Read this installation manual thoroughly before the installation and use of the
boiler. Follow all indicated instructions. This installation manual must remain
with the boiler.
Smart Opentherm™
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided
with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s
instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark
Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future
reference. Please read the Benchmark Checklist carefully, page 90 , and complete all sections, as required by law, relevant to
the appliance and installation. Failure to install and commission according to the manufacturer’s instructions and complete the
Benchmark Commissioning Checklist will invalidate the warranty for the Gas Boiler installation. The details within the Checklist will
be required in the event of any warranty work. On completion the Checklist must be le with the end user. The relevant sections of
the Service Record, pages 91 & 92, must be completed on each subsequent Service visit.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of
Practice which is available from the Heating and Hotwater Industry Council who manage and promote the scheme. Visit www.
centralheating.co.uk for more information.
15 Benchmark Commissioning & Warranty Validation Service record 87
To be completed at each annual service, not subsequent.
4
1 PREFACE
The manufacturer Intergas Heating Ltd accepts no liability whatsoever for damage or
injury caused by failure to adhere (strictly) to the safety regulations and instructions,
or carelessness during installation of the Intergas wall mounted gas fired boiler and
any associated accessories
Intergas Heating Ltd are continuously developing ways to guarantee the quality of its
products and to improve them where necessary. In so doing we (Intergas Heating Ltd.)
reserve the right to modify at any time the features named within this document.
Read and observe all safety instructions within this instruction manual to prevent
unsafe situations, fire, explosion, damage to property or personal injury.
1.1 Regulation
The Intergas combination boiler meets the requirements of Statutory Instrument ‘The
Boiler (Eiciency) Regulations’ and is deemed to meet the requirements of:
► Low Voltage Directive (2014/35/EU)► Gas Appliances Regulation (EU) 2016/426► Boiler Eiciency Directive (92/42/EEC)► EMC Directive (2014/30/EU)► RED Directive (2014/53/EU)► Ecodesign (2009/125/EC)► Energy labelling Regulation (EU) 2017/1369
Intergas declares that the materials used in the manufacturing of this appliance are
non hazardous and that no substances harmful to health are contained within the
appliance.
1.2 Warnings
Intergas accepts no responsibility for the unsatisfactory performance of the appliance
or flue arising from the failure to comply with this installation manual. Incorrect
installation could invalidate your guarantee and may lead to prosecution.
The appliance cannot be removed from the original place of installation and transferred
to another site or re-sold without prior consent from Intergas. You must re-register the
appliance with Intergas in order to maintain any remaining warranty.
The boiler must be installed by a competent Gas Safe registered
engineer and in accordance with these instructions, It is the installers responsibility to
ensure that the installation conforms to the current legislation and Standard Codes of
Practice.
Please read these instructions carefully before installing or using the
appliance.
1.3 Manual handling
When moving the boiler always keep your back straight, bend your knees, don’t twist,
move your feet. Avoid bending forwards or sideways and keep the load as close to
your body as possible. Where possible transport the boiler using a suitable trolley, sack
truck or get some assistance. Grip the boiler firmly and before liing establish where
the weight is concentrated to determine the centre of gravity, repositioning yourself if
necessary.
5
1.4 Pictograms
The following pictograms are used within this installation manual:
CAREFUL / IMPORTANT
Procedures which, if these are not performed
with the required caution, can damage the
product, the surrounding or the environment or
may result in personal injury.
COMMENT
Procedures and/or instructions which, if they
are not followed, can negatively aect the
operation of the boiler.
SEE
Reference to other manuals
1.5 Warnings on the box
INSTRUCTION (THIS SIDE UP)
Store the appliance upright as indicated on the
box.
INSTRUCTION (FRAGILE)
This is a fragile piece of equipment: Please
handle with care do not to drop.
INSTRUCTION (FRAGILE)
This is a fragile piece of equipment: Please
provide dry storage for the appliance.
INSTRUCTION (STACK)
MAX 3 MAX2
No more than three boxes should be stacked on
top of each other.
1.6 Abbreviations
► DHW: Domestic hot water► CH: Central heating► CW:Comfort domestic hot water► HE: High eiciency
► PHS: Pre Heated Solar water.► LT: Low temperature (zone).► HT: High temperature (zone)
► OT:OpenTherm► RF: Radio frequency► PC: Personal computer► NTC: Sensor (Negative temperature coeicient)► PP: Polypropylene► CAC: Combination air supply duct and combustible
gas flue system (concentric chimney system)
6
2 SAFETY REGULATIONS
Safety precautions If you smell gas
A gas leak could potentially cause an
explosion. If you smell gas, observe the
following rules:
► Prevent flames or sparks:
- Do not smoke, use a lighter or strike
matches.
- Do not operate any electrical switches or
unplug any equipment.
- Do not use the telephone or ring
doorbells.
► Turn o the gas at the meter or regulator.► Open windows and doors.► Warn your neighbors and leave the building► Prevent anyone from entering the building.► Call the National Gas Emergency Service on
0800 111 999 (From a location away from
the gas leak).
L.P.G. boilers: Call the supplier’s number on
the side of the gas tank or cylinder.
2.1 General
Depending on the year of construction, an Intergas HR boiler may contain part(s)
in which ceramic fibers are used. Always use the recommended personal
protective equipment when working with ceramic fibers.
It is law that all gas appliances are installed and serviced by a Gas Safe registered
competent engineer, if in any doubt please check with Gas Safe (0800 408 5500)
and in accordance with the following recommendations:
► Current Gas Safety (Installation and Use) Regulations► All current building regulations► Building Standards (Scotland) Consolidated► I.S.813 Installation of Gas Appliances (Ireland) ► IET Wiring Regulations (BS 7671)► Health and Safety Document (Electricity at Work Regulations)► UK Water fittings Regulations and Byelaws ► Health & Safety Regulations
2.2 The installation
The installation must comply with the following British Standards codes of practice:
► BS 5440: Flueing and Ventilation for gas appliances of rated input not exceeding 70kW (Part 1 Flues)► BS 5440: Flueing and Ventilation for gas appliances of rated input not exceeding 70kW (Part 2 Air Supply)► BS 5546: 2010 Specification for installation and maintenance of gas-fired water-heating appliances of a
rated input not exceeding 70Kw net.
► BS EN 12828:2012+A1:2014 Heating systems in buildings. Design for water-based heating systems► BS EN 806-1:2000 Specifications for installations inside buildings conveying water for human consumption.
General (802-2 Design, 806-3 Pipe sizing, 806-4 Installation, 806-5 Operation and maintenance).
► BS 6798: 2014 Specification for selection, installation, inspection, commissioning, servicing and
maintenance of gas-fired boilers of rated input not exceeding 70kW net
► BS 6891: 2015+A1:2019 Specification for the Installation and maintenance of low pressure gas installation
pipework of up to 35mm (R1 1/4) on premises
► BS 7593: 2019 Code of practice for the preparation, commissioning and maintenance of domestic central
heating and cooling water in systems
► BS 7671: 2018 Requirements for electrical installations, IET Wiring regulations► BS 5955-8:2001 Plastic pipework (thermoplastics materials). Specification for the installation of
thermoplastic pipes and associated fittings for use in domestic hot and cold services and heating systems
in buildings.
Reference should also be made to:
► Guide to condensing boiler installation assessment procedures for dwellings (SBSA)► The institute of Gas Engineers document & managers IGE/UP/7 Gas installations in timber frame and light
steel framed buildings.
7
3 GENERAL BOILER INFORMATION
3.1 General
The Intergas Xclusive wall-mounted gas boiler is a room sealed unit. The
boiler is intended solely to provide heat for the water in a central heating
system and domestic hot water installation and is for domestic use only.
The Intergas Xclusive meets the European directives and additional national
regulations that are indicated by CE marking. The associated conformity
declaration can be requested from Intergas Heating Ltd (also see §14)
The Intergas Xclusive meets the electrical protection class IPX4D.
3.1.1 ErP label
Based on the European ErP Directive (Energy related Products) all newly
produced gas fired boilers have to meet minimum standards regarding
energy performance.
The Intergas Xclusive carries an European energy label containing specific
information regarding energy eiciency class (CH and DHW), noise level
and maximum power.
Intergas Heang LtdXclusive --
XL
The Intergas Xclusive carries label A for both CH and DHW.
In addition the Intergas Xclusive meets the following DHW capacity profile:
The extensive product fiche can be found in §12.2.
3.1.2 Gas category
Gas categoryGas typeGas inlet pressure
II
2H3P
The Intergas Xclusive is factory-set for H-gas, G20. The boiler
may optionally be converted to another gas type (as in §3.1.2)
using a conversion set (see §9.8).
(mbar)
Natural gas (G20)20
LPG (G31)37
--
kW
+
A
A
B
C
D
E
F
A
+++
A
++
A
+
A
A
B
C
D
--
2019811/2013
A
dB
8
3.2 Operation
The Intergas Xclusive is a modulating high eiciency boiler. This means
that the output is adjusted according to the desired heating capacity.
Two separate copper circuits are infused within the aluminium
Bithermic heat exchanger.
The boiler has a printed circuit board with microprocessor control, this
allows constant calculations to take place during any demand for either
heating or hot water, these calculations are based on many factors and
measuring points within the boiler.
The microprocessor manages and takes control of the modulating
output, ensuring optimum eiciency is maintained at all times during
production.
3.3 Data plate
Identification of the product
You will find the unit details on the data plate on the bottom
of the boiler. The data plate contains, important information
and the boiler specification (boiler type and model name), and
the serial number:
******
-yymm
PIN
PMS
PWS
Qn HS
Qn Hi
Pn
BE, CH, DE, ES,
FR, GB, IE, IT, MT
I2E(s), I2H,
IIELL3P, II2H3P,
II2Esi3P
G20-20 mbar
G31-37 mbar
B23, ......C93(x)
Tmax
IPX4D
******
Production code - Serial number
YY = year of production,
mm = month of production
Product Information Number
Data related to Domestic Hot Water
Data related to Central Heating
Information regarding electrical power supply
(Voltage, mains frequency, elmax, IP-class)
Permissible overpressure in CH circuit in bar
Permissible overpressure in DHW circuit in bar
Input related to gross caloric value in kilowatts
Input related to net caloric value in kilowatts
Output in kilowatts
Countries of Destination (EN 437)
Approved unit categories (EN 437)
Gas group and gas connection pressure as set
at the factory (EN 437)
Approved flue gas category (EN 15502)
Maximum flow temperature in °C
Electrical protection class
9
3.4 Control panel
The boiler has a fully integrated touch screen control panel
that also displays information about the operational status,
temperature settings, demand symbols and fault codes.
The display has multiple functions and options please refer to
section §9 for further detail.
COMMENT
► The touch screen is very sensitive only
use a finger tip and not any sharp objects.
3.5 Operational modes
The boiler has a number of operational modes:
The boiler is switched o.
The boiler is switched o but is connected to the mains power.
In this mode, the display view is characterised by:
► Displaying the power LED [► Displays the pressure within the central heating system on
le hand side [ ].
► Displaying a line on the right display [ ].
Boiler is switched o
(mains voltage is present)
].
The boiler is switched on and is ready for a heat demand.
The boiler is switched on and is ready to answer a request for
either domestic hot water or hot central heating water.
In this mode, the display view is characterised by:
► Displaying the power LED [
]. All other symbols and values
are not displayed.
The boiler is operating and producing domestic hot
water.
The boiler is operating and supplying domestic hot water to a
tap or shower etc. The display view is characterised by:
► Displaying the power LED [ ].► Displaying the flame i.e. burner is switched on [ ].► Displaying the tap symbol [ ].
The boiler is operating and producing central heating
water.
The boiler is operating and supplying central heating water.
The display view is characterised by:
► Displaying the power LED [ ].► Displaying the flame i.e. burner is switched on [ ].► Displaying the radiator symbol [ ].
Boiler is switched on
(ready for heat demand)
Boiler is in operation (domestic hot water)
Boiler is in operation (central heating water)
10
4 MAIN COMPONENTS
Flue appliance adapter
Air supply duct
(for 80mm twin flue only)
NTC Heat exchanger
sensor (S0)
Air supply duct
(for 80mm twin flue only)
Ignition module
Ignition electrode
vNTC Flue gas sensor (S5)
Fan assembly
Heat exchanger
Expansion vessel
shown as silhouette
3bar Pressure relief valve
NTC Central heating
flow sensor (S1)
NTC Domestic hot
water sensor (S3)
Central heating
low pressure sensor
24V DC Gas valve
Heating Modulating Pump
Flow turbine sensor
Condense syphon
Printed circuit board and
housing
Mains lead 230 V
AC (bare)
Touch screen fascia panel
11
4.1 Standard scope of delivery
>>Betrouwbaar in warmte>>Betrouwbaar in warmte>>Betrouwbaar in warmte
Check whether the package is undamaged. Unpack the boiler
and check whether all components are present. Also check
for any damages to the boiler or accessories and, if present,
immediately notify the supplier.
Volgens geldende voorschriften
geïnstalleerd door:
voor klant
Naam installateur:
Adres:
Postcode:
Woonplaats:
Naam koper:
Adres:
Postcode:
Woonplaats:
12345678910
Type/Serienr.Type/Serienr.
Voor de ‘Garantiebepalingen
Intergas HR-ketels’ verwijzen
Datum installatie:
wij u naar onze website:
Naam koper:
www.intergasverwarming.nl
voor installateur
of naar het bij uw HR-ketel
Adres:
bijgevoegde installatievoorschrift.
Postcode:
Op uw verzoek sturen wij u
graag een exemplaar toe.
Woonplaats:
Het garantiebewijs is slechts geldig, indien de aan het garantiebewijs gehechte
antwoordkaart binnen 8 dagen na de installatie wordt ingezonden. Deze kaart
moet volledig en duidelijk worden
van koper en installateur. Door ondertekening van deze kaart verklaart koper
zich akkoord met de staat van de ketel bij aflevering.
12345678910
ingevuld en voorzien zijn van de handtekening
Garantiebewijs Intergas HR-ketel
Datum installatie:
Naam koper:
Adres:
voor fabrikant
Postcode:
Woonplaats:
Installateur
Het garantiebewijs is slechts geldig, indien de aan het garantiebewijs gehechte
antwoordkaart binnen 8 dagen na de installatie wordt ingezonden. Deze kaart
moet volledig en duidelijk worden ingevuld en voorzien zijn van de handtekening
van koper en installateur. Door ondertekening van deze kaart verklaart koper
1234567891 0
zich akkoord met de staat van de ketel bij aflevering.
Postzegel
niet nodig
Intergas Verwarming BV
Antwoordnummer 5
7740 VB COEVORDEN
Guarantee cardConnection set
12
4.2 Accessories
Original Intergas accessories can be ordered separately at your local stockist.
Instructions about the correct way to assemble and use these accessories are provided
with the product ordered and are therefore not included within this installation manual.
Item no 090347
Post-Heating Solar Boiler
conversion set
Item no 081286
Extension L=1000mm inc.
wall bracket (for plume
management kit)
Item no 087910
60/100 flue weather slate
(pitched roof)
Item no 842177
Thermostatic mixing valve
Item no 084661
Bend 45°
Item no 087372
60/100 flue weather slate
(flat roof)
Item no 203207
Outdoor sensor (For
use with weather
compensation)
Item no 084660
Bend 90°
Item no 082975
60/100 extension
L=1000mm
inc. wall bracket
Item no 081285
Elbow 60° (2 per box) (for
plume management kit)
Item no 081295
Plume terminal bend
Item no 081298
Horizontal telescopic oset
wall terminal
1
Item no 082980
Horizontal non telescopic
straight wall terminal
1
Item no 081297
Horizontal telescopic wall
terminal
1
Vertical roof terminal
(inc. boiler adapter
Item no 081284
Elbow 90° (for plume
management kit)
1
Only to be used in combination with the base adapter on the boiler
Item no 0821973
60/100)
Item no 081294
Plume management kit
(inc. 2x wall brackets)
13
5 INSTALLER IMPORTANT POINTS
Please read all instructions before fitting this appliance
► The installer must instruct the user on the operation of the boiler, fault code diagnosis and how to reset
the boiler, location of the filling loop and how to re-pressurise the system if the water pressure drops to
below 0.5 bar.
► The installer must hand over these installation and user instructions ensuring the Benchmark
Commissioning Checklist has been completed correctly.
► The attending engineer must complete the service record on the Benchmark Checklist aer each
service and/or replacing any parts within the boiler.
► It is required under Gas Safe Regulations for the installation to be notified and to register the
installation with Gas Safe, and Building Control (Gas Safe Notification).
► You must register the boiler with Intergas heating ltd within 30 days of the installation to validate any
warranty supplied with the boiler, via post, website or MiReg if you are the installer.
► When commissioning the boiler, check the gas inlet working pressure is 20mbar (NG) or 37mbar for
(LPG) on P1 of the boiler gas valve. (Min 17mB (NG) 30mB (LPG) with all connected appliances operating
at full rate).
► Combustion analysis with a correctly calibrated and certificated electronic analyser is essential for safe
commissioning of the boiler, this must be documented within the Benchmark commissioning checklist.
