Interlogix Concord 4 REV J Installation Manual

Concord 4 Installation Manual
P/N 466-2182 • REV J NOV12
Copyright
© 2012 UTC Fire & Security Americas Corporation, Inc. Interlogix is part of UTC Climate Controls & Security, a unit of United Technologies
Corporation. All rights reserved.
This document may not be copied in whole or in part or otherwise reproduced without prior written consent from UTC Fire & Security, Inc., except where specifically permitted under US and international copyright law.
Disclaimer
The information in this document is subject to change without notice. UTC Fire & Security assumes no responsibility for inaccuracies or omissions and specifically disclaims any liabilities, losses, or risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document. For the latest documentation, contact your local supplier or visit us online at www.utcfireandsecurity.com.
This publication may contain examples of screen captures and reports used in daily operations. Examples may include fictitious names of individuals and companies. Any similarity to names and addresses of actual businesses or persons is entirely coincidental.
Trademarks and
patents
Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.
Intended use
Use this product only for the purpose it was designed for; refer to the data sheet and user documentation for details. For the latest product information, contact your local supplier or visit us online at www.utcfireandsecurity.com.
Contact information
www.utcfireandsecurity.com. or www.interlogix.com
Technical support
www.interlogix.com/customer-support.
Content
Important information iii
Chapter 1 Introduction 1
Planning the installation 2 SuperBus 2000 bus devices 3
Chapter 2 Installation 5
Installation overview 6 Mounting the panel 10 Intrusion detection devices 15 Smoke detectors 15 Speakers and sirens 18 SuperBus 2000 touchpads 22 SuperBus 2000 modules 22 Phones 28 Power 30
Chapter 3 Programming 33
Overview 34 Quick programming mode 36 Tier 1 programming menus 37 Tier 2 programming menus 40 Security menu 45 Phones menu 50 Phone options menu 54 Timers menu 57 Light control menu 59 Touchpad options menu 60 Reporting menu 61 Siren options menu 66 Sensors menu 67 Audio verification menu 71 Accessory modules menu 73 Onboard options menu 78 Macro keys menu 81 User programming mode 82 Downloader programming 93
Chapter 4 Testing and troubleshooting 95
Testing the system 96
Concord 4 Installation Manual i
Troubleshooting 106
Appendix A System planning sheets 117
Customer information 118 Wireless devices 118 Hardware devices 119 Zone and sensor assignments 121 System settings index and record 124
Appendix B Reference tables 129
Sensor group characteristics 130 Sensor text 134 System event triggers 136 Sensor group event triggers 137 Sensor number event triggers 138 System feature event triggers 141 Response characteristics 143 Response numbers 143 Specifications 145
ii Concord 4 Installation Manual
600-1021-95R
Concord 4 RF
600-1022-95R
Concord Express V4
600-1040
Concord Commercial V4
600-1042
Concord Hybrid
Important information
Intended use
Use this product only for the purpose it was designed for; refer to the data sheet and user documentation for details. For the latest product information, contact your local supplier or visit us online at www.utcfireandsecurity.com.
Changes or modifications not expressly approved by UTC Fire & Security can void the user’s authority to operate the equipment.
About this manual
This manual provides information for planning, installing, programming, and testing this security system. Planning sheets are included for you to record hardware layout and software programming settings.
Use this manual for the following panels:
When necessary, this manual refers you to other documentation with compatible peripherals.
The Concord 4 User Manual (P/N 466-2183) contains user worksheets that you should fill out during the installation and programming of the system. For multiple-partition systems, we suggest a user manual for each partition.
Read these instructions and all related documentation entirely before installing or operating this product.
Note: A qualified service person, complying with all applicable codes, should
perform all required hardware installation.
Concord 4 Installation Manual iii
Chapter 1
Introduction
Summary
This chapter provides information to help you plan your Concord 4 panel and system installation.
Content
Planning the installation 2
Standard panel 2
SuperBus 2000 bus devices 3
Concord 4 Installation Manual 1
Chapter 1: Introduction
Capabilities
Concord Express v4
Concord 4/Concord Commercial v4
Zones
32
96
Partitions
2
6
Bus devices
16
16
User codes
16
230
Power
Input for an AC step-down, plug-in style transformer.
Auxiliary power output
Output that supplies 9 to 14 VDC with up to 1 amp for bus devices and hardwired detectors, such as smoke and motion detectors.
