Figure 37: Mounting position of LON2000 board.......................................................................................... 49
Figure 38: FP1xxx/2xxx Lon port terminal connections................................................................................ 49
Figure 39: Adjustment of the LCD viewing angle.......................................................................................... 50
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 3
1 I
NTRODUCTION
The purpose of this manual is to provide assistance during the installation and
commissioning of the FP/FR1100/1200/2000 Series fire panels, and repeaters/emulators.
Please note that the manual is intended as a guide only and is not to be used to replace
any local building and/or wiring codes.
Other manuals available are:
1. Aritech 900 Series Detectors Installation Manual
2. Aritech 2000 Series Detectors Installation Manual
3. FP1200/2000 Reference Guide
4. FP2000 Series Network Configuration Guide
5. FP1200/2000 End User Manual
Warning
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
4 FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
2 GENERAL INFORMATION
2.1 Product codes
FIRE PANELS:
Max. nr.
Firepanel
FP1200-00 0 4A/4B 126/128 Apollo No 365x444x112 8
FP1200-01 0 2A/2B 64/128 Sentrol No 365x444x112 8
FP1200-02 0 2A/2B 64 Sentrol No 365x444x112 8
FP1216 1xZE2016 2A/4B 126/128 Sentrol No 365x444x112 8
FP1216EN 1x ZE2016 2A/4B 126/128 Sentrol No 440x444x112 9
The FP1100/1200/2000 series fire panels are designed to comply with the requirements
of EN54-2 (control and indicating equipment) and EN54-4 (power supply equipment).
The panels have the following options with requirements according to EN54-2:
•
Output to fire alarm devices
•
Output to fire alarm routing equipment (according to DIN VDE0833)
• Output to fire protection equipment (according to VdS-directive)
• Delays to outputs
• Coincidence detection
• Alarm counter
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 7
• Fault/disablements from addressable points
• Output to fault warning routing equipment
•
Standardised input/output interface (according to DIN 14661)
•
Test condition
•
Total loss of power supply (option)
8 FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
3 TECHNICAL SPECIFICATIONS
3.1 General specifications
Loop capacity:
• Every loop PCB (LC2002) can be configured as two class A loops or four class B
loops. (Except FP1200-00 2A/4B or 4A/4B; FP1200-01 2A/2B; FP1200-02 2A/2B)
• Addressable devices per loop: 126 (900 Series) or 128 (2000 Series)
• Maximum 1008 (900 Series) or 1024 (2000 Series) addressable devices per panel
• Maximum eight loops per panel (FP2000 range only)
• Loop overload: >500 mA
•
Loop operating load: 100 mA maximum
Zone capacity:
•
16 or 64 zones (expandable to 32/128, 48/192 or 64/255 zones in cabinet size B)
•
112 zones for control purposes
LCD screen:
•
Backlit alphanumeric 8 x 40 character LCD
Indicators:
• General indicators
Fire - 2 x LED - Red
Fault - 1 x LED - Amber
Disable - 1 x LED - Amber
Supply fault - 1 x LED - Amber
System fault - 1 x LED - Amber
Processor running - 1 x LED - Green
Supply On - 1 x LED - Green
• Control indicators
Silence buzzer - 1 x LED - Amber
Disable - 1 x LED - Amber
Test - 1 x LED - Amber
Third source test - 1 x LED - Amber
• Sounders indicators
Sound - 1 x LED - Red
Delay On - 1 x LED - Amber
Delay Off - 1 x LED - Amber
Fault/Disable - 1 x LED - Amber
Silence - 1 x LED - Amber
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 9
• Fire brigade indicators
Signal - 1 x LED - Red
Delay On - 1 x LED - Amber
Delay Off - 1 x LED - Amber
Fault/Disable - 1 x LED - Amber
Stop fire brigade - 1 x LED - Amber
• Zone monitoring indicators
Fire - 16/64 x LED - Red (expandable to 32/128, 48/192 or
64/255)
Fault - 16/64 x LED - Amber (expandable to 32/128, 48/192
or 64/255)
•
Indicators related to network facilities
All - 1 x LED - Amber
Panel - 1 x LED - Amber
Membrane keyboard:
1, 2, 3, 4, 5, 6, 7, 8, 9, 0, A .. Z
General control keys:
Silence buzzer
Reset
Disable
Test
Third source test
Sounders control:
Sound
Delay On/Delay Off
Disable
Silence
Fire brigade control:
Signal
Delay On/Delay Off
Disable
Stop fire brigade
Control keys related to network facilities (Excludes FP12xx range):
All
Panel
Control key switch:
Prevents unauthorised resetting and programming of the fire panel.
10 FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Tamper switch (FP2000 Range only):
Fitted to the inside of the fire panel door to record any entry to the cabinet.
Third source (when implemented on the FP2000 range only):
Test button and LED to test total loss of power supply.
Communication ports:
•
2 x DB-9 serial port (set-up, upload/download, internal printer (where applicable),
graphics, remote operation/graphic package)
• 1 x current loop (to connect repeaters and fireman’s panels)
Current Loop:
• Maximum 15 devices
•
Maximum 1 km between 2 current loop devices
•
Aritech FM800 / FR800 - German fire brigade panel (according to DIN 14661) can be
connected.
•
Cable capacitance max. 150 nF
3.2 Panel specifications
3.2.1 Standard Outputs
Standard Outputs
(All standard outputs are
located on the sounder
board.)