► A pressure reducing valve set to 3.5 bar must be fitted if the mains water supply pressure is above 5 bar,
this should be located no closer than 3 metres proximity to the boiler for expansion purposes.
► In areas where the water hardness is 200ppm or above, appropriate protection must be taken in
accordance with BS 7593 & in line with building regulations Part L. (See Warranty Provisions on page 88,
point 15).
Intergas recommend Hydroflow HS38a wired into the boiler or HS38b which can be powered
separately.
► The end user / home owner should be advised to keep this installation manual in a safe place,
preferably near the appliance for servicing and future reference, it is a legal requirement that any
attending engineer can check the validity of the Benchmark commissioning checklist (Benchmark
certificate).
► It is important to protect the boiler during the installation. In particular, do not allow any dust or debris
to enter the flue connection at the top of the appliance.
► Before operating the boiler please ensure that the copper pipework you are installing is connected
to the appropriate tappings on the boiler. (Plastic pipework where appropriate must be a minimum
distance of 1000mm away from the boiler connections as per BS 5955-2008).
► It is important to chemically treat and thoroughly flush the heating circuits, prior to commissioning
the boiler, in order to remove any residue fluxes and debris from within them, (please isolate the
appliance). The system flush must be carried out to BS 7593:2019 and an appropriate inhibitor added
to the correct dosage, dependant on the system capacity, as indicated on the product used.
► Intergas recommend water treatment in accordance with the Benchmark Guidance on Water Treatment
in Central Heating Systems, we recommend the use of FERNOX, SENTINEL or ADEY inhibitors. It is most
important that correct concentration of water treatment is maintained for the life of the boiler, a water
sample is required upon installation and to be verified by the aforementioned manufacturers should
we attend a warranty call a water sample may be required to keep the warranty valid. (BS 7593:2019)
► As per BS 7593:2019 Intergas recommend the fitting of an approved magnetic type filter to the
heating return pipe under the boiler (Intergas Nickel plated brass system filter recommended).
► This boiler has been factory set but adjustment may be required to the heating output in order to
match the individual heating demand. This can be done by changing parameter P010 (= max. power
CH) or parameter P070 (= max. power domestic water). See §9.1.5 "To modify a parameter".
► Please do not use the pressure relief valve as a means of flushing, draining the boiler or system.► Aer domestic hot water production a preset time delay will occur this is designed to prevent the boiler
from cycling thus enhancing the overall eiciency further.
Note: an anti-cycle delay time can be set up to a maximum of 15 minutes by adjusting parameter P036
as described in §8.3.
► When required an external expansion vessels should be inverted with the water side facing downwards
and connected to the heating return (not the flow side) this will allow correct draining of system and
help prolong the life of the vessel diaphragm. (precharge air pressure should be set as per the internal
vessel of the boiler i.e. 0.75bar +/- 0.2bar).
► If you experience any problems please refer to the installation and commissioning guidelines within the
6.1 Overall dimensions of boiler including the wall bracket
450
120
100
246
160
120
Z
=320=
Connections
277
98h
Central heating
A
flow
Central heating
B
return
C
Gas flow
Domestic cold
D
water - Inlet
Domestic hot
E
water - Outlet
Condense
F
syphon outlet
Flue / Chimney
appliance
connection
22mm with isolation
valve fitted
22mm with isolation
valve fitted
22mm with isolation
valve fitted
15mm with isolation
valve fitted
15mm with isolation
valve fitted
Ødn25
Ø60/100
(concentric, wall
terminal )
148
h =
H =
Overall dimensions
618 mm
618 mm
Xclusive 24
Xclusive 30
678 mmXclusive 36
766 mmXclusive 24
95
65
50
F
AB
DE
6.1.1 Mounting the wall bracket
Due to the size and weight of the appliance it is not
recommended to install the boiler on a stud wall as this may
also cause noise issues.
H
766 mmXclusive 30
826 mmXclusive 36
6565120656570
A
ECD
C
F
B
275
Refer to the installation dimensions and clearances on the
boiler template supplied with this appliance.
15
6.2 Installation location
The boiler must be installed on a solid brick wall that has
suicient strength to be able to withstand the weight of the
boiler when filled with water (see Technical data).
The appliance must be connected to a 3 amp fused spur within
one (1) meter of the boiler. The condense discharge from the
boiler must be connected to an internal drain or waste system
where possible to prevent freezing during any adverse weather
conditions.
Any unheated area's i.e. a lo space or garage must be treated
as external and therefore adequate frost protection measures
must be taken for the boiler and any pipework etc. (see §6.3)
Make sure the boiler is easily accessible by ensuring that the
adjacent clearances are adhered to.
Further dimensions
*D =
600 mmXclusive 24,30,36
* 5mm clearance from a closing door
600mm for servicing clearnances
min. 10
min. 50
450
min. 200
H
H =
766 mmXclusive 24
766 mmXclusive 30
826 mmXclusive 36
6.2.1 Installation within a kitchen area or wall cabinet
The boiler can be installed between two kitchen wall units or
inside a cabinet that is of suicient size.
There must be suicient ventilation above and below the
boiler for cooling purposes (as per the adjacent diagram). Any
decor panels or grills used to aid ventilation must be removable
for servicing and maintenance purposes.
CAREFUL
► The appliance must not be installed
above any heat source as this will
invalidate any warranty supplied with
the boiler.
min. 250
Minimum dimension 50cm
277
*D
2
Minimum dimension 50cm
16
2
6.2.2 Removing/installing the front panel
► The front cover of the boiler must be removed to perform
various maintenance activities however you must be a
competent Gas Safe registered engineer before carrying out
the following procedure!
► Loosen both screws (1) under the boiler by using a 5 mm
allen key. (They are captive and therefore will not drop out
of the lower housing).
► Slide the front cover (2) upward and then remove it by
pulling it towards you.
COMMENT
► The front cover has a rubber seal around
the inner edge sometimes making it
very sti to slide o so please ensure the
boiler is secured to the wall correctly
before attempting this procedure!
1
Replacing the room sealed front cover.
To replace the front panel, proceed as follows:
► Position the front panel (3) against the boiler and slide
it downwards until it is correctly connected to the
lower fascia panel.
► Hand tighten screws under the boiler using a 5 mm
allen key (do not over tighten).
CAREFUL
► This is a room sealed cover and therefore
extremely important that it is fitted
correctly, failure to do so could lead to
products of combustion entering the
room / environment where it is situated.
2
3
17
6.3 Installing the boiler
1. Attach the wall bracket.
2. Li the boiler (2 person li) and slide it down onto the wall bracket.
3. Remove the syphon cup.
4. You must fill the syphon cup just over half full with water.
5. Replace the cup and install the supplied black flexible hose onto boiler
outlet union.
6. Connect the flexible hose to a 22 mm O.D solvent weld pipe. To minimize
the risk of freezing the condensate pipe should be connected internally
and terminate to an internal soil stack, (ref.: TB115 Gas Safe & HHIC).
7. Install the flue system (see §7.6).
8. Install the required pipework as per the following sections.
9. Should the condensate be terminated to an external soil pipe, drain,
rainwater system or soakaway we only recommend the Condensate PRO
system which is available from our normal stockists or heating supplies.
https://condensatepro.co.uk
COMMENT
► The Intergas Xclusivehas a boiler-
specific siphon cup. Ensure that
the correct version is ordered upon
replacement. (Item no 510054)
1. Mount the wall bracket (ensure its level)
4. Fill the condense syphon cup5. Replace the condense syphon cup
18
2. Hang the boiler onto the wall bracket3. Twist and pull to remove the condense
and attach the supplied flexible hose
syphon cup
Open connection
to waste system
6. Connect the flexible hose to the waste
system via a tundish or similar.
7 CONNECTION
7.1 Connecting to the central heating system circuit
► Flush the central heating system thoroughly as per
BS7593:2019.
► Fit the flow and return pipes to the isolation valves using the
supplied 3/4" fibre washers, noting that the filling link valve
attaches to the return side as per the adjacent drawing.
► The pipework must be correctly supported with full wrap
over type clips / brackets.
► Do not over tighten the connections onto the boiler as
this can cause stress damage and possible internal boiler
leakage.
The CH system should include the following:
► As per BS 7593:2019 a magnetic type filter such as the
Intergas system filter, should be fitted onto the return
pipework as shown in the adjacent diagram.
► When installing the Intergas system filter, the supplied spigot valve should be fitted to the bottom union to enable
combined isolation with the boiler return valve.
► The drain / dosing valve at the bottom of the filter housing facilitates the easy draining of the appliance, with the spigot
valve and heating flow valve both closed at the same time.
► A drain tap at the lowest point(s) of the installation.
► A full bore spring loaded single check valve, in the return pipework nextto the boiler whenever the pipework
rises above the appliance. This prevents the occurrence of thermosyphoning (radiators getting warm) during DHW
production.
Preformed flow pipe
Preformed return pipe
7.1.1 Expansion vessel
The appliance is fitted with a expansion vessel adequate for a typical
heating system with 8 radiators installed. For larger volume systems,
an additional expansion vessel must be fitted. Refer to the below
table or contact Intergas for further advice in these cases.
SAFETY VALVE
SETTING (bar)
VESSEL CHARGE
PRESSURE (bar)
INITIAL SYSTEM
PRESSURE (bar)
TOTAL WATER
CONTENT of SYSTEM
LITRES
25
50
75
100
125
150
175
200
For syst. volumes other than those
given above, mult. the syst. volume
by the factor across
Intergas system filter.
3.0
0.751.01.5
1.01.52.01.52.02.0
EXPANSION VESSEL VOLUME (litres)
3.56.513.74.710.38.3
7.012.927.59.520.616.5
10.519.441.314.230.924.8
14.025.955.119.041.233.1
17.532.468.923.751.541.3
21.038.882.628.561.849.6
24.545.396.433.272.157.9
28.051.8110.238.082.466.2
0.1400.2590.5510.1900.4120.33
Spigot isolation
valve
Drain/Dosing
valve.
19
7.1.2 Thermostatic radiator valves
If the radiators have thermostatic radiator valves or valves that
can be closed to isolate the flow completely from the return, a
minimum amount of water circulation (6ltrs/min *) must be
maintained by installing a manual fixed bypass as this will not
interfere with the pump modulation, (* also see §9.5).
7.1.3 Underfloor heating
Underfloor heating with pump
For eective operation of the DHW supply any undesired
circulation through the appliance as a result of a second pump
in the CH circuit must be avoided.
Connect the underfloor heating system in a hydraulically
neutral manner to the appliance, or install the CH circuit with
an normally open zone valve ( I ) to prevent flow through the
appliance heat exchanger when there is no CH demmand.
see §9.5. for minimum permissible water circu lation through
the boiler heat exchanger.
Underfloor heating connection diagram
A. Boiler
B. Under floor circulation pump
C. Thermostatic mixing valve
D. Spring-operated non-return valve
E. Normally closed 230V~ zone valve (Radiators)
. Normally closed 230V~ zone valve (Under floor)
E
1
F. Radiators (Fitted with TRV's except room stat location)
G. Programmable room thermostat
H. Limit thermostat
I. Normally open 230V~ zone valve (powered via X4 terminal 3)
G
A
F
I
C
H
D
E
E1
B
20
Underfloor option wiring diagram
230Vac 3amp
Switched
Fused Spur
L N
Wiring centre
Time control to
Heating circuit
L
N
HTG on
Orange & Grey
wires from underfloor
Zone are not required.
Isolate and make safe.
(If applicable cables not always
supplied with this valve model)
12
NEUTRAL
EARTH
GREY (P/LIVE)
Room thermostat
2
1
3
345678910
EARTH
M/V SWITCHED LIVE
Zone Valve
FLOW TO
UNDER FLOOR
V4043B
(normally open)
OpenTherm
Heating Control
Zone Valve
Heating
(normally closed)
M/V SWITCHED LIVE
SWITCHED LIVE
Parameter P081
must adjusted to
value '1'
Switched Live from
NEUTRAL
underfloor heating
SWITCHED LIVE
controls to X3 Pin 2
S/L FROM BOILER
123
V4043H
X15
(24V=)
X13
X14
(24V =)
X12
(24V =)
X11
(24V =)
N/A
X10
(24V =)
N/A
24V=
(230V ~)
230V
X8
X5
(230V ~)
X4
(230V ~)
F1 (3,15 AT)
X3
(230V ~)
FUSE
X2
(230V ~)
X1
(230V ~)
21
7.1.4 X-Plan zone Hydraulic diagram
Key to Hydraulic & Wiring diagrams
A. Honeywell V4043H DHW Zone valve (Normally closed)
B. Honeywell V4043B Heating Zone valve (Normally open)
C. OpenTherm room thermostat (or programmable OT type if
not using the boiler intergral timer option for the heating
D. Cylinder overheat thermostat (manual reset)
E. Cylinder NTC sensor (art. no. 065117)
F. Pressure relief valve (3 Bar)
G. T/P safety (8 Bar)
H. Expansion vessel (potable)
C
Built in 6 ltr
expansion vessel
Stainless steel unvented cylinder (≥30 kW coil)
(storage capacity to be established by the installer)
► The unvented cylinder must comply with G3 regulations regarding
the safety controls which are normally supplied as a kit with the
vessel.
► The over heat protection (with manual reset) is wired through our
OpenTherm circuit to prevent the boiler from creating a hot water
demand should this safety control operate.
► For rapid recovery a 30 kW rated coil or greater is recommended
(this should be specified when ordering your vessel).
Parameter P001 change to option 1
Parameter P081 change to option 3
Parameter P070 adjust output to cylinder coil rating (% of kW)
230v to Overheat thermostat
L N
230Vac 3amp
Switched
Cylinder O/H Stat
Manual reset
Fused Spur
D
EARTH
Zone Valve
D H W
V4043H
(normally closed)
A
Hot Water Timer (option)
(Volt free switching)
L
N
o
on
C
12
E
NTC
Cylinder
Sensor
S/L to HTG M/V
GREY (LIVE)
Wiring Centre
345678910
EARTH
S/L to M/
B
Zone Valve
C/HEATING
V4043B
(normally open)
C
BLUE (neutral)
DHW S/L to M/V
Orange & grey wires from
heating zone are not
required, please isolate &
make them safe.
(if applicable cables not always
supplied with this valve model)
Note:
BLUE (neutral)
BLUE (neutral)
DHW S/L
The zone valve B closes when a
demand for DHW is created giving
priority to recover the cylinder.
X15
(24V=)
12
OpenTherm
Heating Control
1
2
45
3
X13
X14
(24V =)
12123
X12
(24V =)
X11
(24V =)
N/A
X10
(24V =)
N/A
24V=
(230V ~)
230V
X8
X5
(230V ~)
X4
(230V ~)
F1 (3,15 AT)
X3
(230V ~)
FUSE
X2
(230V ~)
X1
(230V ~)
23
7.1.6 S-Plan zone hydraulic diagram
Key to Hydraulic & Wiring diagrams
A. Honeywell V4043H DHW Zone valve (Normally closed)
B. Honeywell V4043H Heating Zone valve (Normally closed)
C. Twin channel Programmer
D. Cylinder overheat thermostat (manual reset)
E. Pressure relief valve (3 Bar)
F. T/P safety (8 Bar)
G. Expansion vessel (potable)
H. System By-pass (Should be 3 meters from boiler connections)
See §9.5 for minimum permissible water circulation through the
boiler heat exchanger.
► To alter the boiler from a combi to a system boiler please see
section §9.1.5 & §9.3
Parameter P001 change to "option 3"
Parameter P010 change to required system output %
(example 30kW set P010 to 50(%) = 15kW output)
C
Built in 6 ltr
expansion vessel
Stainless steel unvented cylinder
(storage capacity to be established by the installer
F
G
D
m
A
ErP modulating
pump
E
Additional expansion
vessel option see §7.1.1
H
CH circuit
24
m
B
7.1.7 S-Plan wiring diagram
230Vac 3amp
Switched
Fused Spur
L N
LIVE SUPPLY
Wiring Centre
Twin channel
Programmer
L
N
HTG on
DHW on
12
NEUTRAL
EARTH
M/V/S/L
3
Cylinder
thermostat
1
C
Room
thermostat
2
1
P/LIVE
345678910
M/V/S/L
HTG S/L
DHW S/L
P/LINE
Zone Valve
EARTH
NEUTRAL
C/HEATING
V4043H
(normally closed)
Zone Valve
D H W
V4043H
(normally closed)
S/L TO BOILER (DHW)
S/L TO BOILER (HTG)
S/LIVE (BOILER)
231
X15
(24V=)
X14
X13
(24V =)
X12
(24V =)
X11
(24V =)
N/A
X10
(24V =)
N/A
24V=
(230V ~)
230V
X8
X5
(230V ~)
X4
(230V ~)
F1 (3,15 AT)
X3
(230V ~)
FUSE
Note:With all wiring diagrams when using a digital type room thermostat the Neutral wire from the
wiring centre (2) to room thermostat (2) will not be required.
Note:With all wiring diagrams when using a digital type room thermostat the Neutral wire from the
wiring centre (2) to room thermostat (2) will not be required.
