Interlogix D2300CPS User Manual

Installation Instructions
Model D2300CPS Fiber Optic Interface
Fire Safety
INTRODUCTION
The Model D2300CPS from Siemens Building Tech­nologies, Inc. (See Figure 1) is a Fiber Optic interface for the MXL’s RS-485 network (MNET or XNET) or the FireFinder XLS network (HNET or XNET). It uses a two-fiber (duplex) pair between each device. The D2300CPS can function as either a repeater or an end point unit.
D2300CPS
A
B
RS485
POWER
DATA REC
DATA XTMR
DATA REC
DATA XTMR
WARNING: This module is NOT backwards compatible with the existing 2300CP. This unit uses +24VDC. Make sure to read the front of the module and connect to the correct voltage. Otherwise, serious damage to the unit will result.
Figure 1
D2300CPS Module
The D2300CPS can operate in either a daisy chain (See Figure 2) or star configuration (See Figure 3). This allows for network configurations that are not possible with the RS-485 network alone.
POWER
(DO NOT USE) -4 (DO NOT USE) -3
-DATA-2 +DATA-1
+24 VDC
-2
-1
MOUNTING
The D2300CPS has four keyhole slots for #6 screws. Mount the device in the locations listed below using the four #6 screws provided.
A bracket (P/N 500-692880) is available for mounting the D2300CPS in any MXL enclosure that will accept a MOM-4 (See Figure 4). This bracket has the same footprint as the MOM-4 and accommodates two D2300CPS modules. An assembly kit is included with the bracket that contains four nuts and eight screws. Mount the bracket in the enclosure with the four nuts at the positions labeled X (See Figure 4). Start four of the 6-32 screws and slip the keyhole slots in the D2300CPS
System 3 style rails that mount on an MBR-2 or MME-3 backbox (P/N MSR-1) are also available and can be used for mounting the D2300CPS with the System 3 MPFO Bracket. Up to three brackets can be installed on a single rail.
A bracket, Model D2300-MP, is available for mounting two D2300CPS modules in any FireFinder XLS CAB enclosure. The D2300-MP fits in the same footprint as a CC-5 and mounts to the CAB-MP. A hardware kit is provided for attaching the D2300-MP to the CAB-MP and mounting two D2300CPS modules onto the D2300-MP. Mount the D2300CPS modules prior to installing the D2300-MP onto the CAB-MP. Note that when using two D2300CPS modules, the center two mounting holes on each D2300CPS share the two center studs on the D2300-MP (See Figure 5).
over them. Tighten the four screws.
WARNING:
The D2300CPS module is not listed for use by Factory Mutual. Applications requiring fiber con­nectivity of voice modules/systems are therefore not Factory Mutual listed.
WARNING:
Do not use the D2300CPS with CXL Systems.
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-050018-0
ELECTRICAL CONNECTIONS
POWER INPUT
The D2300CPS uses filtered or unfiltered 24 VDC. The D2300CPS can only be powered from the sources listed in Table 1 on page 6.
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
DUPLEX OPTICAL FIBER
POWER BUDGET - MAX LOSS
-13 dB 62.5/125 FIBER
- 9 dB 50/125 FIBER
DUPLEX OPTICAL FIBER
POWER BUDGET - MAX LOSS
-13 dB 62.5/125 FIBER
- 9 dB 50/125 FIBER
CONNECTION
POWER
DATA
XTM
DATA
REC
B
D2300CPS
POWER
+24 VDC
-2
-1
NO
DATA
REC
DATA
XTMR
