Intermatic 158TS10983 User Manual

158TS10983 8/6/04 10:48 AM Page 1
MODEL: T7805B
LR3730
SEVEN-DAY DIAL TIME SWITCH
4 POLE; Two Normally Open - Two Normally Closed
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS
CONTACT RATINGS:
AMP. RESISTIVE EACH POLE 120V- 480V AC.
40
40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 277V AC.
24 FLA, 144 LRA (2 HP) - 120V AC.; 28 FLA, 168 LRA (5 HP) - 240V AC.
CLOCK MOTOR: 480 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER WG1606
CLOCK
MOTOR
480 V 60 HZ
SUPPLY
GROUND SCREW
WIRING DIAGRAM
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven day schedule. Clock motor voltage may be other than load voltage, but must be as specified. For terminal markings, internal wiring and contact arrangements refer to wiring dia­gram above. To form the common poles of a DOUBLE POLE DOUBLE THROW switch, if required, install jumpers (extend supply wires) between terminals 1-6 and 3-8. Use solid or stranded COPPER wire with insulation to suit installation. See table for gauge selection. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screw driver to tighten terminal screws firmly.
REPLACE FRONT INSULATOR BEFORE TURNING
ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
MAX. LOAD
(AMP)
15 20 30 40
MIN.
INSUL-
ATION
TEMP(°C)
60 60 60 75
75°C INSULATION MAX. MOTOR
240 V.
2
2 1/2
3 5
LOAD (HP)
SINGLE PHASE
120 V.
1/2
1 2
-
208 V
N/A
3 PHASE
.
240 V.
N/A
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
TO LOADS
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at
day-of-week and time-of-day when
“ON” operations are desired. Tighten tripper
screws securely.
O SET “OFF” TIMES,
2.
T
times when
3.
TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
O SET DIAL
4.
T
“OFF” operations are desired. Tighten tripper screws securely.
O TIME-OF-DA
T
week and time-of-day (AM or PM) on dial with the
place dark OFF trippers against edge of CLOCK-DIAL at
,
Y
turn dial CLOCKWISE and align the exact day-of-
TIME POINTER. Some allowance
may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY
left or right as indicated by arrows.
: Move MANUAL LEVER below CLOCK-DIAL
This will not af
fect next automatic operation.
• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-
day, see step 4 of programming instructions.
OR WORK.
DISCONNECT ELECTRICITY
INTERMA
SPRING GROVE, ILLINOIS 60081-9698
158TS10983
BEHIND-THE-INSULA
BEFORE
ANY
TIC INCORPORA
TED
T