Bus A and B
Input and output that provides communication between bus devices and the panel.
Siren driver
Output that can drive an 8-ohm load and provides intrusion and fire alarm sounds for partition 1 (15 watts maximum).
Two onboard outputs
Can be used to activate other signaling devices based on system events. Out 1 is a 9 to 14 VDC source output, limited to 1.0 amp max. Out 2 is an open-collector output, rated up to 14 VDC, 300 mA max
Microphone input
Input used for 2-way audio when used in conjunction with the Interrogator 200 audio verification module.
Eight supervised hardwired zones
Inputs for various hardwired detectors. Zone 8 can be set up in programming to accept two-wire smoke detectors. It sources 9 to 14 VDC, 90mA max.
Planning the installation
This section describes system capabilities to help you get familiar with the system. Appendix A System planning sheetson page 117 provides planning sheets that let you record the hardware and programming configuration of the system. Fill in all necessary information ahead of time to help prepare for system installation.
Standard panel
Table 1 below shows the standard panel capabilities.
Table 1: Panel capabilities
Table 2 describes the basic panel (out-of-box) hardware capabilities for all panels.
Table 2: Basic panel hardware capabilities
2 Concord 4 Installation Manual
Chapter 1: Introduction
Built-in RF receiver
Allows use of up to 96 (Concord 4) or 32 (Concord Express v4)
319.5 MHz. crystal and/or SAW learn mode wireless sensors and touchpads.
Phone line connection
Allows panel to communicate with central monitoring station and/or pagers.
Touchpads
Use the following touchpads for installer/user programming and system operation.
SuperBus 2000 2x16 LCD touchpad
SuperBus 2000 2x20 LCD touchpad
SuperBus 2000 2x20 VFD touchpad
SuperBus 2000 ATP 1000 touchpad
SuperBus 2000 ATP 2100 touchpad
SuperBus 2000 ATP 2600 touchpad
Use the following touchpads for installer quick programming, system operation and user programming:
SuperBus 2000 fixed display touchpad
SuperBus 2000 FTP 1000 touchpad
SuperBus 2000 RF transceiver
Use the transceiver to receive signals from sensors and touchpad that may be on the fringe of panel reception. The transceiver is compatible with all 319.5 MHz crystal and SAW learn mode wireless sensors and touchpads.
Power line carrier transformer
Allows the use of X10 powerhouse lamp modules for light control and light activation during alarms.
SuperBus 2000 voice only module
Provides an output for a speaker that sounds system status and alarm voice messages.
SuperBus 2000 phone interface/voice module
Allows system access and control using touchtone telephones, onsite or offsite. The module includes an output for a speaker that sounds system status and alarm voice messages
SuperBus 2000 bus devices
The following components can be used with the Concord 4 panel:
Table 3: SuperBus devices
Concord 4 Installation Manual 3
Chapter 1: Introduction
SnapCards
The following SnapCards expand the system as described: 8Z input Snapcard: Provides eight additional hardwired zone
inputs, of which two are dedicated for using two-wire smoke detectors.
4 output SnapCard: Provides four form C relay outputs that can be set up to activate other signaling devices, based on system events, schedules, or direct control.
4Z input/output combo SnapCard: Provides three hardwired zone inputs, one two-wire smoke detector loop, and two outputs that can be set up to activate other signaling devices, based on system events, schedules, or direct control.
SuperBus 2000 8Z input module (HIM)
Provides eight additional hardwire zone inputs.
SuperBus 2000 four-relay output module (HOM)
Provides four form C relay outputs that can be set up to activate other signaling devices, based on system events.
Interrogator 200 audio verification module
Allows central station operators to listen in and talk to occupants on the premises to verify the emergency when an alarm report is received.
SuperBus 2000 energy saver module (ESM)
Provides a money-saving and convenient way to monitor and control temperatures. The ESM uses low- and high­temperature limits to save energy by overriding the existing HVAC thermostat.
SuperBus 2000 automation module
Provides a connection to a compatible home automation device.
SuperBus 2000 wireless cellular gateway
Allows users to control and monitor the status of their system from the alarm.com internet website.
SuperBus 2000 2-amp power supply
Provides an additional 12 VDC, 2 amps for powering system devices and is supervised via the panel data bus.
4 Concord 4 Installation Manual
Chapter 2
Installation
Summary
This chapter provides information on locating and installing the panel and system components.
Content
Error! Bookmark not defined.
