Intermatic 158TS10959 User Manual

158TS10959 7/27/04 3:53 PM Page 1
MODEL: T174
LR3730
24 HR DIAL TIME SWITCH WITH “SKIPPER®
DOUBLE POLE SINGLE THROW (DPST)
40 AMP. RESISTIVE, EACH POLE 120V-480V AC; 40 AMP. INDUCTIVE, OR TUNGSTEN OR 1000 VA. PILOT DUTY EACH POLE - 120-277 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA ) - 240V AC.
TIME POINTER
TIME DIAL
WIRING INSTRUCTIONS:
or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power con­nections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
WIRE SIZE
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-
158TS10959
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
ON/CUTOUT
TRIPPER
DAY ARROW
OFF TRIPPER
MANUAL LEVER
SKIPPER WHEEL
SKIPPING SCREW
WIRING
DIAGRAM
240V 2 WIRE
AND GROUND
240V
SUPPLY
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A” AND 1 AND SUPPLY NEUTRAL TO TERMINAL “A”.
GR
LINE 1 LINE 2
A
1
2
3
4
GROUND
CLOCK MOTOR
TO LOAD(S)
MAX.
INSUL-
LOAD
COPPER
(AWG)
14 12 10
8
ATION
(AMP)
C)
°
TEMP(
60
15
60
20
60
30
75
40
CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1948A.
direction and align the exact time-of-day on the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER. SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s)
is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week
opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.
CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.
SINGLE PHASE
120 V.
1/2
1 2
-
LOAD (HP)
240 V. 208 V.
2
2 1/2
3 5
N/A
3 PHASE
240 V.
N/A
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
CLOCK-DIAL (the
75°C INSULATION MAX. MOTOR
MIN.
of-day. See programming instructions.
INTERMA
SPRING GROVE, ILLINOIS 60081-9698
TIC INCORPORA
TED