Interlogix HDX-135-345 Installation Instructions Manual

Tamper
HDX-135-345 Wireless Rate-of-Rise Heat Sensor Installation Instructions
Introduction
The Interlogix HDX series wireless heat detectors use electronic processing to detect temperature Rate-of-Rise and fixed heat set point conditions plus a learn mode wireless transmitter in one unit. The micro-processor trips the transmitter when the temperature at the detector location reaches a fixed temperature of 135°F (57°C) or senses a rate of rise at 12°F to 15ºF (6.7 to 8.3ºC)
Figure 1
Model HDX-135-345 Wireless 135ºF (57ºC) Rate-of-Rise Heat
Sensor, 345 MHz Wireless, Compatible with Honeywell and 2GIG Wireless Receivers
Installation
Use the following installation guidelines:
Heat detectors should be installed to provide property protection. Reliance should not be placed on heat sensors for life safety. Where life safety is involved, smoke sensors must also be installed.
The detectors allow for normal temperature fluctuations, however, ceiling temperatures should not exceed 100°F (38°C)
Mount the detector in a central location of the area to be protected, either on the ceiling or on a wall.
If mounting on a ceiling, the detect or must be at least 4 in. (10 cm) away from any walls.
If mounting on a wall, the top of the detector must be within 4 to 6 in. (10 to 15 cm) of the ceiling.
The UL maximum spacing allowance of the detector is 50 x 50 ft. (15 x 15 m). Refer to the NFPA Standard 72 for application requirements.
Do not mount the detector close to devices that change temperature rapidly, such as ovens, heat vents, furnaces, or boilers.
Enrolling
The HDX-135-345 is compatible with Honeywell and 2GIG wireless receivers. These panels must learn (program) the detector ID codes in order to respond to detector signals. For complete programming instructions refer to the specific
control panel instruction guides. To add the sensor to panel memory:
Honeywell™
The HDX-135-345 must be enrolled in the control panel before it can operate in the system . The heat protect ion zone must be enrolled as Loop 1 and “Input Type” 3 (supervised RF). Tamper is transmitted as Loop 4, but does not require programming.
1. Place the panel in program mode.
2. Enter the zone number to be programmed.
3. Enter the zone type when prompted. Program as a Fire zone type [9]
4. When prompted, enter Input Type [03] (3 on some
panels) – Supervised RF Transmitter
5. Remove pull tab from sensor battery
6. When prompted for the serial number, transmit from the detector by activating (press and release) the tamper switch (Figure 2).
7. When serial number is displayed, transmit from sensor again by activating tamper switch again. The current loop number will begin to flash (4).
8. Manually change the loop number to loop number [1].
Note: The fire protection zone enrolled must always be Loop 1. Otherwise, fire annunciations will not be reported by the control
9. Exit programming when complete. Test the sensor after enrolling into the system. Refer to the Testing section in this guide.
Figure 2: Tamper
2GIG®
The following procedure describes how to learn-in the HDX­135-345 heat sensor into the 2GIG control panel.
1. Select RF sensor #(01 to 48)
2. Select RF sensor type [09] Smoke/Heat
3. Select RF sensor equipment code. Enter code 0895
466-5304 • REV A • 20January17 1
4. With panel in learn-in mode (press Shift then Learn)
Rate of Rise rating
Operating temperature
UL max. Ambient ceiling
Storage
Relative H
Maximum UL Spacing
Frequency
E
S
Supervision I
Enclosure D
Magnet Mark and Location
Mounting
Holes
cause a tamper by pressing and then release tamper switch (Figure 2). The correct TX ID should appear. Accept by pressing OK.
5. Select RF sensor equipment age [0] New
6. Select RF sensor loop number [1]
7. Select dialer delay (enable/disable)
8. Select voice descriptors (see panel manual)
9. Select sensor reports (enable/disable)
10. Select sensor chime
11. To exit programming, click skip
12. Click end and exit. The panel takes a few seconds to reset.
Mounting the Detector
1. Locate the base mounting holes and mount the base to the wall or ceiling with the appropriate hardware (Figure
3)
2. Attach the detector to the mounting bas e
Figure 4: Magnet Mark
1. With the sensor permanently mounted, place a magnet against the mark located on the sensor body. (Figure 4)
2. Hold the magnet in place for about 15 seconds
3. The control panel should respond by sounding the fire alarm
4. Disarm control panel to silence alarm
Replacing the Batteries
Battery life depends on how often the detector transmits signals, but is more dependent on the temperature of the installation environment. When the battery voltage gets low, the detector transmits a low battery signal to the panel. The panel then activates trouble beeps to notify the customer that the detector battery must be replaced. Pressing the status button identifies the sensor with the low battery.
Figure 3: Mounting Holes
Testing
1. Before permanently securing the detector to the wall or ceiling, test the detector from the installation location using one of the following methods.
2. Place the panel in sensor test mode.
3. Plug in a portable hair dryer.
4. Hold the hair dryer about 12 to 18 in. away from the sensor, aiming it at the side of the sensor.
5. Listen for the appropriate number of beeps from interior sirens and speakers (refer to the specific panel
6. Listen for the appropriate number of beeps from interior sirens and speakers
Magnet Test
Note: Notify central station before any live testing to avoid fire response. The magnet test allows the sensor to send an actual alarm signal to the control panel, if a magnet is held against the housing for 15 seconds.
Replace the battery immediately when this condition occurs, using the following battery: Panasonic CR123A 3V
Battery Disposal
The batteries used in this sensor are lithium batteries and are not reusable. Be sure to properly dispose of used lithium batteries according to your local hazardous waste disposal laws.
Specifications
12° to 15ºF (6.7° to 8.3C)
135°F (57°C): 32 - 100°F (0 - 37°C)
100°F (37.8ºC )
Temperature -30 to 167°F (-34 to 75°C)
umidity 0 to 95% noncondensing
50ft (15.2m) x 50ft (15.2m)
345 MHz (crystal-controlled) xpected Battery Life 10 years tandby Current Less than 0.9 µA
nterval 62-68 minutes
imensions
Diameter: 2.29" (58.25mm) Height: 1.28" (32.4mm)
2 466-5304 • REV A • 20January17
Loading...
+ 1 hidden pages