OUT 1:
Output to alarm devices
(Sounders)
OUT2:
Output to fire routing
equipment (Fire brigade)
OUT3:
Output to fire protection
equipment
OUT4:
Output to fault warning
routings equipment
FP/FR1xxx & FR2000
(
FP1100 and FP1216 only;
FP1200 optional – SD1200
board used)
A: 24 V – 100 mA supervised*
(Supervision at 5V max.)
B: 3K3/680 Ohm switched
output
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
FP1216EN & FP1264
(SD2000 board)
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
FP/FR2xxx
(FP2xxx only -
SD2000 board used)
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680
output
A: 24 V - 0.8 A
supervised (Supervision
at 5V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 11
* The maximum specified current of 100 mA for Output 1 and Output 2 can be exceeded as long as the total
current drawn by the outputs (1-4) is limited to 400 mA.
3.2.2 Standard Inputs
Standard Inputs
Sounder card 4 x supervised inputs
FEP board (FP2xxx and
FB2x00 only)
FP/FR1xxx & FR2000
(FP1100 and FP1216
only; FP1200 optional –
SD1200 board used)
(inputs 1-4)
3.3 kOhm termination
4 x auxiliary inputs
FP1216EN & FP1264
(SD2000 board)
4 x supervised inputs
(inputs 1-4)
3.3 kOhm termination
FP/FR2xxx
(FP2xxx only – SD2000
board used)
4 x supervised inputs
(inputs 1-4)
3.3 kOhm termination
15 VAC or 20-28 VDC
3 mA
3.2.3 Power Supply Characteristics
Power Supply
Characteristics
Input 230 VAC (+10%, -
Output Aux. Power:
Supervisory - Mains fail
FP/FR1xxx &
FR2000
15%)
50 Hz (±10%)
50 VA
21 – 28 VDC
24 V standby battery
19-27.5 VDC, 100
mA (max)
Modem: 5 VDC
(±0.1V), 75mA (max)
Battery charge: 27.6
VDC (±0.2 V) @ 25
°C, 300 mA (max)
- Battery disconnect
FP1216EN &
FP1264
230 VAC (+10%, 15%)
50 Hz (±10%)
220 VA
21 – 28 VDC
24 V standby battery
Aux. Power: 19-27.5
VDC, 100 mA (max)
Modem: 5 VDC
(±0.1V), 75 mA
(max)
Battery charge:
27.6 VDC (±0.2 V) @
25 °C, 1.6 A (max)
- Mains fail
- Battery disconnect
FP/FR2xxx
230 VAC (±15%)
50 Hz (±10%)
200 VA
21 – 28 VDC
24 V standby battery
Auxiliary Voltage:
20.5-28 V
27.6V DC battery
charge voltage, 4A
total (battery charge
and aux. with or
without batteries.)
- Mains fail
- Battery disconnect
FR2032/20128
FR2064/20255
21 – 28 VDC
24 V standby battery
- Mains fail
- Charger fail
12 FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Power Supply
Characteristics
Fuses AC fuse – 0.8 A,
Maximum current
drawn from the
primary input
Maximum output
ripple voltage
Fault Relay
(Configuration
depended on jumper
setting – refer to
section 6.4.2.2.)
FP/FR1xxx &
FR2000
- Battery flat
- Flat battery cut-out
- Earth fault
- Auxiliary supply
fault
250 V, T
(20 mm STD fuse)
250 mA 1 A 1 A 0.3 A (no options
± 300 mV ± 300 mV ± 300 mV
Maximum switching
current:
2A @ 24 VDC
Maximum power
rating:
50 W
FP1216EN &
FP1264
- Battery flat
- Flat battery cut-out
- Earth fault
- Auxiliary supply
fault
AC fuse – 2 A,
250 V, T
(20mm STD fuse)
Maximum switching
current:
2 A @ 24VDC
Maximum power
rating:
50 W
FP/FR2xxx
- Battery flat
- Flat battery cut-out
AC fuse – 2 A
(20 mm STD fuse)
Aux. Output – 5 A
(20 mm STD fuse)
Battery fuse – 5 A
(20 mm STD fuse)
- -
FR2032/20128
FR2064/20255
Fuse – 1 A
(20 mm STD fuse)
installed)
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 13
3.2.4 Panel Operation
Battery operation - Normal operation
(No mains power)
Current required by system 200 mA (max) 200 mA (max) 200 mA (max)
Loop current
- 2 loops
- 127 devices/loop @ 340 µA/device (DP951)
Auxiliary current 0 mA 0 mA 0 mA
Total normal current 286 mA 200 mA 286 mA
FP12XX FR1200/FR2000 FP1216EN & FP1264
86 mA
0 mA
86 mA
Battery Operation - Alarm Operation
(No mains power)
Normal current (as above) 286 mA (max) 200 mA (max) 286 mA (max)
Extra loop current (20 x LED @ 4 mA) 80 mA 0 mA 80 mA
Sounders (Sounder board: Outputs 1-4) 200 mA 0 mA 200 mA
Total alarm current 566 mA 200 mA 566 mA
FP12XX FR1200/FR2000 FP1216EN & FP1264
Normal Operation FP2416/2464 & FP2432/24128 FP2864, FP28255
Mains load (maximum) 200 VA 200 VA
Total output current (27.6 V) 4 A 4 A
Battery capacity I
Battery capacity (maximum) 69 AH 69 AH
Required battery charging current
(Maximum battery capacity)
Current required by system (I
Available auxiliary current 0.45 A 0.15 A