Interlogix 103-20, 103-21, 103-22, 103-22S, 103-23 Specsheet

...
www.GE-Interlogix.com
GE Interlogix
Product Information
Standard Features
Single action
Dual action
Terminal connections
Die cast aluminum alloy
Weatherproof models available
UL Listed
Manual Fire Alarm Stations
Single & Dual Action
103 Series
The 103 Series fire alarms are manually operated non-coded
devices for initiating fire alarm signals. The pull handle latches
until the station is reset by operating the station cover.
Operation of the pull handle closes a single-pole or double-pole
switch. Two wire barrier terminals are provided, each
accommodating two conductors, #14 AWG or smaller. Opening
the cover also closes the alarm initiating switch to allow testing.
Both 103-22 (Hex key reset) and 103-42 (cat 30 key reset) are dual
action stations that are provided with a cover which must be
lifted to expose the pull handle. A break-glass rod is included with
each station for optional use.
For outdoor or harsh environment applications, use the 103-60
(water/weatherproof single action station).
The 103 Series manual fire alarm stations are intended for use as
fire alarm initiating devices, with any fire alarm initiating circuit to
be operated by a contact closure rated not more than 10 amperes,
125 V AC.
The 103 Series manual fire alarm stations mount to standard
single-gang electrical boxes or to a plaster ring. The maximum
depth of the equipment is 1
1
/4”.
Model 103-25 surface mounting box is availble. The box is
5” high x 3
1
/4” wide x 2 3/4” deep.
All stations should be installed in compliance with the
application NFPA standards, local building codes, and plans
and specifications.
Overview
Application
Installation
Manual Fire Alarm Stations
Single & Dual Action 103 Series
©2003 GE Interlogix. E-2277 Rev C-KA-0603
Specifications
Contact Ratings 10A @ 125 V AC Mounting Flush Standard Outlet Box with one device
cover at least 13/4” deep.
Surface Model 103-25 Surface Box
5”H x 31/4” W x 23/4” D
Material Die cast aluminum alloy — enameled finish Color Red housing — white handle Operation General alarm — single or dual action Pre-Signal—Key Operated Removable in either position Shipping Weight
Station 20 oz. Surface Box 14 oz.
GE Interlogix
www.GE-Interlogix.com 2266 Second Street North
North St. Paul, MN 55109 Phone: 651-777-2690 USA & Canada: 800-777-5484
12345 SW Leveton Drive Tualatin, OR 97062 Phone: 503-692-4052 USA & Canada: 800-547-2556 Technical Service: 800-648-7424 Faxback: 800-483-2495
Single action manual fire alarm station, hex key reset, non-coded SPST Single action manual fire alarm station, hex key reset, non-coded DPST Dual action manual fire alarm station, hex key reset, non-coded SPST (s)* with NY stripe Dual action manual fire alarm station, hex key reset, non-coded DPST (s)* with NY stripe Single action (SPST) with key reset Dual action manual fire alarm station, cat 30 key reset, non-coded SPST Water/weatherproof, single action (SPST) with key reset
Red surface box for 103-20 through 103-42 Replacement glass rod for 103-20 through 103-60*
*Note: Glass rod replacements are only intended for use with ESL manual fire alarm stations.
103-20 103-21 103-22 (s)* 103-23 103-31 103-42 103-60
Accessories
103-25 103-26
Ordering Information