X2
(230V ~)
X1
(230V ~)
26
7.1.9 Y-Plan zone hydraulic diagram
Key to Hydraulic & Wiring diagrams
A. Room thermostat
B. Twin channel programmer
C. Cylinder thermostat
D. Boiler pressure reflief valve (3 Bar)
E. Hot water draw o (Gravity)
F. Mid position zone valve
G. Cold feed and expansion tank
H. System By-pass (Should be 3 meters from boiler connections)
► To alter the boiler from a combi to a system boiler please see section §9.1.5 & §9.3
Parameter P001 change to "option 3"
Parameter P010 change to required system output % See §9.5 for minimum permissible water circulation through the boiler
heat exchanger.
G
A
D
Built in 6 ltr
expansion
vessel
ErP
modulating
pump
H
B
E
C
Open vented cylinder
(storage capacity to be established by
the installer
AB
A
B
m
F
CH circuit
27
7.1.10 Y-Plan wiring diagram
230Vac 3amp
Switched
Fused Spur
L N
NEUTRAL
thermostat
Room
2
1
EARTH
3
M/V S/L
Cylinder
thermostat
1
C
2
S/L to BOILER
LIVE
Mid position
Zone Valve
V4073A
Twin channel
Programmer
L
N
HTG on
DHW on
DHW o
X15
(24V=)
Wiring Centre
X13
X14
(24V =)
LIVE
SUPPLY
X12
(24V =)
12
X11
(24V =)
N/A
345678910
NEUTRAL
X10
(24V =)
N/A
HTG S/L
24V=
DHW S/L
X8
(230V ~)
230V
LIVE
X5
(230V ~)
X4
(230V ~)
F1 (3,15 AT)
S/L LIVE to BOILER
231
X3
(230V ~)
FUSE
X2
(230V ~)
X1
(230V ~)
Note:With all wiring diagrams when using a digital type room thermostat the Neutral wire from the
wiring centre (2) to room thermostat (2) will not be required.
28
7.2 Connection of domestic hot water
B, C
► Flush the pipework thoroughly to clean any debris or
residue remaining from the installation (please refer to
current Standard Codes of Practice).
► Using the supplied isolation valve, fibre washer and std
15mm copper tail connect the mains inlet cold water.
► Using the supplied swivel union, fibre washer and Long
15mm copper tail connect the domestic hot water outlet.
► Do not over tighten the connections onto the boiler as
this can cause stress damage and possible internal boiler
leakage.
Comments
► The pipework should be kept to the minimum lengths
possible and where possible long radius or formed bends to
facilitate reduced frictional losses or high resistance circuits.
► The appliance has built-in frost protection, however this
will not protect the entire system, as that will require an
external frost protection kit. (The power & Gas supply
must be switched on for the frost protection to operate at
approximately 5°C to 15°C).
► The Xtreme 24 is equipped with a flow restrictor with a
nominal value of 8 l/min. The Xtreme 30 and Xtreme 36 do
not have this feature.
► The Xtreme 36 & 30 have increased flow rates due to their
increased outputs, so a flow limiter is not normally required.
► Where the mains water is 5 bar or greater then a 3 bar
pressure reducing valve must be fitted no closer in proximity
to the boiler than 3 metres (for expansion purposes).
► In hard water areas of 200ppm or above a scale reducer must be installed on the mains cold water inlet, Intergas
recommend the Hydroflow HS38 powered via X4 connections 1 & 2.
(dependant on fittings used and water circuit lengths)
A. Xclusive 24
B. Xclusive 30
C. Xclusive 36
A
29
7.2.2 Boiler with heat pump boiler
The boiler is suitable for use in combination with a heat pump
unit.
If the outlet temperature of a heat pump boiler is lower than
55°C, then the Intergas Xclusive will create a demand to
increase this depending on the boilers target temperature
setting.
Operational principle:
The domestic hot water outlet connection of the heat pump
unit is connected to the input of the thermostatic mixing valve
(see the adjacent diagram). If the DHW temperature of the
boiler is higher than the set temperature of the mixing valve,
the heat pump boiler will be stopped. (The mixing valve does
not fully close, a small amount (approximately 10%) will
always pass through the Intergas Xclusive.
As soon as the outlet temperature of the heat pump unit
becomes lower than the set temperature of the mixing valve,
the flow through the Intergas Xclusive will increase. If the flow
becomes suicient > 2.5lts/min then the Intergas Xclusive boiler
will start producing domestic hot water.
When the outlet temperature of the heat pump unit has
become lower than the set temperature of the mixing valve
< 12°C, almost the entire domestic hot water flow diverts
through the Intergas Xclusive. This time approximately 10% of
the flow is now taken from the heat pump unit.
The domestic hot water flow rate will be limited to the
maximum possible through the Intergas Xclusive (see §7.2.1).
Connection diagram for Xclusive boiler with heat pump unit
A. Heat pump unit
B. Xclusive Boiler
C. Mixing valve (Set to 55°C) max 60°C
D. Mains cold water inlet (service valve required)
E. DHW outlet from heat pump unit
F. DHW outlet (mixed supply) for consumer
Installation:
The combination must be configured according to the adjacent
connection diagram. The following points are important to
guarantee a correct operation of the combination.
Thermostatic mixing valve (switched):
The thermostatic switch valve used is a modified valve that
meets the specific requirements to which the combination heat
pump boiler and Intergas Xclusiveare subject. For the correct
operation of the combination, the switch valve has a fixed
maximum temperature setting.
B
E
A
D
C
F
30
Domestic hot water inlet pressure:
For a flow volume of 15 litres per minute, the initial pressure
must be a minimum of 2.3 bar. The maximum static domestic
hot water pressure for the Xclusive is 5 bar. A pressure
reducing valve (set to 3 bar) must be installed to prevent
excessive build up, it must be located no closer in proximity to
the boiler than 3 meters (for expension purposes).
Maximum flow volume:
If the domestic hot water flow is greater than 20 litres per
minute, the Intergas Xclusive will start a domestic hot water
demand, regardless of the outlet temperature of the heat
pump unit.
Maximum temperature setting of the heat pump boiler:
The outlet temperature of the heat pump unit must not be set
higher than 60°C.
Position of thermostatic mixing valve:
To prevent the thermostatic mixing valve being influenced too
much by the surrounding air temperature, the valve must be
placed in a position and as close as possible to the domestic
hot water connection of the boiler (maximum distance of
500mm). This prevents the boiler from igniting every time an
outlet tap or shower is operated.
Influence of water flow:
To prevent the flow by the Intergas Xclusivebeing influenced
during operation of the valve, the domestic hot water ‘out’
pipework of the combination must run straight (see connection
diagram [F]).
7.2.3 Boiler with Pre-Heated Solar Boiler)
A connection set and a thermostatic mixing valve are available
to order for this purpose.
Comment:
The NTC cold water sensor must be wired to Connection X13
4/5. When combined with a solar energy system, a thermostatic
mixing valve, set at 55°C (max 60°C), must always be installed
aer the boiler for safety reasons.
► Pre-heated Solar boiler conversion set item no 090347► Thermostatic mixing valve item no 842177
Connection diagram:
A. Intergas Xclusive boiler
B. Solar thermal store
C. Mains cold water inlet
D. Safety group (pressure reducing &
pressure relief valve)
E. Hot out to cold inlet max. 85°C
F. Domestic hot water outlet
G. Thermostatic mixing valve 35°C-65°C
(set at 55°C) TMV3
H. Domestic hot water mixed outlet
I. Inlet water NTC sensor
Thermostatic
mixing valve
B
A
A
I
F
G
H
C
E
C
D
C
31
7.3 Electrical connection
CAREFUL
► A fused spur must be located no more
than 1 metre from the appliance.
► For installation within a moisture bound
area i.e a bathroom or kitchen then
please consult the current electrical
regulations for safe separation distances.
► When working on the electrical circuit
always isolate the 230v supply.
► Should the mains power cord be
replaced, this must be ordered directly
from Intergas.
To gain access to the electrical connections or PCB:
► Remove the front panel (see §6.2.2) and pull the PCB
housing forward; then tilt it downwards.
► Consult the electrical schematic in §12.1 for all boiler
connections.
CAREFUL
► The Xclusive complies with IPX4D water
ingress protection. Any cables routed
through the PCB housing must have
grommets or glands fitted to ensure this
integrity is maintained.
► Aer the desired connections have been made, slide the
PCB housing back into the boiler (until the le and right
safety clips are locked) then replace the front room sealed
cover on the boiler; see §6.2.2.
► Aer making the desired connections re-establish the power
supply to the boiler.
7.4 Gas connection
► Using the supplied gas isolation valve & fibre washer
connect the preformed gas pipe to the installation supply
pipework and fully tighten.
► Ensure that the gas pipework is correctly supported with
wrap over type clips.
► Open the main gas valve and boiler isolation valve then
purge the system of air.
► Carry out a full tightness test checking all connections for
any leakage (any leaks must be rectified before proceeding).
CAREFUL
► Before starting any work on the boiler,
► The boiler is intended exclusively to be
► When pollution in the gas is to be
always close the gas isolation valve.
installed on a domestic gas supply with a
meter that includes an ECV and pressure
governor.
expected a gas filter must be placed
in the gas installation pipework to the
boiler.
Gas isolation
valve
22 mm preformed
gas pipe
32
7.5 Connecting room thermostat
X13
The boiler is suitable for connection to the following room
thermostats:
The boiler is supplied with an OpenTherm connection X13 1/2 .
This allows the connection of the Intergas Comfort Touch as
well as other modulating OpenTherm thermostats without
any additional modifications. The Xclusive is also suitable for
OpenTherm Smart Power.
► Position the thermostat in a room that functions as a
reference point (in general, the living room or hall).
► Remove the link and connect the modulating thermostat to
terminals 1/2 X13 (also see §12.1); the polarity of the wires
is not important in this situation.
If you would like to make use of the *domestic hot water on/
o switch function of the OpenTherm thermostat, the DHW
comfort function must be set to ‘eco’ or ‘on’ (see §9.1.2) and
parameter P074 must be set to 0.
On
O
12
Remove the yellow link
wire prior to connecting
the room thermostat
21
*Dependant on model type and availability for further
information, consult the manufacturers instructions for the OT
room thermostat installed.
7.5.2 Connecting on/o volt free TPI room thermostat
The boiler is suitable for connection to a 2-wire on/o room
thermostat.
► Position the thermostat in the room that functions as a
reference point (in general, the living room or hall).
► Remove the link and connect the TPI room thermostat to
Connector 1/2 X13 (also see §12.1); the polarity of the wires
is not important in this situation.
► If both OpenTherm and on/o TPI
thermostats are connected, the on/o
TPI thermostat will have priority over the
OpenTherm thermostat.
► Position the thermostat in the room that functions as a
reference point (in general, the living room or hall).
► Connect the 2-wire room thermostat to terminals 1/2
X3 (also see §12.1); the polarity is not important in this
situation however terminal 1 (L) is the supply from the PCB
90 to 230v ac, terminal 2 (S) is the demand signal from the
room thermostat to the boiler.
IMPORTANT (HIGH VOLTAGE)
► Isolate the appliance from the electrical
supply before connecting the thermostat.
12
X4 X3 (230V)
Connecting 230V room thermostat
33
7.5.4 Connecting outdoor sensor
The boiler has the facility to operate with an Intergas outdoor
weather sensor, part number 203207. The outdoor sensor must
be used in combination with an on/o or OpenTherm room
thermostat.
In principle, any on/o or OpenTherm room thermostat can
be combined with an Intergas outdoor weather sensor.
With an on/o thermostat, the boiler will adjust the flow
temperature according to the room target temperature.
With an OpenTherm thermostat, the flow temperature is
controlled via the actual internal & external temperatures, this
modulates the burner using load control to give a more precise
output from the boiler saving energy.
► Connect the outdoor sensor to Connector X13 terminals 3/4
(also see §12.1).
For the heating line graph, see §9.7 Outside weather
compensation.
7.5.5 Frost protection
► To prevent freezing of the condensate pipework and the
boiler, it must be installed in a frost-free area..
► The boiler is equipped with a frost protection system.
Should the temperature of the water within the heat
exchanger drop below 5 °C, the pump will run and if
required it will ignite the burner until the temperature of the
water is up to approximately 15 °C.
4
3
Outdoor weather sensor
part number. 203207
34
X13 X12
Connecting outdoor sensor
1212
12
On
O
Comment
With the on/o TPI room thermostat fitted as per §7.5.2 you
must locate the frost stat in an area that will be subject to the
coldest conditions, ideally a radiator fitted within the
frost-sensitive area must be open on both lock shield & wheel
head valves.
► The ideal place to site a frost thermostat is the coldest area
within the property (for example, a garage or roof space).
► Connect the frost thermostat in parallel with an on/o
room thermostat or RF thermostat onto Connector X13 1/2
(also see §12.1).
CAREFUL
► With the use of an OpenTherm
thermostat, a frost thermostat must not
be connected in parallel on Connector
X13. In this situation, connect the
OpenTherm thermostat to Connector X13
and the frost thermostat to Connector
X12.
If the (external) frost thermostat is used for the installation
and it is connected to the boiler as shown, it will not be active
when the boiler is switched o or the power removed.
X13 X12
Frost thermostat and on/o thermostat
parallel connection
12
12
X13 X12
Frost thermostat and OpenTherm thermostat
connection
12
12
34
X13 X12
X14
7.5.6 Connecting boiler sensor/thermostat
► The DHW NTC cylinder sensor can be wired to connector
X13 4/5 (also see §7.1.4 & §7.1.5).
7.5.7 PC interface
The boiler PCB has an interface for a PC. The PC can
communicate with the boiler via an IDS cable, or wirelessly
through the Intergas USB dongle, providing the appropriate
soware has been installed. This facility allows the
attending engineer to monitor complete functionality of the
appliance, change parameters and view historic fault
codes.
Engineers must be fully conversant with this utility, training
is available from Intergas Heating Ltd.
NOTE: IDS cable and USB dongles are subject to
availability (Windows operating system not ISO compliant).
4
5
45
NTC Cylinder sensor
connection
http://www.intergasverwarming.nl
► Connect the cable to Connector X14 (also see §12.1).
7.5.8 Comfort Touch
It is possible to combine the appliance with the Intergas OpenTherm Comfort
Touch Gateway kit this is available in two options:Part number 032034 R.F Gateway inc white Comfort touch thermostat (wired to boiler X13 1/2)
Part number 032044 R.F Gateway inc black Comfort touch thermostat (wired to boiler X13 1/2)
This set consists of a Intergas gateway and a connection set.
The Intergas gateway provides a connection between an Internet router and the boiler, so that
the boiler can be monitored and managed via a web server using the Comfort Touch service app.
The Comfort Touch is available via the regular merchant.
If the end user also wants to make use of the Comfort Touch possibilities of the appliance, the
set is also available with a Honeywell Round thermostat, part number 032164 R.F Gateway inc
Honeywell round R.F thermostat (paired to boiler RF module)
For the end user, a consumer version of the Comfort Touch app is available.
The Comfort Touch service and consumer app can be downloaded from both the Google Play
Store and the Apple App Store.
X15
X13
PC connection
Comfort Touch App
35
7.6 Flue and air supply duct
► For the installation of the flue and
air supply duct material, see the
manual included with the materials.
Further technical information and
specific assembly instructions are
available upon request.
► Only plastic PP flue material is allowed.
► Make sure that the socket connections
of the flue and air supply duct materials
are correctly sealed. Incorrect connection
of the flue and the air supply duct
can lead to hazardous situations or
result in personal injury. Check all flue
components for tightness.
► Do not use screws or nails to mount the
flue system as leakage can occur only
use the correct support brackets at the
recommended distances.
► Do not use any sort of grease when
connecting the flue system. Use water
instead. The sealing rubbers can be
adversely aected when grease is applied
and can also become disconnected.
► Do not mix any components, materials
or ways of connecting from dierent
manufacturers as they must be approved
by Intergas Heating Ltd.
7.6.1 Flue, materials and compounds
Flue materials
ExecutionDiameterMaterialRemark
Rigid ConcentricØ100/60 mm► Plastic T120Plastic; Approved material with lip ring sealing.
Rigid single wallØ80 mm► Plastic T120Plastic; Approved material with lip ring sealing.
Flexible Concentric Ø100/60 mm► Plastic T120
Air supply materials
ExecutionDiameterMaterialRemark
Rigid single wallØ80 mm► Plastic T120Plastic; Approved material with lip ring sealing.
FlexibleØ100/60 mm► Plastic T120Plastic; Approved material with lip ring sealing.
36
7.7 Pipeline lengths
D
R
R/D = 1
D
R/D = 1
R
As the resistance of the flue and air supply duct pipes increases, the
capacity of the boiler will decrease. The allowed decrease in capacity
is a maximum of 5%.
The resistance of the air supply duct and the flue depends on
the length and diameter of the piping system and all associated
components. For each boiler category, the total allowed pipeline
length of the air supply duct and flue is given.
C33
C33
C33C13
C13C33
The specification of the pipeline length in metres assumes Ø80
mm piping.