Concord 4 Installation Manual 5
Chapter 2: Installation
Installation overview
Before starting the installation, plan your system layout and programming using the worksheets provided in Appendix A System planning sheetson page 117.
Note: Class 2, Class 3, and power-limited fire alarm circuits must be installed
using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical Code ANSI/NFPA 70 or Class 2, Class 3, and power-limited fire alarm circuit conductors must be installed as Class 1 or higher circuits.
Note: Class 2, Class 3, and power-limited burglar alarm circuits must be installed
using CL2, CL2R, CL2P, or substituting cable permitted by ANSI/NFPA 70. Wire that extends beyond the cable jacket must be separated from all other conductors by a minimum of 0.25 in. or by a nonconductive barrier.
Use the following installation guidelines:
Centrally locate the panel with relation to detection devices whenever possible, to help reduce wire run lengths and labor.
Locate the panel where the temperature will not exceed 120°F (49°C) or fall below 32°F (0°C).
Avoid running wires parallel with electrical wiring or fixtures such as fluorescent lighting, to prevent wire runs from picking up electrical noise.
Mount the panel at a comfortable working height (about 45 to 55 in. from the floor to the bottom of the panel, as shown in Figure 1 on page 7).
Leave space to the left and right of the panel for wiring, phone jack, and mounting optional modules. Allow at least 9 in. (23 cm) above the panel cabinet for antennas. Allow at least 24 in. (62 cm) in front of the panel to open the panel door.
6 Concord 4 Installation Manual
Chapter 2: Installation
Figure 1: Panel and component locations on a wall
Total system power and wire length guidelines
The panel can supply up to 1 amp (1,000 mA) in full load alarm condition for system devices connected to panel terminals 4 (+12V), 7 and 8 (speaker terminals), 9 (OUT1), 11 (+12V), 24 (2W SMK ZONE 8), and SnapCard terminals.
For 24-hour backup, the total standby current draw for all devices connected to panel terminals 4 (+12V), 9 (OUT1), 11 (+12V), 24 (if configured for 2-wire smoke loop), and SnapCard terminals is limited to 90 mA (during normal standby condition) using a 4.5 or 5.0 Ah battery, or 190 mA (during normal standby condition) using a 7.0 Ah battery.
The total system wire length allowed can vary depending on devices powered by the panel, the wire length between devices and the panel, and the combined wire length of all devices.
Concord 4 Installation Manual 7
Chapter 2: Installation
Device
Max. wire length to panel
Standby mA draw
Alarm mA draw
SuperBus 2000 2x16 LCD alphanumeric touchpad
22 ga.: 300 ft. 18 ga.: 750 ft.
15 mA
90 mA
SuperBus 2000 ATP 1000 alphanumeric touchpad
22 ga.: 300 ft. 18 ga.: 750 ft.
12 mA
110 mA
SuperBus 2000 ATP 2100 alphanumeric touchpad
22 ga.: 300 ft. 18 ga.: 750 ft.
30 mA
165 mA
SuperBus 2000 ATP 2600 alphanumeric touchpad
22 ga.: 300 ft. 18 ga.: 750 ft.
30 mA
165 mA
SuperBus 2000 fixed display touchpad
22 ga.: 300 ft. 18 ga.: 700 ft.
11 mA
65 mA
SuperBus 2000 FTP 1000 fixed display touchpad
22 ga.: 300 ft. 18 ga.: 700 ft.
12 mA
75 mA
SuperBus 2000 RF transceiver
22 ga.: 1,000 ft. 18 ga.: 2,500 ft.
45 mA
55 mA SuperBus 2000 phone interface/voice module
22 ga.: 40 ft. 18 ga.: 120 ft.
25 mA
600 mA
SuperBus 2000 voice-only module
22 ga.: 40 ft. 18 ga.: 120 ft.
20 mA
300 mA (jumper) 600 mA (no
jumper)
SuperBus 2000 2 amp power supply
No load
No load
4 input/2 output SnapCard
N/A
20 mA
185 mA*
8Z hardwired zone expander SnapCard
N/A
38 mA
230 mA*
4 output SnapCard
N/A
1 mA
130 mA*
SuperBus 2000 8Z input module
22 ga.: 1,800 ft. 18 ga.: 4,000 ft.
18 mA
35 mA SuperBus 2000 4-relay output module
22 ga.: 350 ft. 18 ga.: 900 ft.
