This product complies with ANSIZ21.10.3
(2011) / CSA 4.3 Gas Water Heater. For use as
a potable water heater.
Certified to
NSF/ANSI 372
WARNING
If the information in these instructions is not followed
exactly, a fire or explosion could result causing
property damage, personal injury, or death.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
— Installation and service must be performed by
a qualified installer, service agency, or the gas
supplier.
AVERTISSEMENT
Assurez-vous de bien suivre les instructions données
dans cette notice pour réduire au minimum le
risque d’incendie ou d’explosion ou pour éviter tout
dommage matériel, toute blessure ou la mort.
— Ne pas entreposer ni utiliser d’essence ou
ni d’autres vapeurs ou liquides inflammables
à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ
•
Ne pas tenter d’allumer d’appareil.
•
Ne touchez à aucun interrupteur; ne pas vous
servir des téléphones se trouvant dans
le bâtiment.
•
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions
du fournisseur.
•
Si vous ne pouvez rejoindre le fournisseur,
appelez le service des incendies.
— L’installation et l’entretien doivent être assurés
par un installateur ou un service d’entretien
qualifié ou par le fournisseur de gaz.
To avoid product damage, personal injury, or
even possible death, carefully read, understand,
and follow all the instructions in the Installation
and Operation manuals before installing this
product. Improper installation, adjustment, alteration, or
maintenance can cause injury, loss of life, and/or property
damage. This water heater should be installed and
serviced by a qualified technician. The lack of proper
service can result in a dangerous condition.
This manual contains safety information, installation
instructions, and maintenance procedures. It must be left
with the homeowner or placed near the water heater in
a noncombustible place. The customer should retain this
manual for future reference.
The following items are shipped with the water heater;
Polypropylene to PVC adapters (1), manual (2), flat gaskets (3),
electrode seal (4), set of O-rings (5), and bus fuses (6).
1
5
4
2
6
IH-78a
3
1.3 Contact Information
Call us first if you have any questions about this product. We
can help you with questions about installation or operation,
or if there are damaged or missing parts when you unpack
this unit from the shipping box.
Dealer Contact Information
Due to our policy of continuous product improvement and
technology, the design and/or technical specifications are
subject to change without notice.
1.2 Serial Number Plate Locations
Each heat exchanger module has its own ASME certification
plate located on the heat exchanger itself.
A rating plate below the ASME certification plates has the
serial number for the unit. Please provide this serial number
for service or warranty.
R
XX-XXXXX
Serial Number: ___________________________________
Date of Installation: ___ / ___ / ______
iQ751 - iQ1001 General Information4
2. Safety
2.1 Safety Signal Words
DANGER
Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. This signal
word is limited to the most extreme situations.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury.
NOTICE
Indicates that equipment or property damage can result if
instructions are not followed.
SAFETY
INSTRUCTIONS
Safety instructions (or equivalent) signs indicate specific
safety-related instructions or procedures.
Note: Contains additional information important to a
procedure.
2.2 Installation Warnings
WARNING
DO NOT use this water heater for any purpose other than
water heating.
Read, understand, and follow the Installation and Operation
manuals, including all warnings and precautions, before
operating this water heater. If you do not follow these
instructions exactly, a fire or explosion may result, causing
property damage, personal injury, or loss of life.
Follow all local codes and the most recent edition of the
National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or
the Natural Gas and Propane Installation Code in Canada
(CSA B149.1).
This water heater must be installed by a licensed plumber,
gas fitter, and/or professional service technician. Installation
by unqualified person(s) voids the warranty.
DANGER
A. This water heater does not have a pilot. It is equipped
with an ignition device which automatically lights the
burner. Do not try to light the burner manually.
B. BEFORE OPERATING, smell all around the water heater
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire or
police department.
C. Use only your hand to turn the manual gas shut-off
valve. Never use tools. If manual gas shut-off valve will
not turn by hand, don’t try to repair it. Call a qualified
service technician. Force or attempted repair may
result in a fire or explosion.