7.7.1 Replacement lengths
Elbow of 90°
Elbow of 45°
BoilerLength
Intergas Xclusive 24100 m
Intergas Xclusive 3085 m
Intergas Xclusive 3680 m
R/D=0.54 m
R/D=0.52 m
7.7.2 Example calculation
PipingPipeline lengthTotal pipeline length
FlueL1+L2+L3+(2x4m)
Air supply ductL4+L5+L6+(2x4m)16 m
Comments
► The total pipeline length is:
The sum of the straight pipeline lengths + the sum of all the bends
which equates to a total of 33 metres as per the adjacent drawing.
► If the equivalent length of the air supply duct and flue gas duct
combined are less than the maximum permissible quoted then the
twin flue system meets the requirements at this point.
16 m
C33C53
R
R/D = 0,5
D
C13
C13C33C53
R
R/D = 0,5
D
Twin Flue General assembly guide
Flue gas section assembly
► Connect the 80mm vertical adaptor 090767 to the boiler (optional
extra).
► Slide the combustion outlet pipe into the adaptor on the boiler.► Working from the boiler, slide each extension spigot into the previous
socket and continue with each extension or bend.
► The flue must be bracketed every metre and every change in direction.► Each bend should have a bracket fitted either side.
L3 = 6,5m
L4 = 6m
► Connect the final section to the chosen terminal outlet.► The flue gas section must be installed with a fall of 5mm/mtr back
towards the boiler.
Air supply section assembly
► Remove either of the air induction caps by liing the tab and rotating it
anticlockwise by 90 °.
► Slide the first air inlet pipe section into the boiler induction socket.
L6 = 1,5m
► Working from the boiler, lide each extension spigot into the previous
socket and continue with each extension and bend.
L1 = 1m
► The air duct must be bracketed every metre and every change of
direction.
► Each bend should have a bracket fitted either side.► Connect the final section to the chosen terminal outlet.► The air supply section must be installed with a fall away from the boiler.
(*Not applicable to vertical flue/air sections)
37
7.8 General layout of the flue
The following drawing shows possible situations schematically.
COMMENT
► The following schematic drawings serve
as examples and the details may dier
from the actual situation.
C53
C13
C13
C33
C33
C13
C33
C33
C33
C33
C33
Note for flue systems
Cat.Note according to CEMaterials
C13The terminal is located in the façade; the inlet for the air supply duct is located in the
Terminal
same pressure area as the terminal. Example: combined façade terminal
Other components
C33The terminal is located above the roof; the inlet for the air supply duct is located in the
same pressure area as the terminal of the flue piping.
Terminal
Terminal at the
prefab chimney
Other components
C53Closed unit, connected to separate air supply duct and flue channels, terminated in
various pressure zones. See the installation manual for the possibilities.
Intake grille
Other components
and exhaust cap
38
7.8.1 Horizontal wall terminal 60/100mm C13
COMMENT
► PP Pipes for the connection of the air
supply duct and the flue from the boiler
to the wall terminal 076355 must have a
diameter of Ø80 mm.
► The individual flue pipe (Ø80) and/ or
the internal pipe of the combi-pipe
wall terminal / extension pipe must be
approved by Intergas heating ltd.
Allowed pipeline length
► Twin-pipe
Air supply duct and flue pipe together, excluding the length of
the combi-pipe wall terminal.
BoilerLength
Intergas Xclusive 24100 m
Intergas Xclusive 3085 m
Intergas Xclusive 3680 m
► Concentric
Air supply duct and combustible gas exhaust pipe
together, excluding the length of the combi-pipe wall
terminal.
BoilerC13
Intergas Xclusive 2410 m
Intergas Xclusive 3010 m
Ø60/100
Intergas Xclusive 3610 m
Assembly of combi-pipe horizontal terminal
► Create an opening of Ø130 mm at the location of the
terminal.
► Shorten the wall terminal to the required length.► Assemble the concentric flue system.► Slide the wall terminal in through the opening and attach to
the concentric flue.
► Seal the flue through the wall with sand & cement and fit
the supplied decorative covers to the opening both inside
& out.
► The terminal should be positioned level however any
further extensions must slope back to the boiler 5mm/mtr.
art. no. 086890
art. no. 082969
100mm
39
7.8.2 Flue terminal positions 60/100mm C13
Concentric Flue 60/100
The boiler utilises a special concentric flue adapter which can only be used with the
elbow that is part of the horizontal flue kits.
The flue is not supplied with the boiler and should be purchased separately from your
supplier. This flue may be routed to the rear, le or right of the appliance by means of the
900 degree bend, which is supplied in the flue kit.
Note
Only use a pproved Intergas flue products with this boiler, which can be sourced from
your boiler or Intergas stockist, with C33 type applications a vertical flue adapter will be
required to connect to the boiler.
Flue Terminal position
Terminal Position
Directly below an open able window or other opening
A
e.g. air brick
distance
Below gutters, soil pipes or drain pipes can be reduced
Min.
to 25mm, as long as the flue terminal is ectended to clear
B
any overhang. External flue joints must be sealed with
suitable slicon seal.
Below eaves200mm
C
D
Below balconies or car front roofs
E
From vertical drain pipes and soil pip
F
From internal or external corners
G
Above ground, roof or balcony level, Terminal guards
must be fitted if less than 2 metres from the ground.
H
From a surface facing a terminal
I
From a terminal discharging towards another terminal
J
From an opening in a carport (e.g. door, window) into a
dwelling
K
Vertically from a terminal on the same wall
L
Horizontally from a terminal on the same wall300mm
300mm
25mm
200mm
25mm
300mm
300mm
600mm
1200mm
1200mm
1500mm
M
Above an opening, air brick, opening windows, etc.
N
Horizontally to an opening, air brick, opening windows,
300mm
300mm
etc.
P
Above roof level (to base of terminal)
Q
From adjacent wall to flue
R
From an adjacent opening window
From another roof terminal600mm
S
300mm
300mm
1000mm
Distance to a boundery, unless it will cause a nuisance.
BS 5440:Part1 recommends that care should be taken in
-
sitting terminal in relation to boundary lines. A PMK or
Deflector may be fitted.
Terminals adjacent to windows or openings on pitched
and flat roofs:
The flue should not penetrate this area.
T
T1
T2
40
600mm
2000mm
600mm
Note
Intergas cannot be held responsible for
atmospheric conditions when siting flue
terminals it is the installers responsibility to
ensure products of combustion cannot enter
the building under adverse or normal weather
conditions.
CAUTION
Once the flue has been installed and the appliance
commissioned, the installer should observe the
plume direction. Particular attention should be
drawn to plume vapour re-entering the boiler via
the air intake. If this occurs, it is highly possible the
flue is fitted within a negative pressure area and
therefore a plume management kit (PMK) must be
fitted.
7.8.3 PMK terminal positions 60mm
All measurements in millimetres
200
150
25
25
600
1
Boundary
100
7
200
300
Window
To reduce the telescopic flue length further:
Separate the telescopic flue, with the terminal end,
mark the length required (min. 130mm) for the term
inal and cut square, taking care not to damage the
tubes.
Remove any burrs and chamfer the outer edge of the
tubes to assist ease of connection and prevent seal
damage. The aluminum tape is not required when
reducing the termi nal to a single section.
3
2
Balcony
200
150
200
150
Window
300
Door
150
1,200
4
300
150
Window
300
200
5
6
Drainpipe
Terminal Position
600mm distance to a boundary or surface facing a boundary,
unless it will cause a nuisance. BS5440:Part1 recommends that
care is taken when siting terminals in relation to boundaries.
1
Adjacent to a boundary line.
Internal/external corners. The air intake clearance can be
reduced to 150 mm providing the flue exhaust outlet has a 300
2
mm clearance.
The flue cannot be lower than 1,000 mm from the top of the
3
light well due to the build up of combustion products.
41,200 mm between air intake and facing terminal.
5Clearance no less than 200 mm from the lowest point of the
balcony or overhang.
61,200 mm from an opening in a car port on the same
wall i.e. door or window leading into dwelling.
7Balcony kit option.
Using a Plume Management Kit the air intake measurement
can be reduced to 150 mm providing the flue exhaust outlet
has a 300 mm clearance. Plume kits r unning horizontally
must have a 10° fall back to the boiler for proper disposal of
condensate.
For details on specific lengths see relevant boiler Technical &
Specification information.
300 mm minimum clearances to a opening e.g. window.
However the minimum clearance to an opening in direction
that the plume management is facing, must be increased to
1,500 mm.
Where the flue is less than 150 mm to a drain pipe and plume re
direction is used the deflector should not be directe-d towards
the drainpipe.
Min. distance
600mm
300mm
(Air) 150mm
(Exhaust) 300mm
1000mm
1200mm
200mm
300mm
(Air) 150mm
(Exhaust) 300mm
.
Installations in
car ports are not
recommended
41
7.8.2 Vertical roof terminal for twin-pipe 80mm flue
system C33
IMPORTANT
► PP Pipes for the connection of the air
supply and the flue ducts from the boiler
to the vertical Terminal must have a
diameter of Ø80 mm.
► All the flue pipe components and any
terminal used must must be approved by
Intergas heating ltd.
► Intergas Twin-pipe vertical terminal (086883)
Allowed pipeline length
► Twin-pipe
Air supply duct and flue pipe combined, excluding the length of
the Twin-pipe wall terminal or the twin-pipe wall terminal.
BoilerLength
Intergas Xclusive 24100 m
Intergas Xclusive 3085 m
Intergas Xclusive 3680 m
► Concentric
Air supply duct and combustible gas exhaust pipe, excluding
the length of the Twin-pipe wall terminal.
Flat roof
Pitched roof
BoilerC33
Intergas Xclusive 2410 m
Intergas Xclusive 3010 m
Ø60/100
Intergas Xclusive 3610 m
Assembly of twin-pipe vertical terminal
► On a sloping roof, install a pitched weather slate (art no.
087910) then slide the terminal through the slate and adjust
to vertical. Seal around the storm collar and adjusting
section onto the slate with a suitable clear silicone sealant,
that is specifically designed for external conditions (not
supplied).
► On a flat roof, install a flat roof weather slate (art no. 087372)
then slide the terminal through the slate and ensure it is
vertical. Seal around the storm collar using a suitable clear
silicone sealant, that is specifically designed for external
conditions (not supplied).
► Install the 80/80 twin pipe manifold onto the bottom of the
vertical terminal and secure everything in place with the
supplied bracket.
Pitched roof
min. 300
min. 300
Flat roof
42
7.8.3 Vertical roof terminal and air supply duct from
the facade C53
IMPORTANT
► The air supply duct in the facade must
have an Intergas intake grille (art. no.
082856).
► All the flue pipe components and any
terminal used must must be approved by
Intergas heating ltd.
Permissible equivalent pipeline length
Air supply duct and flue pipe combined, excluding the
length of the terminal section.
BoilerLength
Intergas Xclusive 24100 m
Intergas Xclusive 3085 m
Intergas Xclusive 3680 m
Assembly of horizontal air supply duct
► The air supply can be made in an arbitrary location in the
façade.
► At the location of the supply, core an opening of Ø90 mm.► Shorten the air supply duct pipe to the desired length out of
the wall so the cover plate can sit flush.
► Attach the Intergas air intake terminal to the wall using the
4 x screws and plugs provided
► Slide the air supply onto the terminal and attach the
decorative plate to the internal plaster wall face.
► The air supply duct MUST BE angled away from the
appliance to prevent rain entering the boiler during adverse
weather conditions.
Vertical Roof terminal
086883
Intergas intake
grille 082856
min. 500
Air cover terminal
075438
Assembly of vertical flue terminal
► On a sloping roof, install a pitched weather slate (part
number 087909) then slide the terminal through the slate
and adjust to vertical. Seal around the storm collar and
adjusting section onto the slate with a suitable clear silicone
sealant, that is specifically designed for external conditions
(not supplied).
► On a flat roof, install a flat roof weather slate (part number
075333) then slide the terminal through the slate and
ensure it is vertical. Seal around the storm collar using a
suitable clear silicone sealant, that is specifically designed
for external conditions (not supplied).
► The terminal must be at least 500 mm above the roof
surface secure everything in place with the supplied
bracket.
43
7.8.4 Clamping the flue system (twin and concentric)
IMPORTANT
► These regulations are typical for both
concentric and twin flue systems.
► The flue system must be secured to a solid
structure.
► The flue system should have a continuous
fall back to the boiler (1.5° to 3°).
► Only use Intergas approved brackets.► Every bend or change of direction must
be secured by using the approved bracket
(excluding the appliance bend).
If the length of the pipes before and aer
the first elbow, are no more than 250mm,
a support bracket must be used and
positioned on the elbow! (See illustration D)
► Every extension must be secured per metre
with a bracket.
This bracket must be clamped around the
pipe ensuring free movement for expansion
and contraction purposes.
► Make sure bracket is locked correctly
depending on its location i.e.
position "A" = pipe location
position "B" = elbow location.
A = bracket on pipe
B = bracket on elbow
Maximum distance between brackets
Orientation
Flue system
Horizontal/
non-vertical
Vertical
Safe-PP1000 mm2000 mm
Concentric1000 mm2000 mm
► Distribute the length between brackets evenly.► Each flue system has to contain at least 1 bracket.► The distance between the boiler and the first bracket must not be more than 500 mm.
max. 1000 mm
max. 1000 mm
max. 2000 mm
ABC
44
COMMENT
► These examples are typical for
both twin and concentric flue
bracket positioning.
max. 1000 mm
max. 1000 mm
max. 250 mm
max. 250 mm
Second element
aer first elbow
DE
max. 500 mm
max. 250 mm
max. 250 mm
Second element aer first elbow
fall back to boiler
F
45
7.8.7 Twin flue terminal positions
Terminal positions
I
F
L
J
B
A
G
Terminal Position
Directly below to an openable window or other opening
A
e.g. air brick
Directly above an opening
B
Horizontally to an opening300mm50mm
C
D,E
C
M
H
I
H
Flue Min.
Distance
Air Min.
Distance
300mm50mm
300mm50mm
N
K
D
Below gutters, soil pipes or drain pipes
E
Below eaves
F
Below balcony or car port roof, Terminal guards must be
75mm75mm
200mm50mm
200mm50mm
fitted if less than 2 metres from the ground
G
Above ground or balcony or roof, Terminal guards must
150mm25mm
be fitted if less than 2 metres from the ground.
H
From internal or extrnal corners or to boundary
I
Above ground or balcony or roof, Terminal guards must
300mm50mm
300mm50mm
be fitted if less than 2 metres from the ground.
J
From a surface or boundary facing a terminal600mm100mm
K
From a terminal discharging towards another terminal
L
From an opening in a car port (e.g. door, window) into a
dwelling
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
1200mm100mm
1200mm100mm
1500mm1500mm
300mm300mm
46
8 OPERATION
8.1 Using the control panel
Gently touch and release the white power LED symbol
Power on / power o mode.
Gently touch and hold the white power LED symbol for 2 seconds
2sec
8.2 Boiler preparation
8.2.1 Filling and venting the central heating system
► Connect the power cable to a 3 amp fused spur supplied via
a type "A" RCD.
► Switch on the power supply to the boiler, A 22 may
momentary appear on the right display; this means that the
internal sensors are being checked. The firmware version
will be momentary shown on the le display.
The boiler enters standby power o mode, characterised by
a line – on the right display and the central heating system
pressure on the le display.
► When the central heating pressure is
lower than 0.5 bar, this will be indicated
by a flashing display (if the boiler is in
central heating demand).
► If the central heating pressure is below
0.2 bar then the demand will no longer
be met.
WARNING
► When an additive is added to the
central heating water, this must be
suitable for the materials used in the
boiler,such as copper, brass, steel,
stainlesssteel, plastic and rubber.
Intergas recommend products
manufactured from :
• Fernox Tel 0330 100 7750
• ADEY Innovations Tel 01242 546 777
• Altecnic Calei Group Tel 01785 218 200
Central heating pressure is too low.
47
► Connect all the pipework then fill the heating system with
mains water via the filling loop provided to a maximum
pressure of 1.5 bar (The pressure can be viewed with the
power supply on and the boiler switched o, by touching
and holding the power LED for 2 seconds).
► Vent the appliance with the manual air vent screw on the
top le hand side of the boiler.
► Vent the air out the entire system with the manual air vent
screws on the radiators.
► Top up the CH installation pressure as required back to 1.5
bar.
► Check the system for any leaks and repair any found.► Switch on the boiler by touching the control panel just
above the power LED and holding this for 2 seconds.
► Put the boiler in operation using the room thermostat
or Service mode (see §9.1.5) and check the water is
circulating around the system correctly.
Manual air vent
8.2.2 Domestic hot water facility
► Open the cold water main isolation valve under the boiler.► Vent the heat exchanger and the pipework by opening all
domestic hot water outlets.
Leave the outlets open until all the air has dispersed from
the system then close each one in turn.
► Check all connections and pipework for any leaks, repair
any found as required.
► With the boiler switched on run a domestic hot water outlet
and check the boiler is operating correctly (Only aer the
Gas supply has been commissioned correctly).
