Intermatic 158TS10932 User Manual

Project1 7/27/04 4:35 PM Page 1
MODEL: T175CR
LR3730
24 HR DIAL TIME SWITCH WITH “SKIPPER®” AND SPRING-WOUND CARRY-OVER MOTOR
ONE NO - ONE NC CONT
IN
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA. PILOT DUTY PER POLE - 120/208/277 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.
TIME TIME
WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid
or stranded COPPER selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten termi­nal screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
WIRE SIZE
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to
158TS10932
CLOCK MOTOR: 110-125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
OFF
MANUAL
MIN.
MAX.
INSUL-
LOAD
COPPER
(AWG)
14 12 10
ATION
(AMP)
C)
°
TEMP(
60
15
60
20
60
30
CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER. SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s)
is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week
opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.
CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.
proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
ACTS
MAY BE WIRED AS SINGLE POLE DOUBLE THROW
ON/CUTOUT
DAY
SKIPPER
SKIPPING
CLOCK
GRD
A
N
120V
LINE
TYPICAL WIRING SINGLE POLE NORMALLY OPEN SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
WIRING DIAGRAM
2
1
only wire with insulation to suit installation. See gauge
75°C INSULATION MAX. MOTOR
SINGLE PHASE
1/2
2 1/2
1 2
SPRING GROVE, ILLINOIS 60081-9698
3 PHASE
2
3 5
N/A
N/A
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS
3
4
TO LOAD