Intermatic 158TS10978 User Manual

158TS10978 8/6/04 10:37 AM Page 1
MODEL: T7401B
SEVEN-DAY DIAL TIME SWITCH
4 POLE SINGLE THROW
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS
AMP. RESISTIVE EACH POLE 120V- 480V AC.
40
40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR
24 FLA, 144 LRA (2 HP) - 120V AC.; 28 FLA, 168 LRA (5 HP) - 240V AC.
SINGLE PHASE
28 FLA, 168 LRA (7 1/2 HP) -208V AC., (10 HP) -240V AC. 3 PHASE
CLOCK MOTOR: 125 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER WG1600
CONTACT RATINGS:
A
5
6
120 V 60 HZ
SUPPLY
CLOCK MOTOR
2
1
B
4
3
8
7
TO LOADS
LR3730
GROUND
WIRING DIAGRAM
SCREW
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven day schedule. Clock motor voltage may be other than load voltage, but must be as specified. For terminal markings, internal wiring and contact arrangements refer to wiring dia­gram above. Use solid or stranded COPPER
only wire with insulation to suit installation.
See table for gauge selection. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screw driver to tighten terminal screws firmly.
REPLACE FRONT INSULATOR BEFORE
TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
MAX. LOAD
(AMP)
15 20 30 40
MIN.
INSUL-
ATION
TEMP(
60 60 60 75
°
C)
SINGLE PHASE
.
120 V
1/2
1 2
-
75°C INSULATION MAX. MOTOR
LOAD (HP)
240 V.
2 1/2
3 PHASE
208 V.
3
2
4 5
3
7 1/2
5
240 V
3 5
7 1/2
10
PRESSURE PLATE
.
TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLA
TE
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at
day-of-week and time-of-day when
“ON” operations are desired. Tighten tripper
screws securely.
2.
TO SET “OFF” TIMES, place dark OFF trippers against edge of CLOCK-DIAL at
ighten tripper screws securely
times when
3.
TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
4.
TO SET DIAL TO TIME-OF-DAY, turn dial CLOCKWISE and align the exact day-of-
“OFF” operations are desired.
week and time-of-day (AM or PM) on dial with the
T
TIME POINTER. Some allowance
.
may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY
: Move MANUAL LEVER below CLOCK-DIAL
left or right as indicated by arrows. This will not affect next automatic operation.
IN CASE OF POWER F
AILURE OR TO ADVANCE/RETARD TIME:
Reset time-of-
day, see step 4 of programming instructions.
DISCONNECT ELECTRICITY BEFORE ANY BEHIND-THE-INSULATOR WORK.
TED
158TS10978
INTERMA
SPRING GROVE, ILLINOIS 60081-9698
TIC INCORPORA
Loading...