Switch on boiler
2sec
Switch o boiler
2sec
8.2.3 Gas supply
► Purge the gas installation pipework to ensure no air
remains.
► Complete a full tightness test any leaks must be repaired
and retested prior to operating the boiler.
► Check the inlet working pressure via P1 at maximum output
(H) which must be ≥17mB with all other appliances at full
rate and gas-air control at minimum output to ensure the
correct CO levels (see §9.9).
48
(P1) Inlet pressure
measurement test
point
8.3 Commissioning procedure
Aer filling the heating and hot water systems correctly, the
boiler can be commissioned by following the below procedure
for this:
► Switch on the boiler by touching just above the power LED
and holding this for 2 seconds.
► Adjust the pump setting depending on the set maximum
capacity and the heating circuit resistance.
To adjust the pump capacity of the boiler; see §9.6.
► Adjust the temperature on the room thermostat to higher
than the actual room temperature so the boiler creates a
heating demand (Timer must be set to on).
Symbols
► Heat up the system.► Check whether the set central heating output is suicient
to achieve the room target temperature. If necessary, the
maximum central heating output can be adjusted; see §9.3
(parameter P010) and §9.5.
► Check whether the set minimum and maximum values of
the pump output have been adjusted correctly; see §9.3.
► Switch o the boiler by touching just above the power LED
and holding this for 2 seconds.
► Vent the system again once cool and top-up the pressure if
required (see §8.2.1).
► Now switch on the boiler again by touching just above the
power LED and holding this for 2 seconds.
► Check the heating and the domestic hot water facility for
correct operation.
► Instruct the end user about filling and venting and the
operation of the heating and the domestic hot water.
► Hand the installation instructions and warranty registration
card to the customer / end user.
► The heating system must be chemically flushed and treated
to BS7593:2019 as per our "Terms & conditions" failure to
comply will invalidate the warranty supplied with this
product, a system filter should be installed on the return
pipework.
and light up.
Switch on boiler
Switch o boiler
2sec
2sec
Garantiebewijs Intergas HR-ketel
Type/Serienr.
Datum installatie:
Volgens geldende voorschriften
geïnstalleerd door:
voor klant
Naam installateur:
Adres:
Postcode:
Woonplaats:
Naam koper:
Adres:
Postcode:
Woonplaats:
12345678910
Voor de ‘Garantiebepalingen
Intergas HR-ketels’ verwijzen
wij u naar onze website:
www.intergasverwarming.nl
of naar het bij uw HR-ketel
bijgevoegde installatievoorschrift.
Op uw verzoek sturen wij u
graag een exemplaar toe.
>>Betrouwbaar in warmte
Comments
► The boiler has microprocessor control technology which
ignites the burner and continuously monitors the flame,
modulates the fan and pump with each demand for central
heating output.
► The modulating pump operates during a demand for
heating, it has an overrun facility preset in parameter P033
and it is advised not to adjust this setting.
► The pump automatically runs once every 24 hours for 10
seconds to prevent it becoming stuck during the summer
months, this operation takes place 24 hours aer the last
heat demand.
► Please note the pump does not operate during domestic
hot water operation.
49
8.4 Clock function
The boiler is equipped with a digital clock and oers the
possibility to program both CH and DHW operations separately.
To activate the clock program the following parameters have to be set:
For CH operation parameter P040 = 1 (This is factory set to 1 "active")
For DHW operation parameter P087 = 1 (This is factory set to 0 "Inactive")
► In CH operation 6 periods can be programmed to switch from CH
o or CH on.
► In DHW operation 4 periods can be programmed to switch the
pre-heat function of the heat exchanger from on to o.
Additionally the following special modes can be chosen:
In CH operation
► P-on (Program on):
The boiler will respond only on CH demands within the
chosen time slots. If the clock program does not contain
any valid switching points, the boiler will remain in standby.
The actual time is shown on the le display indicating that
the clock program is active.
► T-on (Temporary on):
The clock program will be temporary overruled. The boiler will
respond to every CH demand until the next "o" switching point
(t-ON will be displayed on the le side).
► On (Continuous on):
The boiler will respond to every CH demand without any time
limit.
► O:
The boiler will not respond to any CH demand.
(Heating operation is subject to the room thermostat set
point and boiler flow target temperature, outside weather
compensation, if fitted, can restrict the flow temperature for
energy saving purposes, depending upon curve set-point and
outside temperature at that time ).
In DHW operation
► P-on (Program on):
The appliance's DHW comfort function is switched on
continuously within the chosen time slots. In this mode the
heat exchanger will be kept up to temperature to assure rapid
delivery of DHW. If the clock program does not contain any valid
switching points, the heat exchanger will continuously be kept up
to temperature.
► On (Continuous on):
The appliance's DHW comfort function is switched on
continuously. The heat exchanger will be kept up to temperature.
► Eco:
The appliance's DHW comfort function is self learning within the
chosen time slots. The appliance will adapt to the pattern of DHW
usage. As a result, the temperature of the heat exchanger will
not be maintained during the night or during long absence. If the
clock program does not contain any valid switching points, the
self learning feature is maintained.
► O:
The temperature of the heat exchanger is not maintained, as a
result of the delivery of domestic hot water takes slightly longer.
If you don't require rapid delivery of DHW then the comfort
function can be switched o.
Clock shown (P-on active)
T-on active
Note
For setting and adjusting the clock and timer function see §9.2.
50
8.5 Shutting down the boiler
CAREFUL
► Only drain the boiler and the system if
the mains voltage has been interrupted
and there is a chance of freezing.
► Switch the power o to the boiler.► Remove the 3 amp fuse from the wall spur.► Turn o the gas isolation valve under the boiler.► Drain the boiler completely.► Drain the heating system at the lowest point.► Turn o the mains cold water supply isolation valve under
the boiler.
► Drain the boiler by disconnecting the domestic hot water
connections under the boiler and the pipework at the
lowest point.
51
9 SETTINGS AND ADJUSTMENTS
8
The operation of the boiler can be influenced by the various
(parameter) settings within the PCB. Access of these menus, can
be made and modified via the touch screen display.
NOTE. Some of the settings are only accessible aer entering the
installer’s code (see §9.1.5 and §9.3).
► The boiler has a touch screen display panel.
Symbols will illuminate when they are
operable and they will be extinguished when
they are no longer available.
► 8.8.8.8 8.8.8.8 : Le display / Desired temperature in °C / Central heating pressure
/ Fault code / Time / Information menu
► : - (Minus) button► : + (Plus) button
: Boiler operating (burner is switched on)
►► : Power LED ► : DHW demand / DHW comfort setting / Adjusting domestic hot
water setting
► : Central heating demand / Adjusting maximum central heating
temperature
► : Service button► : Enter button
► 8.8. : Right display / operational code
Touch screen displaying all options
9.1 Navigate the settings
There are several menus to navigate through that are
accessible via the touch screen panel.
The following menus are available:
► Main menu
First line menu from which all other menus are accessible.
► Domestic hot water menu
Menu in which the domestic hot water-related settings can be
modified or set.
► Central heating menu
Menu in which the central heating-related settings can be
modified or set.
► RF menu
Menu in which specific RF room thermostats can be assigned to
the boiler.
► Service menu
Menu in which the test programs can be activated and the
(installer’s) parameters can be modified (installer’s code
required).
► Info menu
Menu in which the current boiler characteristics can be obtained.
9.1.1 Main menu
The main menu is accessible by gently tapping just above the
power LED. The main menu can be viewed with the boiler
switched on or switched o on the fascia (230v power must be
switched on). The main menu will be displayed for 1 minute,
without intervention, it will then return to its original status.
Initial setting
The following symbols will light up:
► The domestic hot water symbol ► The central heating symbol
Main menu
► The Service symbol
The clock time will be displayed on the le side if enabled.
52
9.1.2 Domestic hot water menu
The domestic hot water menu has 2 settings and is accessible
by gently tapping on the Domestic Hot Water symbol from
the main menu.
Within the domestic hot water menu:
► The domestic hot water temperature can be adjusted► The DHW comfort function can be altered
The following symbols will illuminate:
► The Minus symbol ► The Plus symbol ► The Enter symbol
The Central Heating symbol will be extinguished.
The le section will illuminate and will display the current
preset domestic hot water temperature. By tapping on the
domestic hot water symbol once you enter the temperature
adjustment menu, by tapping on the DHW symbol again,
you enter the comfort setting menu.
To adjust the domestic hot water temperature setting:
1. Tap the Domestic Hot Water symbol
temperature is displayed on the le side of the fascia.
2. Using the Plus and Minus buttons, set the desired
temperature (for example, 55°C).
3. Tap the Enter button
PP appears on the right display (all other symbols are
A
extinguished), which means the setting has been stored.
4. The display returns to the main menu.
to confirm (or wait 30 seconds).
Main menu
. The target
Domestic hot
water Temperature
adjustment
For a swier supply of domestic hot water, the boiler has a
DHW comfort function with the following options:
► P-On:
The DHW comfort function is activated within the chosen
time settings. The heat exchanger will then maintain the
preset temperature during these times.
► On:
The DHW comfort function is permanently on. The
heat exchanger will continuously maintain the preset
temperature.
► Eco:
The DHW comfort function of the boiler will self learn.
The boiler will adapt itself to the pattern of usage for
domestic hot water. This means that the heat exchanger
will not maintain temperature during the night or with long
absences.
► O:
The heat exchanger is not preheated, the boiler will now
act as a normal combination boiler and only operate when
there is a demand for DHW.
NOTE: during the winter when the heating is operating the
heat exchanger will already be at a suicient temperature to
facilitate swi DHW supply.
To adjust the DHW comfort function:
1. Tap the Domestic Hot Water symbols 2x
. The preset
comfort setting is displayed on the le of the fascia.
2. Using the Plus and Minus buttons, set the desired
comfort setting (for example, P-On).
3. Tap the Enter button
to confirm (or wait 30 seconds).
A PP appears on the right display (all other symbols are
extinguished), this confirms the chosen setting has been
stored.
4. The display returns to the main menu.
Confirm
Main menu
Domestic hot
water menu
Tap comfort
Confirm
53
9.1.3 Central heating menu
The central heating menu has 3 settings and is accessible by
gently tapping on the Central Heating symbol from the
main menu.
Within the central heating menu:
► the maximum temperature of the central heating water can
be adjusted
► access to the RF menu► the timer function can be adjusted
The following symbols will illuminate:
► The Minus symbol ► The Plus symbol ► The Enter symbol
The Domestic Hot Water symbolwill be extinguished.
The le section will illuminate and the current preset
temperature of the central heating water will be displayed.
To adjust the central heating water temperature setting:
1. Tap the Central Heating symbol
is displayed on the le side of the fascia.
2. Using the Plus and Minus symbols, set the desired
temperature (for example, 60°C).
3. Tap the Enter button
A PP appears on the right display (all other buttons are
extinguished), which means the setting has been stored.
4. The display returns to the main menu.
Main menu
. The target temperature
Central heating
menu
to confirm (or wait 30 seconds).
Confirm
9.1.4 RF menu
The Xclusive range of boilers have a built-in Ramses 2 RF
transmitting/receiving module, this allows the boiler to
wirelessly communicate with Honeywell OpenTherm room
thermostats T87RF2025 Round, CMS927 & CMS727.
Assignment of the thermostat and additional settings can be
made via the RF menu.
The RF menu is accessible by touching and holding the Central
Heating symbol for 2 seconds. The following adjustments
can then be made:
► Assign RF thermostat► Remove assignment between boiler and RF thermostat
The following symbols will illuminate:
► The Service symbol► The Enter symbol
The le display will illuminate and, depending on the
assignment of the boiler, will show ‘rF1–’ or ‘rF1’.
rF1–:
Boiler and thermostat are not assigned.
rF1:
Boiler and thermostat are assigned.
Tap the Enter symbol
to the main menu.
To exit the RF menu without saving your settings tap the fascia
display just above the power LED, this will take you back to the
original menu or standby mode.
(or wait 1 minute) to save and return
Smart Opentherm™
Central heating
menu
RF menu (not assigned)
RF menu (assigned)
2sec
54
To adjust an RF room thermostat:
1. Touch the Central Heating symbol and hold for 2
seconds.
2. The method of assignment is dependent on the type of
room thermostat and is described within the installation
manual and operation instructions of the wireless room
thermostat. Both the appliance and the thermostat
must be in pairing mode to be able to pair.
https://youlearn.honeywellhome.com
3. Aer a successful assignment, ‘rF1’ appears in the le
display. Tap the Enter symbol to save.
To remove an assignment:
1. Touch the Central Heating symbol and hold for 2
seconds.
2. ‘rF1’ appears in the le display.
3. Tap the Service symbol to remove the assignment.
4. ‘rF1–’ appears in the le display.
5. Tap the Enter symbol to confirm the removal and return
to the main menu.
6. Make a new assignment if desired as described above.
NOTE: Removing an assigned room thermostat will disable the
central heating operation until a new one is assigned or a hard
wired control is fitted (see §7.5)
Central heating
menu
Confirm
Central heating
menu
RF menu
2sec
2sec
Delete assignment
Confirm
55
9.1.5 Service menu
The service menu is accessible by first touching the display just
above the power symbol then press and hold the service symbol
for 2 seconds.
Within the service menu:
► the test programs can be activated► access to the (installer’s) parameters► access to the info menu
The following symbols will illuminate:
► The Minus symbol ► The Plus symbol ► The Enter symbol
The Domestic Hot Water symboland the Central Heating
symbol will be extinguished.
Test programs
The boiler has a test mode facility within the PCB.
By activating a test program, the boiler will operate with a
fixed fan speed without any of the control functions
intervening however, the safety functions remain active.
The following test programs are available:
Program ‘L’
Burner on at minimum output.
Press and together once.
Program ‘h’
Burner on at maximum range rated central heating output.
Press
and together once.
Program ‘H’
Burner on at maximum output.
Press
and twice.
Switching o test program
Press
andtogether once.
Main menu
2sec
Service menu
Service menu
To activate the ‘L’ test program:
1. Press the Service symbol
and the Minus button once
at the same time. The symbol ‘L’ will appear on the right of
the display.
2. Tap the Minus button and the Plus button at the same
time to terminate the program.
To activate the ‘h’ test program:
1. Press the Service symbol and the Plus symbol once
at the same time. The symbol ‘h’ will appear on the right of
the display.
2. Tap the Minus symbol and the Plus symbol at the
same time to terminate the program.
To activate the ‘H’ test program:
1. Press the Service symbol and the Plus symbol twice
at the same time. The symbol ‘H’ will appear on the right of
the display.
2. Tap the Minus symbol and the Plus symbol at the
same time to terminate the program.
Test program ‘L’
Service menu
Test program ‘h’
Service menu
Test program ‘H’
56
(Installer’s) parameters
The (installer’s) parameters within the PCB are factory set as
detailed within table in §9.3.
These parameters can only be modified using the installer’s
access code.
The installer’s code is shown on the le display and is preceded
by the letter CC.
The parameters are also shown on the le display and are
preceded by the letter PP.
To modify a parameter:
(for example, modify parameter P031 from 80 to 90)
1. Tap the Service symbol and the Enter symbol at the
same time. The Enter symbol
is extinguished and all
other buttons remain on. ‘C000’ appears in the le display.
2. Using the Plus symbol and the Minus symbol , set the
installer’s code (C015) and tap on the Service symbol .
Parameter ‘P001’ will now be shown on the le display.
3. Using the Plus button and the Minus button , set the
desired parameter (in this example, ‘P031’) and tap on
the Service button . The current value of the relevant
parameter will be shown on the le display (in this example,
‘80’).
4. Using the Plus symbol and the Minus symbol , set the
desired value of the parameter (in this example, ‘90’).
5. Tap the Service symbol . Repeat Steps 3 and 4 to set any
additional parameters.
6. Tap the Enter symbol
to confirm. A PP appears on the right
display (all other symbols are extinguished), which means
the settings have been stored.
7. The display returns to the initial setting and is ready for any
heat demand.
Service menu
► By tapping just above the power LED during
any parameter modification will cancel the
procedure without saving any modifications
made. The display will return to the initial
setting and is ready for any heat demand.
57
9.1.6 Info menu
The info menu is accessible by touching the Service symbol
from the service menu and holding it for 2 seconds.
(Note if you are not in the service menu you will need to touch
the service symbol and hold it for 2 x 2 seconds).
Via the info menu certain boiler operational statistics can be
viewed.
Info menu
Ionisation current
The following symbols will illuminate:
► The minus symbol ► The plus symbol
Respectively the right and le display will display the relevant
infocode and its corresponding value.
