MODEL: T174CR
24 HR DIAL TIME SWITCH WITH “SKIPPER®” AND SPRING-WOUND CARRY-OVER MOTOR
DOUBLE POLE SINGLE THROW (DPST)
IN TYPE 3R RAINPROOF ENCLOSURE,
40 AMP. RESISTIVE, EACH POLE 120-480 VOLT A.C. 40 AMP INDUCTIVE, OR TUNGSTEN OR 1000 VA. PILOT DUTY EACH POLE - 120V -277V AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
TIME POINTER
TIME DIAL
OFF TRIPPER
MANUAL LEVER
or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF
operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER.
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week
opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.
• IN CASE OF POWER F
proper time-of-day. See programming instructions.
158TS10930
MAX. LOAD
(AMP)
15 20 30 40
MIN. INSUL­ATION
TEMP(°C)
60
60
60
75
ON/CUTOUT
TRIPPER
DAY ARROW
SKIPPING SCREW
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120 V. 240 V. 208 V.
2
1/2
2 1/2
1
3
2
5
-
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
WIRING DIAGRAM
SKIPPER WHEEL
240V
SUPL
277 480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A” AND 2 AND SUPPLY NEUTRAL TO TERMINAL “A”.
3 PHASE
240 V.
N/A
N/A
AILURE,
A
GRD
LINE 1
Y
LINE 2
reset CLOCK-DIAL to
1
2
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
3
GROUND
4
LR3730
CLOCK
MOTOR
TO LOAD