Interlogix HDX-135, HDX series, HDX-200, HDX-135Z Installation Instructions Manual

Wireless Rate-of-Rise Heat Sensor Installation Instructions
Introduction
The Interlogix HDX series wireless heat sensors use electronic processing to detect both heat and freeze conditions using a learn mode wireless transmitter all in one unit. The micro-processor trips the transmitter when the temperature at the sensor location reaches a fixed temperature of 135°F (57°C), 200°F (94°C), 41°F (5°C), depending on the model installed, or senses a rate of rise at 12°F to 15ºF (6.7 to 8.3ºC)
Figure 1
Models HDX-135 Wireless 135°F (57°C) Rate-of-Rise Heat
Sensor
HDX-200 Wireless 200°F (93°C) Rate-of-Rise Heat
Sensor
HDX-135Z * Wireless 135°F (57°C) Rate-of-Rise Heat &
Freeze Sensor
* The HDX-135Z sensor has two independent ID #’s for heat and
freeze, the sensor will alarm at a fixed 135°F (57°C) temperature or a 12° to 15ºF (6.7 to 8.3ºC) rate of rise, or when the sensor reaches 41°F (5°C), the sensor will restore at 50°F (10ºC).
Installation
Use the following installation guidelines:
Heat sensors should be installed to provide property protection. Reliance should not be placed on heat sensors for life safety. Where life safety is involved, smoke sensors must also be installed.
The sensors allow for normal temperature fluctuations, however, ceiling temperatures should not exceed 100°F (38°C)
Mount the sensor in a central location of the area to be protected, either on the ceiling or on a wall.
If mounting on a ceiling, the sensor must be at least 4 in. (10 cm) away from any walls.
The UL maximum spacing allowance of the sensor is 50 x 50 ft. (15 x 15 m). Refer to the NFPA Standard 72 for application requirements.
Do not mount the sensor close to devices that change temperature rapidly, such as ovens, heat vents, furnaces, or boilers.
Enrolling
The panel must learn (program) the sensor ID codes in order to respond to sensor signals. For complete programming information, refer to the specific control panel documentation.
Note: The HDX-135Z sensor has two ID numbers, one for heat the
other for freeze. Each number is programmed separately.
To add the sensor to panel memory:
1. Place the panel in program mode.
2. Proceed to the Learn Sensors menu. When the panel prompts you for a sensor group number, with Simon
XT/XTi, Concord, and Advisor panels program the zone to use sensor group 26. With NetworX and Ultrasync panels program the zone to use sensor group 8.
3. Select the desired sensor number. When the panel prompts you to trip the sensor, remove and reinsert the battery (or remove battery pull tab) until the panel beeps, indicating successful programming.
4. When programming for the HDX-135Z model for freeze detection remain in program mode.
Simon XT/XTi, Concord, and Advisor panels
select sensor group 29.
NetworX panels program the zone to use sensor
group 22.
Ultrasync panels program sensor type to “24-
Hour Audible” and sensor option to “Low Temp”. Also check box for “Disable Internal Reed”.
5. Hold down the tamper switch (Figure 2), then remove and reinsert the battery to learn in the freeze portion of the sensor.
Tamper
If mounting on a wall, the top of the sensor must be within 4 to 6 in. (10 to 15 cm) of the ceiling.
466-5244 • REV A • 25MAY16 1
6. Exit Program Mode
Figure 2: Tamper
Mounting the Sensor
1. Locate the base mounting holes and mount the base to the wall or ceiling with the appropriate hardware (Figure
3)
2. Attach the sensor to the mounting base
Mounting
Holes
Figure 3: Mounting Holes
Testing
1. Before permanently securing the sensor to the wall or ceiling, test the sensor from the installation location using one of the following methods.
2. Place the panel in sensor test mode.
3. Plug in a portable hair dryer.
4. Hold the hair dryer about 12 to 18 in. away from the sensor, aiming it at the side of the sensor.
5. Listen for the appropriate number of beeps from interior sirens and speakers (refer to the specific panel documentation).
6. To test the freeze sensor, use either freeze spray or place an ice cube in a plastic bag and hold against the sensor until the device trips.
7. Listen for the appropriate number of beeps from interior sirens and speakers
Magnet Test
Note: Notify central station before any live testing to avoid fire response. The magnet test allows the sensor to send an actual alarm signal to the control panel, if a magnet is held against the housing for 15 seconds.
Magnet Mark and Location
Figure 4: Magnet Mark
1. With the sensor permanently mounted, place a magnet against the mark located on the sensor body. (Figure 4)
2. Hold the magnet in place for about 15 seconds
3. The control panel should respond by sounding the fire alarm (Heat and Freeze Alarm)
4. Disarm control panel to silence alarm
Replacing the Batteries
Battery life depends on how often the sensor transmits signals, but is more dependent on the temperature of the installation environment. When the battery voltage gets low, the sensor transmits a low battery signal to the panel. The panel then activates trouble beeps to notify the customer that the sensor battery must be replaced. Pressing the Status button identifies the sensor with the low battery.
Replace the battery immediately when this condition occurs, using the following battery: Panasonic CR123A 3V
Battery Disposal
The batteries used in this sensor are lithium batteries and are not reusable. Be sure to properly dispose of used lithium batteries according to your local hazardous waste disposal laws.
Specifications
Minimum Rate of Rise rating 12° to 15ºF (6.7° to 8.3C)
Operating temperature
UL max. Ambient ceiling 100°F/150°F (37.8ºC / 65.6ºC)
Storage Temperature -30 to 167°F (-34 to 75°C)
Relative Humidity 0 to 95% noncondensing
Detection range up to 2500 sq. ft.
Frequency 319.5 MHz (crystal-controlled)
Expected Battery Life 10 years
Standby Current Less than 0.9 µA
Supervision Interval 62-68 minutes
Enclosure Dimensions
Regulatory
135°F (57°C): 32 - 100°F (0 - 37°C)
200°F (94°C): 32 - 150°F (0 - 66°C)
Diameter: 2.29" (58.25mm) Height: 1.28" (32.4mm)
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 985 Household Fire Warning System Units
CAN/ULC-S530 Heat Actuated Fire Detectors for Fire Alarm Systems
CSFM Category 7270
FCC: 15.109 Class B, 15.231
Industry Canada: ICES-003, RSS­210
Contact Information
Visit us online at www.interlogix.com. For technical support, see www.interlogix.com/support
Product Ordering
Model
HDX-135 Wireless 135°F (57°C) Rate-of-Rise Heat
Sensor
HDX-200 Wireless 200°F (93°C) Rate-of-Rise Heat
Sensor
HDX-135Z Wireless 135°F (57°C) Rate-of-Rise Heat &
Freeze Sensor
2 466-5244 • REV A • 25MAY16
Loading...
+ 1 hidden pages