By tapping the plus symbol and the minus symbol the
following characteristics are displayed in succession:
Le display Right display
► Ionisation current in A ► Domestic hot water flow in litres/minute ► Boiler output in kW ► Pump RPM in % ► Last fault code ► Current PCB Firmware version ► Current Firmware version DSP processor ► Temperature sensor S0 (Heat exchanger) ► Temperature sensor S1 (Htg flow) ► Temperature sensor S2 (not present) ► Temperature sensor S3 (DHW) ► Temperature sensor S4 (not present) ► Temperature sensor S5 (Flue gas) ► Temperature sensor S6 (Outdoor sensor option) ► Temperature sensor S7 (Cylinder sensor option)
Info menu
DHW flow
Info menu
Boiler output
Info menu
Pump RPM
Info menu
Last fault code
Info menu
Current PCB firmware version
Info menu
Current Firmware version DSP processor
Info menu
Temperature sensor S0 (Heat exchanger)
Info menu
Temperature sensor S1 (Htg flow)
Info menu
Temperature sensor S3 (DHW)
Info menu
Temperature sensor S5 (Flue gas)
58
9.2 Setting and adjusting the clock functions
Show actual time
► With the boiler in standby or operating, gently tap just above
the power LED to access the main menu (also see §9.1.1).
The actual time is shown in the le display. The symbols ,
and will also illuminate.
► If the boiler is switched o when accessing the main menu
the symbols and will also illuminate.
Clock setting and adjusting
► Ensure parameter P087 is set to 1 (clock active) default = 1► Ensure the boiler is switched o by touching and holding
just above the power LED and holding this for 2 seconds.
► Tap just above the power LED to access the main menu.
Adjust the clock to the correct time by pressing either the
or symbol.
Note: Holding the or symbol for more than 1 second
will make the clock time adjustment scroll faster.
► Tap the Enter symbol to confirm.
Note: By tapping just above the power LED instead of the
Enter symbol the display returns to the main menu
without saving any changes.
Clock shown (boiler standby)
Clock shown (boiler switched o)
Main menu
Confirm
9.2.1 Programming the CH on / o times
► With the boiler in standby or operating, gently tap just
above the power LED to access the main menu. The
symbols , and illuminate.
► Tap on the Central Heating symbol.► Tap on the Service symbol.► The symbols , , and are displayed. Also the first
switching period "t1" illuminates on the le display.
► Tapping the or symbol will scroll between the 6
dierent on/o switching periods.
► Choose a switching period (for instance "t1") and tap on the
Central Heating symbol.
► Tap on the or symbol to set the time and tap the
Central Heating symbol again to set the desired action, use
the or symbol to select either On / O or –.
The options are as follows:
► On: Start period CH on providing there is a demand
from the room thermostat.
► O: End period CH o. No hearting demand will be
provided (boiler frost protection only).
► – – : No action. The time period set will be ignored
during this section resulting in no On or O period.
► Tap on the Central Heating symbol to select the
next switching period. Set the switching time and the
corresponding action and repeat this, if required, for all 6
switching periods.
► Tap the Enter symbol to confirm. The switching times
and actions will be saved in the boiler PCB. (Aer 2 minutes
of inactivity changes made will also be saved).
A PP appears in the right display before it returns to the
Central Heating menu.
Note: By tapping just above the power LED instead of the
Enter symbol the display returns to the Central Heating
menu without saving any changes.
Main menu
Central heating menu
Switch moment 1
Switch point t1
Action moment t1
59
To apply the clock program
► With the boiler in standby or operating gently tap just above
the power LED to access the main menu (also see §9.1.1).
► Tap on the Central Heating symbol. The current
temperature of the central heating water is illuminated in
the le display. Tap the Central Heating symbol again to
activate the programmed time settings.
► Using the Plus or Minus symbol, set the desired
program option (P-on, T-on, On or O).
► Tap the Enter symbol to confirm. The chosen program
option will be saved in the boiler PCB. (Aer 2 minutes of
inactivity any changes made will automatically be saved.
A PP appears in the right display and then returns to the
Central Heating menu.
Note: By tapping just above the power LED instead of the
Enter symbol the display returns to the Central Heating
menu without saving any changes.
9.2.2 Programming the DHW pre-heat on / o times
► With the boiler in standby or operating gently tap just above
the power LED to access the main menu. The symbols ,
and illuminate.
► Tap the Domestic Hot Water symbol
is shown on the le display. Tap the Domestic Hot Water
symbol
again to switch to the clock program setting
► Tap on the Service symbol.► The symbols , , and are displayed. Also the first
switching period "t1" illuminates on the le display.
► Tapping the or symbol will scroll between the 4
dierent on/o switching periods.
► Choose a switching period (for instance "t1") and tap on the
Domestic Hot Water symbol
► Tap on the or symbol to set the time and tap the
Domestic Hot Water symbol
again to set the desired
action, use the or symbols to select either On / O or –.
The actions to be set are as follows:
► On: Start period, DHW pre heat will now keep the heat
exchanger at the preset temperature.
► O: End period, DHW pre heat is now deactivated so
the heat exchanger will not be kept at temperature.
► – – : No action. The time period set will be ignored
during this section resulting in no On or O period.
► Tap on the Domestic Hot Water symbol
next switching period. Set the switching time and the
corresponding action and repeat this, if required, for all 4
switching periods.
► Tap the Enter symbol to confirm. The switching times and
actions will be saved in the boiler PCB. (Aer 2 minutes of
inactivity changes made will also be saved).
A PP illuminates in the right display before it returns to the
Central Heating menu.
Note: By tapping just above the power LED instead of the
Enter symbol the display returns to the Central Heating
menu without saving any changes.
. The set temperature
.
to select the
Main menu
Domestic hot
water menu
Temperature
Switch moment 1
Switch point t1
Action moment t1
60
To operate the preheat with the programmed times
► With the boiler in standby or operating gently tap just above
the power LED to access the main menu (also see §9.1.1).
► Tap on the domestic hot water symbol
. The current
temperature is illuminated in the le display. Tap the
Domestic Hot Water symbol
again to activate the
programmed time settings.
► Using the Plus or Minus buttons, set the desired
program setting (P-on, On, Eco or O).
► Tap the Enter symbol to confirm. The chosen program
setting will be saved in the boiler PCB. (Aer 2 minutes of
inactivity changes made will automatically be saved).
A PP illuminates in the right display before it returns to the
Central Heating menu.
Note: By tapping just above the power LED instead of the
Enter symbol the display returns to the Domestic Hot
Water menu without saving any changes.
61
9.3 Parameters
Para
metre
P001P001
P010P010
P030P030
P031P031
P032P032
P033P033
P034P034
P035P035
P036P036
p040p040
P057P057
Set
Setting
System type0
Set maximum central heating output
Central heating pump setting0
Maximum capacity of modulating central
heating pump
Minimum capacity of modulating central
heating pump
Central heating pump overrun aer central
heating demand
Central heating pump overrun aer boiler
operation
Pump modulation
Anti-cycle time central heating
Activate clock program CH operation1
Response for OpenTherm room thermostat1
valueDescription/Setting range
------100
0 = Xclusive Combination
1 = Xclusive System boiler + cylinder
2 = Xclusive Instantaneous water heater
3 = Xclusive System boiler
75
65Value displayed as a percentage (%)
35Set 15% of parameter P031
75 = Xclusive 36
100 = Xclusive 24 / Xclusive 30
25% to 100% (see §9.5)
0 = overrun active
1 = continuous
10 to 15 minutes
10 to 15 minutes (n/a for Combi boiler)
0 = o
1
1 = on
Delay time for central heating only 0 to 15 minutes
5
(this does not delay DHW production)
0 = inactive
1 = active
0 = do not respond to heat demand if requested
temperature is lower than 30°C
1 = respond to heat demand with minimum flow
temperature limited at 30°C
2 = respond to heat demand with maximum set flow
temperature (on/o function)
1
P059P059
P070P070
P074P074
P075P075
P077P077
P081P081
p087p087
Maximum setting value of flow temperature8010°C to 90°C
Set maximum DHW output10020% to 100%
Number ECO days (During pre-heat)70 to 10 days
Max flow temp during DHW production8060°C to 90°C
Waiting time central heating demand aer
DHW operation
Setting of three-way valve or electric shuto valve
Activate clock program DHW operation0
0 to 15 minutes
0 = powered during central heating demand
0
1 = powered during DHW operation
0 = inactive
1 = active
1
DHW comfort function o.
62
9.4 Switching DHW comfort function on and o
H/M
L/M
08172533
It is possible to switch on and o the DHW comfort function
from an OpenTherm room thermostat (provided the
thermostat supports this function). To do this, the boiler must
be set at the ‘eco’ setting and the parameter P074 must be
set to 0. The self-learning character of the control is therefore
switched o. (See section §8.4 for further options).
9.5 Adjusting the maximum central heating output
The maximum central heating output is factory-set. If this
needs to be adjusted to suit the requirements of the property,
then the output can be modified via parameter P010.
See the table below:
Setting central heating output.
Desired central heating
output in kW (approx.)
P010P010
243036243036
100
75
50
35
13.819.425.76.69.312.3
10.614.619.35.16.99.2
7.39.812.83.54.76.1
5.47.09.02.63.34.3
25-
Note:
The output during combustion will slowly increase or decrease as per
the "set" flow target temperature (modulation on T
9.6 Adjusting pump capacity
The Xclusive boiler has an ErP pump that modulates based on
the central heating output demand. The minimum and
maximum output of the pump can be adjusted with the
parameters P031 and P032. See section §9.3.
The set value of parameter P031 (max. pump setting) is a
percentage of the maximum pump capacity and is linked to
parameter P010 maximum central heating system output.
The set value of parameter P032 (min. pump setting) is linked
to the minimum central heating output.
The pump capacity must be set so that the temperature
dierencial (t) between the flow and return is correct for the
system design criteria.
If the central heating load modulates between the minimum
and maximum value, the pump capacity will modulate
proportionately with it.
5.16.4
Xclusive
Minimum flow
quantity (ltrs/min)
-
2.43.1
).
flow
100%
7
6
5
C
B
75%
4
A
3
Pressure loss graph boiler central heating side
A. Xclusive 24
B. Xclusive 30
C. Xclusive 36
50%
2
1
25%
0
63
9.7 Outside weather compensation
When an optional Intergas outdoor sensor is connected, the
heating flow temperature will be automatically controlled
according to the set heating curve, depending on the outside
temperature at that time.
The weather-dependent control functions solely with an
on/o room thermostat. When using an OpenTherm room
thermostat, the outside temperature will be relayed, but the
heating line of the central heating boiler will not be active.
Taking the graph as an example and using the factory setting A.
With an outside temperature of -9°C the boiler will achieve an
approximate heating flow temperature of 80°C
Adjusting the OTC to example B. will result in an approximate
heating flow temperature of 60°C.
90
Heating line
X: T outside in °C
Y: T flow in °C
A. Factory setting
(T
CH = 80°C, T
max
B. Example
(T
CH = 60°C, T
max
CH = 25°C, T
min
CH = 25°C, T
min
out = -9°C, T
min
out = -9°C, T
min
out = 25°C)
max
out = 25°C)
max
80
70
60
50
T flow in °C
40
30
20
10
Y
0
-30-20-100
X
Tmax.
AA
B
Tmin.
102030
T outside in °C
64
9.8 Conversion to another gas type
IMPORTANT
► Only qualified competent gas safe
registered engineers may work on
the boiler and Intergas training is
recommended before undertaking the
following procedure.
If the boiler is connected to a dierent gas type than originally
set by the manufacturer, then the gas restriction ring must be
replaced. Conversion kits for other gas types are available to
order.
Changing / replacing of the gas restriction ring
► Switch o the boiler and isolate the power supply.► Close the gas isolation valve supplied with the boiler and
test to ensure there is no let-by (the valve must be replaced
if faulty or letting by before continuing with the conversion).
► Remove the room sealed front casing of the boiler.► Disconnect the union above the gas valve and rotate the gas
mixture pipe clear of the gas valve.
► Replace the O-ring seal and gas restriction ring with the
ones supplied in the new conversion kit (ensuring they are
the correct type for the gas category being supplied to the
boiler).
► Reassemble in reverse order.► Open the boiler gas isolation valve.► Check the gas connections prior to the gas valve for
tightness.
► Reestablish the power to the boiler.► Briefly operate the boiler checking all unions above the
gas valve for tightness with a calibrated electronic gas leak
detector or leak detection fluid .
► Now check the adjustment of the gas/air proportion (see
§9.10 to §9.10.3).
► Place the supplied, fuel category sticker, over the existing
one on the gas valve.
► Place the second supplied, fuel category sticker near the
data plate under the boiler.
► Aer adjusting the mixture correctly and completing all gas
safety checks, as per regulation 26(9), then replace the room
sealed front cover to check the flue integrity at full gas rate
("H" in the display).
Gas mixture pipe
Union connection
O-ring
Gas restriction ring
65
9.9 Gas/air control
IMPORTANT
► Only qualified competent gas safe
The gas/air control valve is factory set to optimise combustion for the
gas type used. The gas type (Natural Gas or LPG) is detailed on the
data plate situated under the boiler
The boiler must only be operated with the gas category specified on
the aforementioned data plate.
The boiler may optionally be converted to another gas type using a
conversion set. See §9.8.
For the correct gas restriction ring, see the table below.
Table 1: Gas restriction rings
Boiler type
Xclusive
24528392315
registered engineers may perform
adjustments to the gas/ air ratio control
on the gas valve.
Gas category
Fan
Venturi
Insert
number
Natural gas
G20
20 mbar
Gas restriction ring number
LPG
G31
30 & 50 mbar
30500450370
36500450370
By default, the boiler is set to natural gas G20 unless otherwise
stated on the boiler carton and data label.
To ensure correct operation of the gas air control valve a
calibrated electronic flue gas analyser must be used, taking the
measurement directly from the flue sampling test point with the
appliance firstly at high (min 10 minutes) and then minimum
output (for this, see §9.10.1 and §9.10.2). Any adjustments to the
valve must only be corrected at minimum out (see §9.10.3).
IMPORTANT
► Inspection of the gas/air control valve must
be carried out with room sealed casing
opened.
► The measurement must be performed
based on O2 ; in other words, the flue gas
analyser must have an O2 sensor.
► The deviation of the flue gas analyser may
be a maximum of ± 0.3% (based on O2 ).
► Any extreme weather conditions i.e. high
winds can influence the results of the test.
► Any readings that are out of tolerance
during maximum output cannot be
corrected by adjusting the gas valve. The
boiler must be meticulously inspected for
gas quality / type, correct components used
(especially the gas restriction ring and the
fan including venturi).
► When replacing components and/or
converting to another gas type, the
operation of the gas air control valve must
always be checked.
66
9.10 Inspection of the gas air control valve
9.10.1 Measuring the flue gas at maximum output
A. Switch o the boiler (see §8.2.1).
A dash
–– will appear on the right display and the central heating
pressure will be visible on the le display.
B. Remove the room sealed cover of the boiler by loosening the 2x
5mm Allen key screws (1) and then sliding it up and forward (2).
C. Remove the cap of the flue gas sampling test point (3) on the
appliance connector on top of the boiler.
D. Place the sampling probe of the calibrated electronic flue gas
analyser into the flue gas sampling point (3).
IMPORTANT
► Make sure that the flue gas analyser is
calibrated. The start-up procedure of
the flue gas analyser must be completed
before the analyser probe is placed in the
flue gas measurement point.
► The analyser probe must completely seal
o the flue gas measurement point to
provide a reliable measurement.
► The end of the analyser probe must be
located entirely in the flue gases (middle
of the flue gas pipe).
2
E. Switch on the boiler by touching above the power light for 2
seconds.
F. Switch on the boiler to maximum output. To do this, hold the
Service symbol and at the same time tap the Plus symbol
twice until the capital letter HH appears on the right display.
G. Wait until the readout of the flue gas analyser is stable (at
least 10 minutes).
IMPORTANT
► Make sure that the capital letter HH
appears on the right display. This
provides assurance that the boiler is
operating as maximum load.
H. Note the measured CO
CO2(H) = measured maximum output CO2 value
I. Check according to Table 2 whether the measured
maximum output CO2(H) % is between the indicated upper
and lower limits.
(H) value.
2
1
3
Cap
Flue gas
analyser
67
Table 2: Allowed CO
(H) limits at maximum output (open casing)
2
Gas category
Value limits
Natural gas
G20
[%]CO2 [%]
CO
2
Upper limit9.610.8
Lower limit8.69.8
IMPORTANT
► Any readings that are out of tolerance
during maximum output cannot be
corrected by adjusting the gas valve.
The boiler must be meticulously
inspected for gas quality / type, correct
components used (especially the gas
restriction ring and the fan including
venturi).
J. The flue gas performance measurement must also be
checked at minimum output (see §9.10.2).
9.10.2 Measuring the flue gas at minimum output
Before measuring the flue gases at minimum output, the
measurement at maximum output must be completed.
See §9.10.1.
The measured CO2 (H) % at maximum output is
important to determine equilibrium, this must be
completed before checking the minimum output %.
LPG
G31
A. Switch on the boiler at minimum output. To do this, tap
simultaneously the Service symbol and the Minus
symbol until the capital letter LL appears on the right
display.
B. Wait until the readout of the flue gas analyser is stable (at
least 10 minutes).
C. Note the measured CO2(L) value.
CO2(L) = measured minimum output CO2 value
D. Check according to Table 3 whether the measured
minimum output CO2(L) value is between the indicated
upper and lower limits.