12 mA
180 mA
Table 4 below describes the maximum wire length allowed between compatible devices and the panel, and the minimum and maximum current draw of each device.
Table 4: Wire length requirements
8 Concord 4 Installation Manual
Chapter 2: Installation
Device
Max. wire length to panel
Standby mA draw
Alarm mA draw
SuperBus 2000 energy saver module
22 ga.: 1,600 ft. 18 ga.: 4,000 ft.
20 mA
20 mA
SuperBus 2000 automation module
22 ga.: 1,500 ft. 18 ga.: 4,000 ft.
30 mA
35 mA SuperBus 2000 wireless cellular gateway
22 ga.: 40 ft. 18 ga.: 90 ft.
65 mA
1600 mA
Interrogator 200
22 ga.: 3,200 ft. 18 ga.: 4,500 ft.
10 mA
10 mA Interrogator AVM
22 ga.: 110 ft. 18 ga.: 260 ft.
45 mA
300 mA
Two-wire smoke detectors (ESL 429AT, 429C, 429CT, 521B, 521BXT, 521NCSXT
22 ga.: 330 ft. 18 ga.: 330 ft.
70 µA
60 mA
Two-wire smoke detectors (system sensor 2400, 2400TH)
22 ga.: 330 ft. 18 ga.: 330 ft.
120 µA
80 mA
Hardwired interior siren (13-949)
22 ga.: 750 ft. 18 ga.: 1,500 ft.
0 mA
85 mA
Piezo dynamic exterior siren (13-950)
22 ga.: 750 ft. 18 ga.: 1,500 ft.
0 mA
150 mA
Speaker siren (60-528 or 13-060)
18 ga.: 100 ft.
0 mA
500 mA
*Maximum current draw for the SnapCards does not include the load which may be applied to their auxiliary DC supply.
Wire type
Total system wire
18-gauge, unshielded 18-gauge, shielded
4,000 ft. 3,000 ft.
Table 5 below describes the total system wire lengths allowed for all SuperBus 2000 devices when installing systems using unshielded or shielded cable. After determining panel location, run all necessary wires to that location using the information in Table 6 on page 10.
Table 5: Wire lengths
Concord 4 Installation Manual 9
Chapter 2: Installation
Wire type
Total system wire
22-gauge, unshielded 22-gauge, shielded
4,000 ft. 3,000 ft.
Device
Wire requirements
AC power transformer
2-conductor, 18-gauge, 25 ft. max.
Earth ground
Single conductor, 16-gauge solid, 25 ft. max.
Telephone (RJ-31X)
4-conductor
Detection devices
2- or 4-conductor, 22-gauge, 1,000 ft. max. 2- or 4-conductor, 18-gauge, 2,500 ft. max. (based on 30 ohms max. loop resistance including device)
Speakers
2-conductor, 18-gauge, 100 ft. max.
SuperBus 2000 devices
4-conductor, 22- or 18-gauge
Interrogator 200 AVM power and microphone
4-conductor, 22-gauge, shielded
2-wire smoke detectors
2-conductor, 22-gauge, 330 ft. max. 2-conductor, 18-gauge, 830 ft. max.
Table 6: Device wire requirements
Mounting the panel
Mount the panel to the wall or wall studs.
Caution: Make sure you are free of static electricity whenever you work on the
panel with the cover open. To discharge any static, first touch the metal panel chassis, and then stay in contact with the chassis when touching the circuit board. We recommend using a grounding strap.
To mount the panel:
1. Remove the panel door and remove the necessary wiring knockouts. Be careful not to damage the circuit board.
2. Feed all wires through wiring knockouts and place the panel in position against the wall.
3. Level the panel and mark the top and bottom mounting holes (see Figure 2 on page 11).
4. Install anchors where studs are not present.
10 Concord 4 Installation Manual
Chapter 2: Installation
Mounting hole
Backup battery terminals
Programming
touchpad header
Mounting hole
Antennas
Mounting hole Snapcard connector
Processor
Terminal strip
Mounting hole
Grounding wire
Water pipe
Grounding clamp
5. Partially insert screws into the two top mounting hole locations, then hang the panel on the two screws.
6. Recheck for level, insert the two lower screws, and tighten all four mounting screws.
Figure 2: Panel components and mounting holes
Grounding the panel
For maximum protection from lightning strikes and transients, connect the enclosure to earth ground as shown in Figure 3 below. Use 16-gauge, solid copper wire from an earth grounded cold water pipe clamp to the enclosure.