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
EOLR 120 OHMS, 1/4W P/N 140-820150
RS-485 32 NODES MAX SUPERVISED
SUPERVISED
PSR-1
POWER
DATA
XTMR
DATA
REC
B
D2300CPS
POWER
+24 VDC
-2
-1
DATA
XTMR
DATA
REC
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
EOLR 120 OHMS, 1/4W P/N 140-820150
RS-485 32 NODES MAX SUPERVISED
EOLR 120 OHMS, 1/4W P/N 140-820150
SUPERVISED
RCC-1
RCC-1
CONNECTION
POWER
DATA
XTMR
DATA
REC
B
D2300CPS
POWER
+24 VDC
-2
-1
NO
DATA
XTMR
DATA
REC
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
EOLR 120 OHMS, 1/4W P/N 140-820150
USE THE 120 ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
W,
32 NODES MAX
MMB
SUPERVISED
PSR-1
Figure 2
Daisy Chain Configuration (MNET Shown)
2
RS-485
EOLR 120 OHMS, 1/4W P/N 140-820150
CONNECTION
POWER
DATAPXTMR
DATAPREC
B
DUPLEX OPTICAL FIBER
POWER BUDGET - MAX LOSS
-13 dB 62.5/125 FIBER
- 9 dB 50/125 FIBER
NO
DATAPXTMR
DATAPREC
A
CONNECTION
DATA
XTMR
DATA
REC
B
NO
POWER
DATA
XTMR
DATA
REC
A
CONNECTION
POWER
DATA
XTMR
DATA
REC
B
NO
DATA
XTM
DATA
REC
A
SUPERVISED
TO ADDITIONAL D2300CPS MODULES
D2300CPS
POWER
+24 VDC
-2
-1
USE THE 120 ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
W,
D2300CPS
POWER
+24 VDC
-2
-1
RS-485 32 NODES MAX SUPERVISED
MMB
D2300CPS
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
POWER
+24 VDC
-1
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
-2
PSR-1
EOLR
PSR-1
120 OHMS, 1/4W P/N 140-820150
Figure 3
Star Configuration (MNET Shown)
3
X
-1
-2
-DATA-2
+DATA-1
+24VDC
(DONOT USE) -4
(DONOT USE) -3
POWER
BRACKET
P/N 500-692880
D2300CPS
A
B
DATAPREC
DATAPREC
DATAPXTMR
POWER
-DATA-2
+DATA-1
(DONOT USE) -4
(DONOT USE) -3
DATAPXTMR
-1
-2
+24VDC
POWER
OMM-1
D2300CPS
A
B
DATAPREC
DATAPREC
DATAPXTMR
DATAPXTMR
POWER
X
WARNING
DISCONNECT POWER
PRIOR TO REMOVING TERMINAL
BLOCK PROTECTION
Figure 4
Mounting the D2300CPS in an MBR-2 or MME-3 Backbox
FIBER OPTIC CABLE
D2300-MP
POWER
DATA
XTMR
DATA
XTMR
DATA
REC
DATA
B
D2300CPS D2300CPS
POWER
+24 VDC
-2
-1
REC
A
POWER
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
+24 VDC
-DATA-2
-1
POWER LIMITED HNET/XNET
ROUTE AS SHOWN
_
TB1
P5
1
1
P4
34
7
PSC-12
RESET
POWER
MODULE FAIL
CAN FAIL
HNETFAIL
GND FAULT
24V 12AFAIL
24V 4AFAIL
+
1
-
HNET
BATTERY
O OFF
19
13
12
+
+
3
2
-
-
ON
TB2
24
18
Z O N E 1
Z O N E 2
+
-
DLC
RESET
POWER
CARDFAIL
HNETFAIL
GNDFAULT
ALARM
TROUBLE
ZONESSTATUS
CLASSA OPEN
CLASSA RETURN
SHORT
CLASSA OPEN
CLASSA RETURN
SHORT
+
1
2
-
HNET
+
3
-
POWER
DATA
XTMR
DATA
XTMR
DATA
REC
DATA
B
REC
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
-2
NIC-C
RESET
POWER
CARDFAIL
CANFAIL
HNETFAIL
XNETFAIL
GNDFAULT
LOOPA FAIL
LOOPB FAIL
ACTIVENETWORKS
CAN
HNET
XNET
HNET/XNETSTYLE
STYLE7
STYLE4
GROUNDFAULT
ENABLED
DISABLED
NETWORK PORT
+
+
+
3
1
2
-
-
-
HNET
+
6
2
1
TB3
12
P12
H N GND
2
1
P9
_
+
_
TB4
+
CAB-1
Figure 5
Mounting the D2300CPS in a CAB-1 Backbox
4
POWER BUDGET - MAX LOSS
SUPERVISED
-13 dB 62.5/125 FIBER
- 9 dB 50/125 FIBER
N.C.
N.C.
DATA REC
DATA XTMR
DATA REC
DATA XTMR
DATA REC
DATA XTMR
DATA REC
DATA XTMR
A
B
A
B
D2300CPS
D2300CPS
END POINT
FACP
RS-485 NETWORK MNET/HNET/XNET (SEE FIGURES 7,8&9)
REPEATER
FACP
POWER BUDGET - MAX LOSS
SUPERVISED
-13 dB 62.5/125 FIBER
- 9 dB 50/125 FIBER
N.C.
N.C.