E. If the minimum output measurement falls outside the limits
given in Table 3a or 3b, continue at §9.10.3 to adjust the
gas valve. If the setting is correct, continue to Step F.
► The CO
upper limit is the CO2(H) value that
2
was noted during the maximum output
measurement. (See §9.10.1, Step H)
measured value at minimum output falls
within the indicated upper and lower
limits. Adjustment of the gas air control is
not necessary in this case. The setting at
minimum output must be adjusted using
the method described in §9.10.3 if the
measured value is outside the indicated
limits.
Example (Natural gas G20)
► During maximum output a CO2(H) value
of 9.0 % has been measured. In this case
the CO2(L) value at minimum output
must be 8.7 ± 0.1 % (= 0.5x CO2(H) + 4.2)
as stated in the table 4 and 5. When
measuring the gas-air ratio at minimum
output (L) and the value is out of this
range then it must be adjusted, as
described in §9.10.3
F. Reattach the room sealed cover and tighten the 2 screws by
hand.
Check the CO value at minimum output. The maximum
allowed CO measurement value is 160ppm.
G. Switch the boiler to maximum output. To do this, hold
the Service symbol and at the same time tap the Plus
symbol twice until the capital letter HH appears on the
right display. Check the CO value at maximum output. The
maximum allowed CO measurement value is 160ppm.
H. Switch o the boiler.
I. Remove the probe of the flue gas analyser from the flue gas
sampling point and carefully replace the cap on the adapter
above the boiler.
J. Switch on the boiler again.
K. Check the gas integrity of the flue gas sampling point.
L. Carry out a flue integrity test via the air sampling point on
the boiler adaptor.
69
9.10.3 Minimum output correction
Before the minimum output correction is performed, the
maximum output and minimum output measurements must
be completed. The measured CO2(H) value at maximum output
is important for determining the correct value for the setting at
minimum output (see §9.10.1 and §9.10.2).
A. Remove the dust cap of the gas valve so that the adjustment
screw is accessible.
B. Switch on the boiler at minimum output. To do this, tap
simultaneously the Service buttonand the Minus button
until the capital letter LL appears on the right display.
C. Wait until the readout of the flue gas analyser is stable (at
least 3 minutes).
D. Measure the CO2(L) value.
E. Using the adjustment screw B, set the correct CO2(L) value.
For the correct CO2(L) setting value, see Tables 4a or 4b.
F. Reattach the cover screw of the gas valve so that the
adjustment screw is sealed.
G. Check the measurements at both maximum output and
minimum output noted in §9.10.1 and §9.10.2 (start with
Step F in §9.10.1) to ensure the correct flue gas emission
levels are obtained.
► Select the correct table depending on the
applicable gas category:
4a: natural gas (G20)
4b: LPG 3P (G31)
► The maximum output measurement
value is important for a correct
adjustment. This measurement value
was noted during the maximum output
measurement CO2(H) (see §9.10.1, Step
H).
► Turning the adjustment screw to the right
increases CO2.
Turning to the le decreases CO2.
► Turn the adjustment screw with small
steps and wait aer each turn until the
measurement stabilises.
Adjustment screw
Dust cap
Use a T15 Torx drive for the dust cap
removal & oset adjustments
Clockwise to
increase CO
2
Anticlockwise to
decrease CO
2
Table 4a: Checking CO2(L) levels for Natural gas
(open casing)
Natural Gas G20 (20 mbar)
Measured value at
maximum output
(see §9.10.1, Step H)
CO
(H) [%]CO2(L) [%]
2
Setting value minimum
output
(= 0.5 x CO
(H) + 4.2)
2
9.69.0 ± 0.1
9.48.9 ± 0.1
9.28.8 ± 0.1
9.08.7 ± 0.1
8.88.6 ± 0.1
8.68.5 ± 0.1
Table 4b: Checking CO2(L) levels for LPG (open
casing)
LPG G31 (37 mbar)
Measured value at
maximum output
(see §9.10.1, Step H)
CO
(H) [%]CO2(L) [%]
2
Setting value minimum
output
(= CO
(H) - 0.3)
2
10.810.5 ± 0.1
10.610.3 ± 0.1
10.410.1 ± 0.1
10.29.9 ± 0.1
10.09.7 ± 0.1
9.89.5 ± 0.1
Example (when using natural gas G20)
► During maximum output, a CO2(H) level of
9.0% is measured. In this instance a minimum
output CO2 value must be 8.7 ± 0.1%.
70
10 FAULTS
10.1 Fault codes
Viewing fault codes
If the boilers PCB detects a fault, this is indicated by a
flashing service symbol
as F004F004, is illuminated on the le display.
The service symbol remains flashing until the boiler has
reset or where required the faulty component has been
replaced.
Resetting the boiler
The boiler can be reset by touching the flashing Service
button and holding it for 2 seconds. If the fault code
reoccurs an Intergas trained engineer should be requested.
on the display. A fault code, such
Fault code illuminated
Reset
IMPORTANT
► Using the fault code table below to
establish the cause of the issue before
attempting to reset the boiler.
NOTE: A reset is not possible when a
component is outside its tolerance
values.
The following fault codes can be established:
Fault codeDescriptionPossible cause / solution
F000F000
F001F001
F002F002
F003F003
F004F004
F005F005
F006F006
Sensor S0 is defective.► Replace heat exchanger sensor S0.
► Vent the heating system & boiler heat exchanger (see §8.2.1).
► Pump does not operate (check power, impellor, replace pump.
Temperature is too high
during central heating
demand.
Temperature too high
during DHW demand.
Flue gas temperature is
too high.
No flame during start-up.
Flame failure during
normal operation.
Flame simulation.
► Check wiring to the CH flow sensor S1 (ensure its connected and
not damaged).
► Check the CH flow sensor S1 (is located and installed correctly)► Check for the correct operation of CH flow sensor S1.► Replace central heating flow sensor S1.
► Check wiring to the DHW sensor S3 (ensure its connected and not
damaged).
► Check the DHW sensor S3 (is located and installed correctly).► Check for the correct operation of DHW sensor S3.► Replace domestic hot water sensor S3.
► Check heat exchanger for contamination or debris.► Check the flue / chimney for blockages.
► Gas valve is faulty or no power from PCB (24v dc pins 1 & 5).► Gas inlet working pressure below 17mbar (20mbar
recommended).
► Condensation drain is blocked or frozen.► Check ignition module, ignition pin, lead or spark gap.► No power to Ignition unit.► Poor earth to boiler or ionisation pin.
► Condensation drain is blocked or frozen.► Gas inlet working pressure below 17mbar (20 mbar
recommended).
► Check ignition module, ignition pin, lead or spark gap.► Check adjustment of gas valve (See §9.10.1).► Check the flue integrity for possible re-circulation or blockages► Poor earth to boiler or ionisation pin.
► Replace faulty gas valve.► Replace faulty PCB.
2sec
71
Fault codeDescriptionPossible cause / solution
► Check ionisation/ignition pin is clean and correctly located.► Check ionisation/ignition pin wiring is connected not damaged.► Replace ionisation/ignition pin.
► Check fan wiring.► Check and/or replace fan assembly .► Replace PCB.
F007F007
F008F008
No or insuicient
ionisation current.
Incorrect fan speed
detected
F009F009
F010, F011F010, F011
F012F012
f014f014
f015f015
f016f016
F018F018
F019F019
F027F027
f028f028
Internal PCB fault.► Replace PCB.
► Check wiring to heat exchanger sensor S0 (ensure its connected
Heat exchanger Sensor
S0 fault.
Flue gas sensor fault S5.
Heat exchanger sensor
S0 mounting fault.
Heating sensor S1
mounting fault.
DHW sensor S3
mounting fault.
Flue and/or air supply
duct is blocked/restricted.
Boiler memory module
fault.
Short circuit of outdoor
weather compensation
sensor S6.
Reset error.
and not damaged).
► Check heat exchanger sensor S0 resistance values are correct.► Check for the correct location of heat exchanger sensor S0.► Replace heat exchanger sensor S0.
► Check wiring to flue gas sensor S5 (ensure its connected).► Check flue gas sensor S5 resistance values are correct .► Check for the correct location of flue gas sensor S5.► Replace flue gas sensor S5.
► Heat exchanger sensor S0 is not mounted correctly. Attach the
sensor correctly.
► Central heating flow sensor is not mounted correctly. Attach the
sensor correctly.
► Domestic hot water sensor S3 is not mounted correctly. Attach
the sensor correctly.
► Check the flue and the air supply duct including seals or gaskets.► Clean the flue and/or the air supply duct.
► Check BMM wiring or connector for damage.► Replace BMM.
► Check wiring to outdoor sensor and ensure its connected
correctly and not damaged.
► Check the outdoor sensor resistance values are correct.► Replace the outdoor sensor.
► Check the reset button for unintentional operation (e.g. cleaning
of control panel).
► Replace the PCB.
f029f029
F031F031
IMPORTANT
► Any replacement components must be
► Using 3rd party components or installing
Gas valve fault.
CH flowsensor fault S1.
original Intergas parts.
them incorrectly can lead to serious
consequences, with a risk to health,
occupants or buildings.
► Check the gas valve wiring, coil resistances.► Replace the PCB.
► Check wiring of central heating flow sensor for damage and
ensure its connected correctly.
► Ensure the central heating flow sensor resistance values are
correct.
► Check for the correct operation of central heating flow sensor S1.► Replace central heating flow sensor S1.
72
10.2 Other faults
10.2.1 No heat (central heating)
Possible causesAnalysisSolution
The power LED is not illuminated. Yes
The right display shows a line (
The boiler is o.
––).
↓ No
Yes
↓ No
Check the power supply.
Check the fuse; see Electrical schematic §12.1.
Switch on the boiler by touching just above the power LED and
holding this for 2 seconds
Room thermostat / weatherdependent control is not connected
or is defective.
Yes
Check the wiring.
Check OpenTherm, On/O connection of the boiler, or the
connection between the central heating boiler and the
OpenTherm room thermostat. Replace the thermostat.
↓ No
Replace the weather-dependent control.
No electricity (24V). Yes Replace defective programmer. Check the wiring according to
the schematic.
Check Connector X13.
10.2.2 Central heating does not reach the correct temperature
Possible causesAnalysisSolution
System water pressure is too low. Yes
↓ No
Room thermostat is turned down.
Yes
↓ No
Temperature is set too low. Yes
↓ No
Poor or no flow in the system. Yes
↓ No
The boiler output is not correctly set. Yes
Top up the system via the filling loop; see §8.2.1.
Check the setting and adjust it if necessary.
Increase the central heating temperature; see central heating
demand. If an outdoor sensor is present: check the sensor
location or for damage, check curve setting (see §9.7)
Check the t (±20°C) between central heating flow and return.
Ensure no air locks are in system also check pump speed
setting parameter P031, P032.
Adjust the boiler capacity. See §9.5 and §9.6.
↓ No
No heat transfer due to debris within
Yes
the central heating boiler/system.
↓ No
Flue and/or air supply duct is blocked
Yes Check and (if necessary) clean the flue and the air supply duct.
or restricted.
10.2.3 Central heating system remains too warm
Possible causesAnalysisSolution
Room thermostat / weatherdependent control is defective or has
a short circuit.
There is thermo-syphon in the
central heating circuit (Radiators
getting warm when DHW operates
with combination boilers).
Yes
↓ No
Yes
Flush and clean the heating system via the central heating
circuit to BS 7593 and install a return magnetic filter.
Check the wiring or batteries if applicable.
Check OpenTherm, On/O connection of the boiler, or the
connection between the central heating boiler and the RF room
thermostat. Replace the thermostat.
Replace the weather-dependent control.
For thermo-syphon Install a check valve in the CH return
pipework near the boiler. For under floor heating install a
"normally open" zone valve into the flow circuit. (see under
floor wiring diagram on our website).
73
10.2.4 No domestic hot water (DHW)
Possible causesAnalysisSolution
The power LED is not illuminated. Yes
Check the power supply.
Check the fuse; see Electrical schematic §12.1.
↓ No
Flow turbine does not work.
Yes
↓ No
Domestic hot water flow < 2l/min. Yes
↓ No
Domestic hot water sensor S3 is
Yes
Replace the flow turbine.
Increase the domestic hot water flow.
Replace domestic hot water sensor S3.
defective.
↓ No
No electricity on the flow turbine (5V
Yes Check the wiring according to the schematic.
DC).
10.2.5 Domestic hot tap water does not reach the correct temperature
Possible causesAnalysisSolution
Domestic hot water flow is too high. Yes
Reduce the domestic hot water flow.
Setting for domestic hot water
temperature is too low.
Insuicient heat transfer due to
lime scale or contamination
within the DHW water circuit.
The central heating system becomes
warm while operating the domestic
hot water.
Central heating pressure is too low. Yes
The flue is blocked. Yes Check the flue.
10.2.6 Burner ignites loudly
Possible causesAnalysisSolution
Inlet Gas pressure is too high. Yes
Ignition spark gap is incorrect.
Gas-air control is not correctly
adjusted.
The spark is weak. Yes Check the ignition cable is connected to the ignition module
↓ No
Yes
↓ No
Yes
↓ No
Yes
↓ No
↓ No
↓ No
Yes
↓ No
Yes
↓ No
Increase the domestic hot water temperature; see §9.1.2.
De-scale or flush the domestic hot water circuit within the
boiler heat exchanger.
For thermo-syphon Install a check valve in the CH return
pipework near the boiler. For under floor heating install a
"normally open" zone valve into the flow circuit. (see under
floor wiring diagram on our website).
Top up the central heating system via the boiler filling loop until
the pressure is between 1 to 1.5bar.
The Gas meter governor may be defective. In this case, contact
the energy company 0800 111999.
Replace the ignition pin complete with cable.
Check the adjustment; see §9.9 and §9.10.
correctly.
Replace the ignition module mounted within the top cover.
Replace the ignition pin.
Burner is defective Ye s Replace the burner.
74
10.2.7 Burner resonates
Possible causesAnalysisSolution
Gas inlet pressure lower than 20mbar
or sometimes lower.
There is recirculation of flue gases.
Gas-air control is not correctly
adjusted.
Burner seal is defective. →Yes
Burner is defective. →Yes
10.3 Notifications
In addition to error codes, the burner control can also show notifications on the display. Notifications
are displayed if an anomaly occurs somewhere in the system that does not aect the vital functioning
of the system. Notifications disappear if the system can fix the abnormality. Intergas Heating should
be consulted if a notification returns repeatedly.
→Yes
↓ No
→Yes
↓ No
→Yes
↓ No
↓ No
→ The Gas meter governor may be defective. In this case, contact
the energy company 0800 111999.
→Check the flue and air supply ducts and seals.
→Check the adjustment; see §9.9 and §9.10.
→Replace the burner seal.
→Replace the burner.
The following notifications are distinguished:
NotificationDescriptionPossible cause / solution
► Check if parameter P001 is set correctly.► Check wiring of domestic hot water sensor S3 for damage and
N030
N152
N202
N245
DHW demand is blocked.
Power reduction due to flue gas
sensor faulty.
Burner switched o due to flue
gas temperature limitation.
Fan speed adapted to CAC
protection.
ensure its connected correctly.
► Ensure the DHW sensor resistance values are correct.► Check for the correct operation of domestic hot water sensor S3.► Replace domestic hot water sensor S3.
► Check whether flue gas sensor S5 is present and install it if
necessary.
► Check whether it has been mounted correctly.► Check the wiring for break / short circuit.► Replace flue gas sensor S5.
► Flue gas temperature higher as to be expected. Check the fins
of the heat exchanger for wear. Replace the heat exchanger if
necessary.
► Backflow of flue gasses detected. Fan on low speed to prevent
recirculation of flue gasses. Check the flue gas non-return valve.
75
11 MAINTENANCE
The boiler and the system must be inspected annually by an qualified competent gas safe registered engineer.
The boilers heat exchanger should be cleaned and inspected as stated below at each service interval.
CAREFUL
► Aer completion of the Annual service
procedure all 26 (9) safety checks must be
performed and the results recorded within
the service & interim boiler work pages, at
the back of this manual.
► Some components can be very hot during and
just aer operating the appliance.
►For Health & Safety reasons the use of PPE is
recommended during the below procedure.
11.1 Annual service procedure
► Switch o the appliance and isolate the power supply at the fuse
spur, make safe the appliance before continuing (Ref TB118).
► Close the boiler gas isolation valve (test for let-by).► Remove the room sealed cover of the boiler by loosening the two
Allen screws (A) and then liing the panel up and forward (B)
► Wait until the boiler has cooled down. This can be done by
opening a domestic hot water tap (with the power switched o).
1
2
B
A
11.2 Annual service continued (syphon maintenance).
► Detach the syphon cup (1) by rotating it a quarter turn to the
le and then pulling it out downwards.
► Remove the flexible hose (2) from the siphon base and the
sewage connection.
► Empty the syphon cup (3).► Detach the syphon base (3) by pressing the three securing
clips in, while simultaneously pushing the siphon base
downwards (4).
► Remove the circlip and the plastic ball from the syphon base
(5).
