158TS10990 8/6/04 10:29 AM Page 1
MODEL: T7402B
LR3730
SEVEN-DAY DIAL TIME SWITCH WITH
SPRING WOUND CARRY-OVER MOTOR
4 POLE SINGLE THROW
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS
40 AMP. RESISTIVE EACH POLE 120V-480V AC.
40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR
277V AC. 1000 VA PILOT DUTY EACH POLE 120V - 277V AC.
24 FLA, 144 LRA (2 HP) - 120V AC.; 28 FLA, 168 LRA (5 HP) - 240V AC.
SINGLE PHASE
28 FLA, 168 LRA (7 1/2 HP)-208V AC., (10 HP)-240V AC. 3 PHASE
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER 131T69GA
CLOCK
MOTOR
208
277 V
60 HZ
SUPPLY
A
5
2
1
6
7
B
4
3
8
TO
LOADS
GROUND
SCREW
WIRING DIAGRAM
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven
day schedule. Clock motor voltage may be other than load voltage, but must be as
specified. For terminal markings, internal wiring and contact arrangements refer to wiring
diagram above. Use solid or stranded COPPER wire with insulation to suit installation. See
table for gauge selection.
To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends
of wire under the pressure plate of terminals. Use 3/16 or larger screw driver to tighten
terminal screws firmly.
REPLACE FRONT INSULATOR BEFORE TURNING
ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14
12
10
8
MAX.
LOAD
(AMP)
15
20
30
40
MIN.
INSUL-
ATION
TEMP(°C
60
60
60
75
75°C INSULATION MAX. MOTOR
240 V.
2
2 1/2
3
5
LOAD (HP)
SINGLE PHASE
120 V.
1/2
1
2
-
208 V
3
4
5
7 1/2
3 PHASE
.
240 V.
3
5
7 1/2
10
PRESSURE PLA
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
TE
PROGRAMMING INSTRUCTIONS
O SET “ON” TIMES,
1. T
day-of-week and time-of-day when
place bright ON trippers against edge of CLOCK-DIAL at
“ON” operations are desired. Tighten tripper
screws securely.
2.
TO SET “OFF” TIMES, place dark OFF trippers against edge of CLOCK-DIAL at
times when
3.
TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
O SET DIAL
4.
T
week and time-of-day (AM or PM) on dial with the
“OFF” operations are desired. Tighten tripper screws securely.
O TIME-OF-DA
T
Y,
turn dial CLOCKWISE and align the exact day-of-
TIME POINTER. Some allowance
may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL
OPERA
• TO OPERATE SWITCH MANUALLY
TING INSTRUCTIONS
: Move MANUAL LEVER below CLOCK-DIAL
COUNTERCLOCKWISE.
left or right as indicated by arrows. This will not affect next automatic operation.
• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-
day, see step 4 of programming instructions.
BEHIND-THE-INSULATOR WORK.
DISCONNECT ELECTRICITY
BEFORE
ANY
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10990