Figure 3: Grounding the panel
Note: For best results, we recommend that you crimp a spade lug on the wire
end at the panel and secure the lug to the enclosure.
Concord 4 Installation Manual 11
Chapter 2: Installation
Antenna shrouds
Install a plastic antenna shroud (included with panel) over each antenna and snap them into the holes on the top of the enclosure (skip this step for hybrid and commercial systems).
12 Concord 4 Installation Manual
Chapter 2: Installation
Mounting hole
Snapcard connector
Snapcard
Mounting hole
Optional SnapCards
Use the SnapCard header on the right side of the panel (Figure 4 below) to install an optional SnapCard. Install the SnapCard onto the panel SnapCard header and secure it in place with two screws, included with the SnapCard. To connect all necessary input/output wiring, refer to the SnapCard documentation.
Figure 4: Installing a SnapCard
Concord 4 Installation Manual 13
Chapter 2: Installation
TIP
(+)
RING
(-)
BRN
GRY
GRN
RED
(-)
(+)
(-)
(+)
_
+ NC
COM
SW SW GND #1 #2
+12V - Red
BUS A - Green
BUS B - White or Yellow
GND - Black
1
2
3
4
5
6
7 8 9
10
11 12 13
14
15 16 17
18
19
20
21
22
23 24
25 26 27
28
16.5 VAC
GND
+12V
A
B
SPKR SPKR
OUT1 OUT2 +12V MIC GND
ZONE1 ZONE2
GND
ZONE3
ZONE4
GND
ZONE5 ZONE6
GND
ZONE7 ZONE8
GRN
BRN
GRY RED
Panel terminals
Figure 5 below shows an overview of panel terminals. The following sections provide details on how to connect devices to the panel.
Figure 5: Panel terminals
Zones
The panel comes with factory programmed onboard hardwired zones. Install 2 kohm, end-of-line (EOL) resistors on all unused factory programmed onboard hardwired zones. If you don’t want to install EOL resistors, delete any unused zones from memory.
Zone inputs 1 through 8 are supervised using the included 2-kohm, end-of-line resistors at the last device on each circuit. All eight zones accept either normally open (NO) or normally closed (NC) detection devices.
14 Concord 4 Installation Manual
Chapter 2: Installation
Panel terminals
Normally closed (NC) contacts in series
2 kohm resistor
Normally open (NO) contacts in series
2 kohm resistor
Motion detector
GND
ZONE1 ZONE2
GND
ZONE3 +12V
GND
ZONE5
NC
COM
Intrusion detection devices
Figure 6 below shows the typical wiring for NC and NO door/window intrusion detection and the typical wiring for a PIR motion detector. The minimum available panel voltage for hardwired PIR motion detectors is 8.5 VDC.
Figure 6: Connecting intrusion detection and motion detector circuits
Smoke detectors
You can connect two-wire and four-wire smoke detectors to the system.
Two-wire smoke detectors
Zone input 8 can be set up (in program mode) to accept the following 12 VDC, two-wire smoke detectors:
ESL models 429AT, 429C, 429CT, 521B, 521BXT, 521NCSXT (models 521B and 521BXT require the following dip switch settings: 1-on, 2-off)
Caution: Use only the two-wire smoke detector models listed. Alarm signals from
other detectors may not process correctly if the panel loses AC power and is operating only from the backup battery.
When set up for two-wire smoke detectors, zone 8 can handle up to 20 smoke detectors (all of the same model, as listed above) with 120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm condition is 90 mA. Connect one or more, two-wire smoke detectors to the panel as shown in Figure 7 on page 16.
Concord 4 Installation Manual 15
Chapter 2: Installation
GND ZONE 7 ZONE 8 GND ZONE 7 ZONE 8
Two-wire smoke detectors
Four-wire smoke detectors
Panel terminals
Note: When using two-wire smoke detectors on zone 8, the two-wire smoke
setting (in program mode) must be turned on before entering the learn sensors menu.
Figure 7: Connecting two- and four-wire smoke detectors
Note: The two-wire smoke setting (in program mode) must be on when using
four-wire smoke detectors as shown in Figure 7 above. See “Onboard options ­inputs settingson page 78 for complete details.
If two-wire smoke detectors with built-in sounders are used (521INCSXT), a polarity reversal relay (model 405-03) may be used to activate the sounders on all smoke detectors during a fire alarm (see Figure 8 on page 17). An output must be used to activate the polarity reversal relay. This output must be configured for fire alarm trigger, and siren tracking response (001-11).