DATA REC
DATA XTMR
DATA REC
DATA XTMR
A
B
D2300CPS
END POINT
FACP
Figure 6
Wiring the D2300CPS as both a Repeater and End Point Unit
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
(DO NOT USE) (DO NOT USE)
D2300CPS
(DO NOT USE) (DO NOT USE)
D2300CPS
(DO NOT USE) (DO NOT USE)
D2300CPS
-DATA
+DATA
-DATA
+DATA
-DATA
+DATA
-4
-3
-2
-1
-4
-3
-2
-1
-4
-3
-2
-1
EOLR
120 OHMS, 1/4W
P/N 140-820150
STYLE 4 MNET
SUPERVISED
W,
USE THE 120 ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
SUPERVISED
EOLR 120 OHMS, 1/4W P/N 140-820150
1234
SUPERVISED
120 OHMS, 1/4W
P/N 140-820150
EOLR
TB1
(DO NOT USE)
4
(DO NOT USE)
3
2
1
REFER TO NET-7 INSTALLATIONINSTRUCTIONS P/N 315-091914
MMB
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
TB1
NET-7
MOM-4
STYLE 7 MNET
Figure 7
Wiring the RS-485 MNET Network in Style 4 and Style 7
5
1elbaT
METSYSECRUOSREWOP
LXM21-95BT;5-41BT:2-BMM
SLXredniFeriF-,+4BT:21-CSP
ECRUOSREWOP
3-DAP-,+XUA
53-SP6-51BT
21-95BT;-,+9BT:3-BMM
6-3;2-13BT:1-RSP
+4BT:21-XSP
-,
For non-power limited wiring, the PLM-35 (Installation Instructions P/N 315-093495) must be used to comply with NFPA 70 per NEC 760. All wiring must be in accordance with Article 760 of NEC or local building codes.
For additional information on the MXL/MXLV System, refer to the MXL/MXLV Manual, P/N 315-092036.
24 VDC CURRENT CALCULATION (MXL ONLY)
The 24 VDC output ratings for the MMB/SMB and PSR-1 are:
MMB-2/-3 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) SMB-2 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) PSR-1 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12)
The following modules all draw current from the 24 VDC supply. Add the value for each module that is installed in the enclosure where the D2300CPS is to be installed. Be sure to include the D2300CPS in this calculation.
CDV42EVITCA
ELUDOM
1-MCAAm58 1-CSAAm14 2-CSAAm16
003-IMCAm0
4-MRCAm57
4-MSC
4-MZC
SPC0032DAm75
4-/2-BKMAm0 4-TENAm0 7-TENAm0
M7-TENAm0
7-IOMAm021
61-DOMxamAm058
MxamAm23
61-DI
1-MIPAm0
1-CTBAm44
1-MCRAm031
03-CAZW03taA3
1-CCOAm71
B8-1CZAm071 B8-2CZAm243
BA4-2CZAm761 BA4-3CZAm861
B8-TCZAm8
ELUDOM
TNERRUCYTITNAUQLATOT
xamA5.1+Am43
ucricrep
ti
Am027
mralanisenoz4
7
LATOT
6
(DO NOT USE)
(DO NOT USE)
D2300CPS*
-DATA
+DATA
EOLR
-4
-3
-2
-1
*
120 OHMS, 1/4W
P/N 140-820150
SUPERVISED
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
*
(DO NOT USE)
(DO NOT USE)
D2300CPS
-4
-3
-DATA
-2
+DATA
-1
120 OHMS, 1/4W
P/N 140-820150
SUPERVISED
EOLR
Figure 8
Wiring the RS-485 XNET Network
in Style 4 and Style 7 (MXL)
RS-485 NETWORK
The RS-485 MNET, XNET and HNET networks connect to the D2300CPS on the terminal block with the markings +DATA (1) and -DATA(2). Terminals 3 and 4 are not used. For Style 4 networks one D2300CPS is needed at each Fiber Optic drop. For Style 7 networks two D2300CPS modules are needed at each drop.End of line devices are required on each RS-485 pair in the system. Install them at the extreme ends of each pair. Refer to Figures 7 and 8 (MXL) and Figure 9 (FireFinder XLS) for wiring instructions and ratings for both Style 4 and Style 7.
NOTE: Positive and negative ground fault detected
when terminals shorted to earth.
FIBER CONNECTIONS
*
OMIT THIS EQUIPMENT FOR STYLE 4 XNET
EOLR
120 OHMS, 1/4W
P/N 140-820150
1234
REFER TO NIM-1R OR NIM-1W INSTALLATION INSTRUCTIONS P/N 315-092953 OR P/N 315-099165, AS APPLICABLE
TB3
NIM-1R/-1W
MOM-4
When installing the fiber pairs, each fiber must connect between the transmit data (DATA XTMR) on one D2300CPS and the receive data line (DATA REC) on the other D2300CPS.
