Intermatic 158TS11760 User Manual

158TS11760 7/27/04 3:49 PM Page 1
MODEL: T105
LR3730
24 HOUR DIAL TIME SWITCH
ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS
Y BE WIRED AS SINGLE POLE DOUBLE THROW
MA
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA. PILOT DUTY PER POLE - 120/208/240VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.
CLOCK MOTOR: 110-125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
TIME DIAL
TIME POINTER
OFF TRIPPER
MANUAL LEVER
ON TRIPPER
To wire as
SINGLE POLE NORMALLY CLOSED, move clock
motor lead from terminal
2. To wire as SINGLE POLE DOUBLE THROW, install jumper (the same gauge as LINE to 2, LOADS to 1 and 4. NEUTRAL connection always as shown. Use COPPER wire only. For gauge selection and wire connection, see details below. Use 3/16 or larger screwdriver, tighten terminal screws firmly (25lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MAX.
MINIMUM
LOAD
COPPER
(AMP)
WIRE SIZE
(AWG)
TEMP(°C)
14
15
12
20
10
30
8
40
MIN. INSUL­ATION
SINGLE PHASE
120 V. 240 V. 208 V.
60
1/2
60
1
60
2
75
-
75°C INSULATION MAX. MOTOR
LOAD (HP)
2
2 1/2
3 5
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK- DIAL (the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER
below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
158TS11760
SPRING GROVE, ILLINOIS 60081-9698
WIRING DIAGRAM
120V SUPPLY
TYPICAL WIRING: SINGLE POLE NORMALLY OPEN SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
GRD.
LINE
CLOCK
MOTOR
A
N
3
2
1
GROUND
4
TO LOAD
3 to 1, and connect LINE to 1, LOAD to
Line wire) between 2 and 3 and connect
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
N/A
3 PHASE
240 V.
N/A