Interlogix ESL, 60-848-01-95, Caddx NX-491T Installation Instructions Manual

ESL Wireless Smoke Alarms
Caddx: NX491T
Wireless
Installation Instructions
ITI: 60-848-01-95
U
¤
L
C
4300 Series
NX Series
Wireless Smoke Detector
Wireless Smoke Alarm/Detector
US
LISTED
Description
The ESL smoke alarms are Learn Mode wireless sensors with 319.5 MHz transmitters that use photoelectric technology with a self contained sounder, a low battery annunciator, and a status LED. The smoke alarms are part of a security/fire alarm system and communicate with the system control panel.
The smoke alarms provide the following features: Self-diagnostics. The smoke alarms monitor their own
sensitivity and operational status. Base tamper switch sends a tamper signal transmission to
the control panel when the smoke alarms are removed from their mounting bases.
Integrated fixed 135°F temperature and rate of rise heat detector trips an alarm based on high temperature detected or rapidly rising temperature rate (15°F/minute minimum).
Transmitted Signal Outputs
The smoke alarms transmit the following signals to the control panel:
• Alarm
• T amper
• Test
• Low battery
• Trouble
• Supervisory
Sounder
LED
Figure 1. Alarm Features
T emperature sensor
T est/Silence button
Selecting a Location
Selecting a suitable location is critical to the operation of smoke alarms. This equipment should be installed in accordance with the National Fire Protection Association’s (NFP A) Standard 72. See Figure 2.
A-8-1.2.1.a Where to Locate the Required Smoke Alarms in Existing Construction.
The major threat from fire in a family living unit occurs at night when everyone is asleep. The principal threat to persons in sleeping areas comes from fires in the remain­der of the unit. Therefore, a smoke alarm(s) is best located between the bedroom areas and the rest of the unit. In units with only one bedroom area on one floor, the smoke alarm(s) should be located as shown in Figure 2 A.
In family living units with more than one bedroom area or with more than one floor, more than one smoke alarm is required, as shown in Figure 2 B.
In addition to smoke alarms outside of the sleeping areas, the installation of a smoke alarm on each additional story of the family living unit, including the basement, is required. These installations are shown in Figure 2 C. The living area smoke alarm should be installed in the living room or near the stairway to the upper level, or in both locations. The basement smoke alarm should be installed in close proximity to the stairway leading to the floor above. Where installed on an open-joisted ceiling, the alarm should be placed on the bottom of the joists. The alarm should be positioned relative to the stairway to intercept smoke coming from a fire in the basement before the smoke enters the stairway .
ESL Wireless Smoke Alarms
1
Kitchen
Dining Room
Figure 2 A. Alarm Placement
TV Room
Bedroom
Bedroom
Living Room
Dining
Kitchen Bedroom
Room
Living Room
Bedroom
Bedroom
Bedroom
A-8-1.2.1.c Are More Smoke Alarms Desirable?
The required number of smoke alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms. For this reason, it is recommended that the householder consider the use of additional smoke alarms for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms. The installation of smoke alarms in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.
Important !
Regulations pertaining to smoke alarm installa­tions vary from state to state. For more informa­tion, contact your local fire department or local authority having jurisdiction.
Figure 2 B. Alarm Placement
Bedroom
Living Room
Basement
Figure 2 C. Alarm Placement
= Required smoke alarms
= Additional smoke alarms required for new construction
Bedroom
Dining Room
In addition to NFP A 72, use the following location guidelines to optimize performance and reduce the chance of false alarms:
• Locate ceiling-mounted smoke alarms in the center of a room or hallway at least 4 inches (10.2cm) from any walls or partitions.
• Locate wall-mounted smoke alarms so the top of the alarm is 4 to 12 inches (10.2 to 30.5cm) below the ceiling.
• Locate in a suitable environment as follows:
- T emperature between 40°F (4.4°C) and 100°F (37.8°C)
- Humidity between 0 and 95% non-condensing
• Locate away from air conditioners, heating registers and any other ventilation source that may interfere with smoke entering the alarm.
• Mount smoke alarms on a firm permanent surface, typically a stud or metal runner.
• Locate away from large metallic objects.
A-8-1.2.1.b Where to Locate the Required Smoke Alarms in New Construction.
All of the smoke alarms specified in A-8-1.2.1.a for existing construction are required and, in addition, a smoke alarm is required in each bedroom.
2
ESL Wireless Smoke Alarms
Installing the Alarms
1 . Slide the battery compartment cover away from the
alarm to unsnap it and lift it off. See Figure 3.
2 . Observing proper polarity, insert the two lithium
batteries provided into the alarm battery compartment and replace the battery compartment cover.
3. Making sure that the unit is removed from its base, put the panel in program mode/Learn Mode.
4 . Remove the red plastic dust cover from the alarm. The
alarms are shipped with a dust cover for protection on construction sites with dusty environments.
5. With the base still removed, press the test/silence button until the panel indicates that the sensor has been enrolled.
6 . Before permanently mounting the alarm, disconnect the
alarm notification appliances and test the communica­tion between the control panel and each smoke alarm as follows:
- Press the test/silence button on the alarm for 2 seconds. The alarm sends a test signal to the control panel.
- At the control panel, verify the test signal was received and the RF signal strength is adequate. If no signal is received or the RF signal is weak, relocate the alarm and retest.
7. Using the two screws and anchors provided, mount the base.
8 . Attach the alarm to the mounting base as follows:
- Line up the raised tab on the lip of the alarm with the slot on the lip of the mounting base. See Figure 3.
- Insert the alarm into the base and turn clockwise approximately 15 degrees. It should snap firmly into place.
9. Test the communication between the control panel and each smoke alarm as follows:
- One at a time, press the test/silence button on the alarm for 2 seconds. The alarm sends a test signal to the control panel.
Note
Continuing to press and hold the test button for more than 20 seconds will send an alarm signal to a control station.
- At the control panel, verify the test signal was received.
10. Test each alarm (see Smoke Testing the Alarm) and reconnect all alarm notification appliances.
Tab
Slot
Battery compartment
Figure 3 - Alarm-to-Base Alignment
Smoke Testing the Alarms
Smoke alarms should be tested in place annually using smoke or Smoke! in a can®. Follow the instructions on the canned smoke or use the following steps to test the alarms with smoke:
1 . Hold a smoldering punk or cotton wick close to the
smoke entry openings.
2 . Gently direct the smoke into the unit for 20 seconds or
until an alarm is indicated.
Be sure to properly extinguish the smoke source after testing! The alarm LED should remain on while the built-in
transmitter sends an alarm signal to the control panel. The alarms will sound a temporal rhythm until the test/silence button is pressed. The alarms automatically reset when smoke is no longer present.
Important !
The control panel alarm and all auxiliary func­tions should be verified for a complete test of the system.
ESL Wireless Smoke Alarms
3
Loading...
+ 5 hidden pages