Note: Onboard outputs 1 or 2, SnapCard outputs, or output module outputs may
be used to activate the polarity reversal relay. Maximum alarm current that the panel can source to all external devices is
limited to 1 amp. Be sure to include the alarm current for all sounder smoke detectors in the alarm current calculation.
16 Concord 4 Installation Manual
Chapter 2: Installation
OUT 2
+12V GND
ZONE 8
2W-SMK
Polarity reversal
module (part # 405-03)
521NCSXT
521NCSXT
Minimum voltage
Maximum current available
8.3 VDC
Up to 30 mA total (combined alarm) current
8.1 VDC
Up to 40 mA total (combined alarm) current
7.6 VDC
Up to 60 mA total (combined alarm) current
7.1 VDC
Up to 80 mA total (combined alarm) current
Figure 8: Polarity reversal module
Four-wire smoke detectors
Terminal 24 provides power to four-wire smoke detectors that latch and remain in the alarm state until power turns off, then restores to the detector. The panel provides this power interruption from terminal 24 (2W SMK ZONE 8) only when the two-wire smoke option is on.
Note: The two-wire smoke feature must be on for smoke detectors to reset after
canceling a fire alarm. Table 7 below describes the minimum available panel power. Use only four-wire
smoke detectors that operate at these power limits. Connect up to five smoke detectors as shown in Figure 7 on page 16.
Table 7: Minimum available panel power
Concord 4 Installation Manual 17
Chapter 2: Installation
Panel terminals
SPKR SPKR
SPKR SPKR
Splice
Two 8-ohm speakers
in series (16 ohms)
Speakers and sirens
The panel provides one siren driver output for intrusion (steady), fire (temporal
3), and auxiliary (on-off-on-off) alarm sounds. This output trips only for partition 1 alarms. Install all sirens/speakers indoors in a concealed location.
Note: Do not connect a bell or piezo siren to the speaker output (terminals 7 and
8). The output can drive a single 8-ohm speaker or a multiple speaker circuit of 8
ohms or higher. When connecting two or more speakers, wire them in series. Wiring speakers in parallel can permanently damage the panel. Compatible speakers are shown below.
Caution: To avoid disabling the panel speaker output, do not make speaker
connections with the panel power on.
15-watt speaker (13-060)
For exterior siren applications, connect the speaker to the panel using 18-gauge wire as shown in Figure 9 below.
Figure 9: Connecting exterior speakers
Hardwired interior speaker (60-528)
Connect interior speakers to the panel (see Figure 10 on page 19) using 18­gauge wire.
Caution: Connect only the large speaker to panel terminals 7 and 8 as shown.
The smaller speaker cannot handle output to terminals 7 and 8. To avoid damaging the speaker, do not connect the smaller speaker to terminals 7 and 8.
18 Concord 4 Installation Manual
Chapter 2: Installation
SPKR SPKR SPKR SPKR
Not used
Not used
7 8 7 8
Figure 10: Connecting hardwired interior speakers
Exterior/interior piezo sirens
Onboard output 1 (OUT 1terminal 9) is a 9 to 14 VDC switched, programmable output that can handle a maximum of 1,000 mA current. The default setting (01614) activates the output 30 seconds after a police or fire alarm condition occurs. This allows you to connect a piezo siren without changing the output configuration number in programming. This output is typically used for exterior siren applications. Connect multiple piezo sirens in parallel. (For more information on output configuration numbers, see “Onboard options menu” on page 78.)
Note: For 24-hour backup, external power drain is limited to 90 mA (during
normal standby condition), using a 4.5 or 5.0 Ah battery, or 190 mA continuous using a 7.0 Ah battery.
Piezo dynamic exterior siren (13-950)
Connect the siren to panel as shown in Figure 11 on page 20.
Concord 4 Installation Manual 19
Chapter 2: Installation
Panel terminals
Red
Black
OUT1 GND
OUT2 +12V
To zone input
2 kohm resistor
Figure 11: Connecting exterior sirens
Output 2
Onboard output 2 (OUT 2terminal 10) is an open-collector (switched path-to­ground), programmable output that can handle a maximum of 300 mA current sink and up to 14 VDC. The default setting (01710) activates the output for status and alarm tones, allowing for a piezo siren connection without changing the output configuration number. This output is typically used for interior siren applications. (For more information on output configuration numbers, see Onboard options menu” on page 78.)