The D2300CPS fiber connection is classified as Style DCLB per ULC-527.
INDICATORS
The D2300CPS has five LED indicators for Power and Status.
The LEDs are located on the side of the module with the Fiber Optic connectors. The Power LED is green and lights whenever there is 24 VDC. Both channels A and B have a yellow and green LED. The green LED indicates that the D2300CPS is transmitting data on that channel. The yellow LED lights when data is received.
The D2300CPS can function as both a repeater and an end point unit. When used as an end point, connect to the fiber connectors labeled A. Make no connec­tion to the B connectors. In the repeater mode, use both pairs of connectors, A and B.
Two Fiber Optic cables are required between each pair of D2300CPS modules. Use a high quality duplex Fiber Optic cable containing either 50/125 or 62.5/125 fiber. Duplex fiber optic cable has two cables in a single shield similar to electrical zip cord. Use ST style fiber connectors. Please contact the fiber manufacturer
regarding instructions for terminating the fiber.
ELECTRICAL RATINGS
tnerruCeludoMCDV42evitcAAm75
tnerruCeludoMCDV42ybdnatSAm75
Input Power 18-31 VDC, 57mA max Battery Power 24 VDC, 57mA max RS-485 8V (P-P), 150mA max Transmitter Power 20µW (-17dBm)
(62.5/125 Fiber)
7
(DO NOT USE)
(DO NOT USE)
-DATA
+DATA
EOLR
-4
-3
-2
-1
120 OHMS, 1/4W
P/N 140-820150
D2300CPS
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
NO EOLR REQUIRED AT THE NIC-C
STYLE 4 HNET/XNET
(DO NOT USE)
(DO NOT USE)
-DATA
+DATA
D2300CPS
-4
-3
-2
-1
SUPERVISED
DO NOT USE
12345678
910111213141516
DO NOT USE
NIC-C
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
DO NOT USE
EOLR
120 OHMS, 1/4W
P/N 140-820150
(DO NOT USE)
(DO NOT USE)
D2300CPS
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
NO EOLR REQUIRED AT THE NIC-C
-DATA
+DATA
-4
-3
-2
-1
SUPERVISED
SUPERVISED
DO NOT USE
12345678
910111213141516
DO NOT USE
DO NOT USE
NIC-C
ONE SLOT OF CC-5/CC-2
STYLE 7 HNET/XNET
17 18 19 20 21 22 23 24
DO NOT USE
Figure 9
Wiring the RS-485 HNET or XNET Network in Style 4 and Style 7 (FireFinder XLS)
P/N 315-050018-0
Contacting us
For help installing, operating, maintaining, and troubleshooting this product, refer to this document and any other documentation provided. If you still have questions, contact us during business hours (Monday through Friday, excluding holidays, between 5 a.m. and 5 p.m. Pacific Time).
Table 3. Sales and support contact information
Sales Technical support
Phone:
Toll-free: 888.437.3287 in the US, including Alaska and Hawaii; Puerto Rico; Canada.
Outside the toll-free area: 503.885.5700.
E-mail
Fax
888.329.0331 888.329.0332
techsupport@interlogix.com
Note: Be ready at the equipment before calling.
Online
Another great resource for assistance with your Interlogix product is our online publication library. To access the library, go to our website at the following location:
http://www.interlogix.com
1
1. Many Interlogix documents are provided as PDFs (portable document format). To read these documents, you will
need Adobe Reader, which can be downloaded free from Adobe’s website at www.adobe.com.
Copyright © 2011 UTC Fire & Security. All rights reserved.
r
Trademarks and
patents
Manufacture
Certification
FCC compliance Class A: This equipment has been tested and found to comply with
Interlogix and IFS names and logos are trademarks of
UTC Fire & Security. Other trade names used in this document may be trademarks or
registered trademarks of the manufacturers or vendors of the respective products.
UTC Fire & Security Americas Corporation, Inc.
2955 Red Hill Avenue, Costa Mesa, CA 92626-5923, USA Authorized EU manufacturing representative:
UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert, The Netherlands
N4131
the limits for a Cla Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
ss A digital device, pursuant to part 15 of the FCC
ACMA compliance Notice! Thi
product may cause radio interference in which case the user may be required to take adequate measures.
Canada This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-0
European Union
directives
Contact information For contact information, see www.interlogix.com.
2004/108/EC (EMC directive): Hereby, UTC Fire & Security
decl
ares that this device is in compliance with the essential requirements and other relevant provisions of Directive 2004/108/EC.
2002/96/EC (WEEE directive): Products marked with this symbol
cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
s is a Class A product. In a domestic environment this
03 du Canada.
Loading...