
Evaporator Coil
Clip
FIG. 9 Connect Thermistor Probe to Evaporator Coil
10. If additional thermistor probes are needed repeat all steps in this section. For large evaporators, additional thermistor probes may be added to a coil on each (opposite) side.
11. For multiple-evaporator installations, see "Optional: Multiple Evaporators" on page 6.
ICUBE™ Adaptive Defrost Module
4
System Startup
1. As needed, update your scheduled initiation and termination times. See DDT40 or DTAV40 instructions or www.intermatic.com for programming instructions.
2. Snap the provided dead front cover into place, if applicable. See FIG. 10.
3. Re-apply power to the unit.
4. The control will sense the number of probes connected. Note: Observe the blue LED during startup in order to verify that the ICUBE™ module registers the correct number of thermistor probes. The blue LED will flash once for each recognized probe.
5. See TABLE 1 and FIG. 11 or FIG. 12 to verify proper operation of the ICUBE™ module.
Provided Dead Front
FIG. 10 Attach the Provided Dead Front
Diagnostics
Mode LED Status Control Mode
Green LED ON Refrigeration mode active
A
Red LED OFF Defrost mode active Green LED OFF Red LED OFF
B
Green LED ON Red LED ON
A/B Blue LED
ON Next scheduled defrost to be
OFF Next scheduled defrost active 1 flash/1 second Calibration mode 5 flashes/
10 seconds 1-4 flashes/
10 seconds
TABLE 1 LED Status Indicator Table
Refrigeration mode active
Defrost mode active
delayed (efficiency mode)
Thermistor sensor error
Only occurs at startup to indicate the number of sensors connected to the control
Blue LED
Green LED
Red LED
FIG. 11 LEDs (Enclosed Model Shown)
ICUBE™ Adaptive Defrost Module
Blue LED
Green LED
Red LED
FIG. 12 LEDs
5
ICUBE™ FUNCTIONALITY
Modes
Efciency Mode – Scheduled defrosts are bypassed when the control is in this state. This is indicated when the blue LED is ON continuously. If there is no thermistor probe attached or a probe failure occurs, the ICUBE™ module operates solely off of the defrost timer and does not enter efficiency mode.
Calibration Mode – The ICUBE™ module enters calibration mode after the first Scheduled Defrost and after each allowed defrost cycle. During calibration the control establishes a baseline coil behavior.
Thermistor Probe Initialization – The number of thermistor probes connected to the control is detected during the initial startup of the system. The blue LED flashes the number of times equal to the number of probes detected. If the correct number of probes is not detected, disconnect power to the control before you attempt to correct the problem.
Optional: Manual Defrost
To initiate a manual defrost, rotate the FM timer dial clockwise through two consecutive scheduled defrosts within 60 seconds.
Optional: Multiple Evaporators
The ICUBE™ module has four sensor inputs that can monitor up to four evaporator coils. Typically, in a four-evaporator system, the timer activates a contactor that energizes the multiple defrost loads simultaneously. When the ICUBE™ module senses a decrease in capacity in one or more coils, efficiency mode shuts off and the defrost timer initiates a defrost at the next scheduled interval as shown in FIG. 13.
Sensor Wires
FIG. 13 Evaporator System
For additional assistance, contact Technical Services at 1.815.675.7000.
ICUBE™ Module with Grässlin™ Defrost Timer
Remote Condensing Unit (Indoor or Outdoor)
ICUBE™ Adaptive Defrost Module
6
©2016 Intermatic
Loading...
+ 12 hidden pages