Hardwired interior siren (13-949)
This siren has two inputs, steady (#1) and warble (#2). Use the steady (#1) terminal for Concord 4 panels. The siren also includes a cover tamper switch that can be connected to a hardwired zone input on the panel, SnapCard or SuperBus 2000 hardwired input module. Connect the siren to the panel/zone input terminals as shown in Figure 12 below.
Figure 12: Connecting an interior siren
20 Concord 4 Installation Manual
Chapter 2: Installation
Panel terminals
SPKR
SPKR +12V MIC GND
Yellow
Splice
Audio verification module
Interrogator 200 audio verification module
A maximum of two audio veification modules (AVM) are allowed (partition 1 only). Connect the Interrogator 200 AVM to the panel terminals as shown in Figure 13 below. Use shielded cable to prevent crosstalk between the speaker and microphone.
Figure 13: Connecting an Interrogator 200
Caution: If a speaker is already connected to panel terminals 7 and 8, the
Interrogator 200 speaker must be hooked up in series with that speaker to provide a 16-ohm load. Hooking up speakers in parallel to panel terminals 7 and 8 creates a 4-ohm load that can cause permanent damage to the panel.
Concord 4 Installation Manual 21
Chapter 2: Installation
Panel terminals
Touchpad with wires
Touchpad with terminals
GND +12V A BUS B GND +12V A BUS B
+12V - Red
A
+12V
B
GND/COM
BUS A - Green
BUS B - White or Yellow
GND - Black
SuperBus 2000 touchpads
SuperBus 2000 touchpads may have wires or screw terminals. All use the same wiring scheme for power and bus connections. Connect touchpads as shown in Figure 14 below.
Figure 14: Connecting touchpads
SuperBus 2000 modules
You may install SuperBus 2000 modules inside the panel cabinet or away from the panel in the enclosure provided with the module.
Mounting modules inside the panel enclosure
Use the following guidelines when mounting modules inside the panel enclosure (Figure 15 on page 23):
Up to four of the SuperBus 2000 modules listed in Table 3 on page 3 can be mounted inside the cabinet.
The 2-amp power supply and phone interface/voice module each use two mounting spaces when mounted inside the panel enclosure.
The panel includes two support standoffs you install to secure module bookplates to the panel.
Even if you don’t plan to mount modules inside the cabinet, install the support
standoffs for future use and to avoid losing them. The cabinet has built-in mounting clips on the top and sides that module
backplates slide onto for mounting.
22 Concord 4 Installation Manual
Chapter 2: Installation
Panel terminals
Power supply terminals
To power inputs on devices
GND +12V A BUS B
Figure 15: Installing SuperBus 2000 modules
SuperBus 2000 2-amp power supply (600-1019)
Refer to the power supply documentation for the mounting procedure. Connect the power supply to the panel terminals and devices to be powered as shown in Figure 16 below.
Note: Do not connect power (AC and battery) to the power supply until the panel
is ready for power-up. For power supply AC and battery connections, refer to the power supply documentation.
Figure 16: Wiring the SuperBus 2-amp power supply to the panel
SuperBus 2000 transceiver modules
The transceiver expands RF reception range when placed near sensors on the fringe of panel RF reception. Refer to the transceiver documentation for mounting information.
Connect the transceiver (up to four) to the panel as shown in Figure 17 on page
24.
Concord 4 Installation Manual 23
Chapter 2: Installation
+12V
A
B
GND/COM
Panel terminals
Transceiver terminals
GND +12V A BUS B
Panel terminals
Module terminals
Not used
GND +12V A BUS B SPKR SPKR
+12V A BUS B GND SPK 1 SPK 2 AUD 1 AUD 2
Figure 17: Wiring transceivers
SuperBus 2000 voice-only module
The module can be mounted inside or outside of the control panel cabinet. Refer to the documentation included with each module, for complete mounting instructions. For RJ-31X connections, see “RJ31X phone jackon page 28.
The module requires panel power and bus connections, and speaker connection through panel terminals as shown in Figure 18 below.
Figure 18: Wiring for the voice-only module
SuperBus 2000 phone interface/voice module
The phone interface/voice module includes two backplates for mounting the module inside the control panel cabinet. You may also mount the module outside
24 Concord 4 Installation Manual
Loading...
+ 123 hidden pages