Intermatic 158T10710 User Manual

Project4 7/27/04 3:45 PM Page 1
MODEL: T185
24 HOUR DIAL TIME SWITCH WITH ADJUSTABLE TRIPPERS
LR3730
LISTED
885L
ONE NORMALLY OPEN -ONE NORMALLY CLOSED CONTACTS MAY BE WIRED AS SINGLE POLE DOUBLE THROW.
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA, PILOT DUTY - 120-277 VOLT AC; 2 HP (24 FLA) - 120V. AC; 5 HP (28 FLA) - 240V AC.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
LEVER
WIRING DIAGRAM
GRD.
120V
N
SUPPLY
LINE
TYPICAL WIRING: SINGLE POLE NORMALLY CLOSED SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
TRIPPER TIME
POINTER
FIGURE 1
CLOCK DIAL
A
CLOCK
MOTOR
3
2
1
GROUND
4
TO LOAD
WIRING INSTRUCTIONS: To wire switch follow diagram above.
To wire as SINGLE POLE NORMALLY OPEN, move motor lead from terminal 3 to 1, and connect LINE to 1, LOAD to 2. To wire as SINGLE POLE DOUBLE THROW, install jumper (the same gauge as LINE wire) between terminals 2 and 3 and connect LINE to 2, LOADS to 1 and 4. NOTE: Line 2 if present is uninterrupted. Use COPPER wire only. For gauge selection and wire connection, see details below. Use 3//16 or larg­er screwdriver, tighten terminal screws firmly (25lb-in minimum).
REPLACE FRONT INSULATOR BEFORE TURNING ON ELECTRICITY.
MAX.
MINIMUM
LOAD
COPPER
(AMP)
WIRE SIZE
(AWG)
TEMP(°C)
14
15
12
20
10
30
8
40
PROGRAMMING INSTRUCTIONS
• TO SET TRIPPER(S): A. Loosen screw A. (Fig. 1 inset); move time
selector pointer to desired timing (scale is in minutes); tighten screw A. Place TRIPPER(S) on CLOCK-DIAL at time(s) daily operation(s) is/are to take place. Tighten screw B. firmly.
• TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either
direction and align the exact time-of-day on the now, when switch is being put into operation) to the pointer. DO NOT
MOVE POINTER.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation. minutes immediately after an automatic operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time­of-day. See programming instructions.
158T10710
75°C INSULATION MAX. MOTOR
MIN. INSUL­ATION
SINGLE PHASE
120 V. 240 V. 208 V.
60
1/2
60
1
60
2
75
-
2 1/2
2
3 5
LOAD (HP)
N/A
3 PHASE
240 V.
N/A
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
CLOCK-DIAL (the time
NOTE: The MANUAL LEVER is inoperative for 15
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698