► Clean the following components with water:
◉the inside of syphon base ◉plastic ball◉circlip◉syphon cup◉opening of the exhaust manifold
3
4
2
1
1
1
5
76
► Return the plastic ball to the syphon base and attach the
ca. 6 cm
circlip.
► Check that the ball and circlip have been installed correctly
(6). Make sure that the top of the circlip is about 6 cm below
the edge of the syphon base.
► Replace the O-ring (art. no. 086154) at the bottom of the
exhaust manifold.
► Attach the syphon base to the bottom by pushing it high
enough so that the securing clips click over the lip (7).
IMPORTANT
► Make sure that the syphon base is
returned to its original position, firmly
locked into the bottom with no gaps.
Incorrectly attaching the syphon base
(or not attaching it at all) will result in
products of combustion leaking into the
room creating a dangerous situation.
► Make sure that the syphon cup is filled with ¾ water (8) before
placing it back, slide it into the syphon base and rotate it a
quarter turn to the right (clockwise) so that it is correctly
secured (9).
► Slide the ribbed hose onto the syphon base and into the
waste connection.
6
7
–
!
K
C
–
I
C
L
NOTE
► To assist the replacement of the syphon base and syphon cup
silicone lubricant is recommended on the following seals,
◉ Exhaust manifold O-ring seal
◉ Syphon base outer seal
◉ Syphon cup O-ring seal
8
9
10
77
11.3 Annual service continued (internal maintenance)
► Li and rotate the expansion vessel to the le side.► Disconnect the electrical connector to the fan assembly.► Loosen both unions and the electrical connector then remove
the gas valve.
► Unscrew the 6mm Allen key shoulder bolts of the front cover
and remove it forward along with the fan (Being careful not to
damage any components). Lay the removed front cover face
down on to its foot supports, this is best achieved on a flat heat-
proof surface.
► The burner and the integrated insulation panel do not require
cleaning only inspecting. Therefore, never use a brush or
compressed air to clean these components (dust hazard).
COMMENT
► The expansion vessel must be inspected and
tested at each annual service and if required
repressurise to 0.75 bar (cold and with no
system pressure). Ensure the flexible hose is
not kinked, leaking or damaged (Replace if
required).
11.3.1 Annual service continued (cleaning)
► Clean the slats of the heat exchanger from top to bottom with a
brush or Intergas comb (use a vacuum cleaner to remove debris).
► Clean the underside of the heat exchanger.► Only clean the underside of the front panel.
CAREFUL
► The integrated insulation panel and
burner seal contain ceramic fibres use the
appropriate P.P.E dust mask & gloves.
78
11.4 Annual service (re-assemble)
IMPORTANT
► Replace the front plate O-ring at least
every 3 years or if damaged/ discoloured.
Art.no: 877927 — Xtreme 24/30
620274 — Xtreme 36
► Check and replace any other worn gaskets.
Also check they are correctly located.
► Check whether there is a thin layer of ceramic grease
between the flange of the shoulder bolts and the front
panel.
► If there is insuicient grease present, extra must be applied
using the foam application tool (A) within the kit (ceramic
grease kit available to order).
► Check whether the gasket around the front panel is
correctly located. Place the front panel on the heat
exchanger and attach it with the 6mm Allen key shoulder
bolts. Tighten the shoulder bolts (1 to 11)* by hand, working
diagonally. The order of tightening is shown in the diagram.
► Fully tighten the Allen shoulder bolts with a torque wrench
set at 10-12 Nm when available to ensure uniformity.
► Check and tighten the burner bolts diagonally by hand.► Replace the gas valve and when necessary replace the seals► Reinstate the electrical connector to the gas valve and fan.► Open the gas isolation valve and check both of the gas
unions for tightness.
► Check and repair any water leaks within the boiler.► Turn the expansion vessel back to its original position. Make
sure the vessel is secured by the lip on the cable cover.
► Check a 3amp fuse is fitted before re-establishing the
power.
► Switch on the boiler.► Check the front panel, the fan seal, fan connection to the
front panel, also check the flue components for leakage,
repair or replace as required.
► Check the gas/air control (see §9.9 and §9.10) and check
the gas outlet on the gas valve for tightness.
► Refit the room sealed cover and tighten the 5mm Allen bolts
under the boiler. (Do not overtighten)
► Check the domestic hot water facility for correct operation.
A
7
8
9
6
3
2
1
5
11
10
4
* 1 to 9 bolts on 24 & 30Kw models. (Do not overtighten)
Clicking noise (expansion) during operation is normally due
to overtightening of the front panel bolts or lack of ceramic
grease.
Please check suicient ceramic grease has been applied and
the correct torque setting applied before calling the Intrgas
service team.
79
11.5 Annual service checklist
No.Activity
Isolate the boiler from the fused spur and make safe (ref TB118) check
1
the correct 3amp fuse has been fitted.
Carry out inspection of boiler for dust and dirt and clean where
2
necessary.
Visually inspect the front plate and heat exchange for signs of
3
damage. If damage is evident proceed to column 2.
Check the gas inlet pressure on HIGH rate (DHW mode).
4
Check combustion by measuring CO, CO
5
tolerances then proceed to a full service in column 2.
Close the boiler gas isolation valve.
6
Isolate flow and return valves and drain boiler via the drain o on
the return. Check the pressure in the expansion vessel. Recharge if
7
necessary.
Remove the front plate and clean the inside of the heat exchanger.
8
Check the front plate seal, replace the seal if damaged, discoloured,
9
3 years old or later.
Check the burner has not delaminated also check the burner seal.
10
Check the ignition pin for clearance and debris.
11
Check the condensate trap, clean and refill.
12
2
. If the values are outside the
Inspection at
every annual
service
Maintenance
must be carried
out at regularly
Open the isolation valves on flow and return and refill the water in the
13
boiler between 1.2 to 1.5 bar via the filling loop.
Open the gas isolation valve, reconnect the power to the boiler via
14
fused spur.
Check visually the ignition and burner performance.
15
Check the boiler for leaks of any kind (gas, flue gas, water,
16
condensate) rectify if necessary.
2
Recheck the CO,CO
17
Complete the Benchmark Service Record on the back pages of the
18
Installation manual.
and adjust if necessary, adjust CO2 only LOW fire.
Optional (Frost thermostat if OT thermostat on X13)
OpenTherm thermostat (primary connection)
Aan
On/o room thermostat
Uit
Frost thermostat
Outdoor sensor S6 (12k / 25°C)
Hot water cylinder sensor S7
PC Interface
Gas valve
BMM (Boiler Memory Module)
Flue gas sensor S5
Domestic hot water sensor S3
Heat exchanger sensor S0
7 – 15
7 – 9– 17
7 – 8– 17
Central heating flow sensor S1
Flow sensor
Central heating low water pressure sensor
83
12.2 Product Fiche according to CELEX-32013R0811, Appendix IV
Supplier
Type designationSymbolUnit
Intergas Heating Ltd
Unit 2
Easter Park
Worcester Road
Kidderminster
DY11 7AR
Intergas Xclusive
243036
Seasonal energy eiciency class for
room heating
Nominal heat output (capacity)P
Seasonal energy eiciency class for
room heating
Annual energy useQ
Noise levelL
--AAA
rated
HE
WA
s
kW182327
%939393
GJ384858
dB565658
Domestic hot water capacity profile--LXLXL
Energy eiciency class for water
heating
Domestic hot water eiciency
Annual electricity useAECkWh13
Annual fuel useAFC
--AAA
WH
%858687
17
GJ111817
15
IMPORTANT
►Before installation, read the installation manual and the operation instructions.► This appliance is not intended for use by individuals (included children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
supervision of or instruction concerning the use of the appliance is given. Children shall not
play with the appliance. Cleaning and user maintenance shall not be undertaken by children.
► The boiler and system must be inspected annually by an qualified Gas Safe registered
engineer and cleaned if necessary. See §11 for the annual servicing procedure.
► The boiler outer casing must only be cleaned with a damp cloth. Do not use aggressive
scrubbing, agents or solvents.
12.3 NTC resistances
NTC 12 kOhm
T [°C]R [Ω]T [°C]R [Ω]T [°C]R [Ω]T [°C]R [Ω]
-15760201518300455522751994
-10588802014770504609801717
-5459502512000553863851467
036130309805603253901266
528600358055652752951096
1022800406653702337100952
84
13 SPARES SHORT LIST
DescriptionPart number
PCB complete with housing
230V EBM NRG130 Fan assembly (complete with 877807 seal & 2 x 312027 M5 nuts)074304
S0 NTC Temperature sensor (heat exchanger)230034
S1 NTC Temperature sensor (CH Flow) Clip on 18mm230054
Modulating Yonos Wilo CH pump074604
Ignition / Ionisation electrode210024
Pressure sensor (CH) screw in type230044
24V Gas valve Siemens VGU76S074514
240V Ignition module ZAG1210014
S3 Flowswnsor (DHW) clip on 15mm NTC200177
S5 Flue gas temperature sensor NTC074704
DHW Flow turbine074804
DHW HALL sensor (Clip on)900004
Graphite Seal gas valve (inlet) 21.5/15.5mm875757
O-ring gas restriction ring 19x2mm875727
074104
O-ring type front plate seal for 36kW (New type Black Viton replaces 620274) 086474
O-ring type front plate seal for 24 & 30kW (New type Black Viton replaces 877927) 086504
Condensate syphon sediment bowl510054
Condensate syphon complete075044
Pressure relief valve (3bar)600024
Natural Gas G20 restrictor disc kit 392 (24kW)076924
Natural Gas G20 restrictor disc kit 450 (30 &36kW)076934
LPG G31 restrictor disc kit 315 (24Kw)076047
LPG G31 restrictor disc kit 370 (30 & 36kW)076914
85
14 WARRANTY PROVISIONS AND CE DECLARATION
1. The installer must be registered with Gas Safe, installer must
complete the Benchmark Commissioning Checklist in full at
the time the boiler is installed. The Benchmark must be made
available and can be found at the back of the installation
instructions. The Benchmark Commissioning Checklist must
be retained on site by the owner/occupier for inspection during
an engineer's visit.
2. The boiler and Intergas system filter* must both be registered
for warranty with Intergas by either the installer or you the
householder, within 30 days of the boiler being installed.
For the new build properties, this must be done within 30
days of the sale being completed. if these conditions are
not met, the warranty will not be valid.
(*Intergas system filter must be installed on the same date as
the boiler and registered for warranty at the same time).
The product must be registered via the internet at
www.intergasheating.co.uk or on the Intergas MiREG
website www.myintergasregistration.co.uk or by returning
the warranty card.
3. The boiler must be serviced annually by a registered Gas Safe
Engineer in accordance with manufacturer’s instructions.
4. Service details must be recorded in the Benchmark Checklist
or provide proof of service which must be available for
inspection.
5. The cost of the annual service is not included in the warranty.
If the above conditions are not meet this warranty will be
limited to 12 months from the date of installation or date of
Manufacture, as recorded on the Benchmark commissioning
checklist.
IMPORTANT
Warranty terms mentioned above are based
on domestic use only. Any non-domestic
applications will be covered by a 12 months
warranty. Service intervals may need to be
increased depending on commercial usage.
For additional information please contact
Intergas Heating Ltd.
6. Only boiler component failures are covered by the warranty.
The warranty does not cover any connected system or
accessories such as time switches, thermostats, motorised
valves, external pumps and so on.
7. Any repair carried out under the terms of this warranty does
not extend the warranty beyond its original period.
8. If the boiler breaks down, Intergas may ask you* (Homeowner
or Installer) to pay a deposit before we visit to complete the
repair. We will return the deposit in full if we find a fault that is
covered by the warranty. We may keep the deposit if we cannot
access the property at the time we have arranged with you to
visit or we find other conditions of this warranty have not been
met.
9. The system must be flushed and cleansed in accordance with
BS7593:2019.
10. If any failure is caused by contaminated water in the system
the engineer visit becomes chargeable.
11. All installation, non boiler or external system faults calls will be
charged to the home owner/occupier.
12. Roof space installation BS6798:2014 Require a permanently
fixed access ladder must service installations in los or attics.
Adequate lighting and permanently fixed flooring must also be
available.
13. Engineers will not carry out repairs if they think accessing the
boiler would be a risk to Health and Safety. A responsible adult
must be at the property to give our engineer access to the
boiler.
14. If your boiler is in a cupboard, there must be enough room
for the engineer to work (the minimum area as set out in the
installation instructions). We are not responsible for removing
cupboards, kitchen units, trims etc to gain access for repairs.
15.
In hard water areas of 200ppm or above, appropriate protection
actions must be taken in accordance with BS 7593:2019 in
line with building regulations Part L1. (Above 200ppm we
recommend Combimate*, Adey Electroscale or Hydroflow
HS38 should be installed. 300ppm and above we recommend
a Combimate*, Water soener* or HS38 should be installed.)
(*serviceable item)
16. The central heating system must be maintained in accordance
with the Benchmark Guidance on water Treatment in Central
Heating Systems & BS7593:2019, we recommend the use of
Fernox, Sentinel or Adey products, Inhibitors & filters. It is
important that the correct concentration of water treatment
is maintained for the life of the boiler, should we attend a
warranty call Intergas reserve the right to take system water
samples and should they fail the aforementioned requirements
then the warranty will be void and the call will become
chargeable. (Intergas system filter must be installed & registered
at the same time as the boiler for enhanced warranty period).
17. If the boiler suers a breakdown you should contact Intergas
on 01527 888000 selecting option 2. Our normal working hours,
excluding Bank Holidays are:
8.00am – 5.00pm Monday to Friday and
8.00am – 12.00pm Saturday mornings.
Installers are required to carry out installation, commissioning and
servicing work in accordance with the Benchmark Code of Practice which
is available from the Heating and Hotwater Industry Council who manage
and promote the scheme. Visit www.centralheating.co.uk for more
information.
CE DECLARATION
Manufacturer Intergas Heating Limited
Address Unit 2
Easter Park
Worcester Road
Kidderminster
DY11 7AR
hereby declares that CH appliance:
INTERGAS, Type:
► Xclusive 24► Xclusive 30► Xclusive 36
Meets the provisions of the following directives:
► Low Voltage Directive (2014/35/EC)► Gas Appliance Regulation (2016/426/EC)► Directive regarding eiciency requirements for new oil and gas-
burning central heating boilers (92/42/EC)
► EMC Directive (2014/30/EC)► RED Directive (2014/53/EC)*► Ecodesign (2009/125/EG)► Energy labelling (2010/30/EU)
* The conformity declaration can be requested from Intergas.v
S. Zouch, September 2020
86
15 BENCHMARK COMMISSIONING & WARRANTY VALIDATION SERVICE RECORD
Benchmark Commissioning &
Warranty Validation Service Record
It is a requirement that the boiler is installed and commissioned to the manufacturers’
To instigate the boiler warranty the boiler needs to be registered with the
manufacturer within one month of the installation. The warranty rests with the
end-user (consumer), and they should be made aware it is ultimately their
responsibility to register with the manufacturer, within the allotted time period.
It is essential that the boiler is serviced in line with the manufacturers’
recommendations, at least annually. This must be carried out by a competent Gas
Safe registered engineer. The service details should be recorded on the Benchmark
Service and Interim Boiler Work Record and left with the householder. Failure to
comply with the manufacturers’ servicing instructions and requirements will invalidate
the warranty.
www.hhic.co.uk
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturers’ instructions and complete this Benchmark Commissioning Checklist will invalidate the
warranty. This does not affect the customer’s statutory rights.
It is recommended that your boiler and heating system are regularly serviced and maintained, in line with manufacturers’ instructions, and that the appropriate service /
interim work record is completed.
Service provider
When completing a service record (as below), please ensure you have carried out the service as described in the manufacturers’ instructions. Always use the
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
It is recommended that your boiler and heating system are regularly serviced and maintained, in line with manufacturers’ instructions, and that the appropriate service /
interim work record is completed.
Service provider
When completing a service record (as below), please ensure you have carried out the service as described in the manufacturers’ instructions. Always use the
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate
Engineer name:Company name:
Telephone N
Max rate CO ppm CO
Min rate CO ppm CO
undertaken in accordance with manufacturers’
instructions, and readings are correct?”
Gas rate:m
System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593
and boiler manufacturers’ instructions. *
o
:Gas Safe registration No:
3
/hORft3/h
delete as appropriate YesNo
²
²
% CO/CO
% CO/CO
Date:
²
²
yes
yesn/a
Comments:
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component.
Intergas Heating Limited
Unit 2
Easter Park
Worcester Road
Kidderminster
DY11 7AR
Tel: 01527 888000
Fax: 01384 279480
info@intergasheating.co.uk
www.intergasheating.co.uk
2021 Intergas Heating Ltd.
All rights reserved.
The information provided applies to the standard version of the
product. Intergas Heating Ltd can therefore not be held liable for any
damage ensuing from specifications that deviate from the standard
version of the product. Although the available information has been
composed with all possible care, Intergas Heating Ltd cannot be held
liable for any errors in the information or for the consequences of such.
Intergas Heating Ltd cannot be held liable for damage ensuing from
activities that are performed by third parties.
This document is subject to modifications without prior notice.
Smart Opentherm™
84010403
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.