WARNING
DO NOT use or store flammable liquids around the water
heater, including gasoline, oils, spray paints, etc.
DO NOT operate this water heater unless it is properly
vented to the outside (the exhaust vent piping must be
connected from the unit directly to the outside). Improper
venting can cause a build-up of carbon monoxide, which
can result in brain damage or death. Exhaust gases must
be completely expelled out of the building.
This water heater is factory preset for NATURAL GAS but
may be field converted for use with propane. For propane
conversion, refer to the Propane (LPG) Conversion section
of this manual. Connecting the water heater to any other
gas supply can result in property damage, serious injury,
or even death.
This water heater is suitable for use in potable water
heating applications. The cold and hot water fittings on
the top of the water heater MUST NOT be connected to any
heating system.
The water heater temperature is factory set to 120°F
(49°C). Hot water temperatures above 125°F can cause
severe burns instantly or death from scalds. If the
proposed water heater outlet temperature is to be set
above 125°F, installation of a thermostatically controlled
(or temperature limiting) mixing valve is recommended for
all hot water going to faucets to avoid the risk of scalding.
Examples include commercial applications where 140°F
(60°C) is often needed or if the space heating temperature
required is higher than the domestic hot water. Always
check the temperature of the hot water before bathing,
showering, washing, etc.
Protect against snow and debris accumulation around the
vent terminations. Regularly inspect the exhaust vent
pipe and the air intake pipe to ensure they remain clear
from obstructions at all times.
5Safety Section
CAUTION
Make sure you know the location of the gas shut-off valve
and how to operate it. Immediately close the gas shut-off
valve if the water heater is subjected to fire, overheating,
flood, physical damage, or any other damaging condition
that might affect the operation of the unit. Have the water
heater checked by a qualified technician before resuming
operation.
If the water quality is known to have high acidity and/or
high hardness, water treatment is recommended. Consult
the local water authority.
SAFETY
INSTRUCTIONS
DO NOT use this appliance if any part has been under
water.
DO NOT reverse the cold water and gas connections as this
will damage the gas valve.
DO NOT overtighten fittings as damage may occur, causing
internal leakage.
The appliance should be located in an area where leakage
within the unit or at its connections will not result in
damage to the surrounding area. The manufacturer will
not be responsible for any damage resulting from leaking
if adequate drainage is not provided.
Safety Section 6
3. Technical Specifications
3.1 Specifications Chart
Specifications
Type
Fuel
Minimum Input (Btu/h)
Maximum Input (Btu/h)
Maximum Output (Btu/h)
Thermal Efficiency94%93%
Turn Down Ratio (TDR)25:133:1
Water Inlet / Outlet Connections
Gas Inlet Connection
Condensate Drain Connection
Maximum Condensate Flow Rate (GPH)5.47.2
Dimensions H X W X D (inches)
Service Clearances
Weight (lbs)525590
Venting Type
Venting Materials (USA)
Venting Materials (Canada)
Vent Size (Diameter)
Max 6” Vent Length - Single Pipe / Power Vent220 ft.*130 ft.*
Max 6” Vent Length - Two pipe / Direct Vent120 ft.*65 ft.*
* Venting Note: From the maximum lengths above, deduct 5 ft. per 90° elbow and 2 ft. per 45° elbow
Ignition
Temperature Range
Temperature Stability
Installation Location Ambient Temperature
Safety
Water Pressure Min / Max (PSIG)
NG/LP- Min. Dynamic Gas Pressure (Full Fire)
NG/LP - Maximum Static Gas Pressure
Gas Pressure for Adjustments
Electrical
Power Consumption
Internal Water Volume (gallons)34
Features and Approvals
4 unit Cascaded High Turn Down 100:1 133:1
Built-In Redundancy
Cascading
Common Venting
Heat exchanger
Applicance Certification to ANSI Z21.10.3
SCAQMD
ASME
Performance GPM
Hot Water Capacity, 45F Rise31.441.6
Hot Water Capacity, 70F Rise20.226.7
Hot Water Capacity, 90F Rise15.720.8
Hot Water Capacity, 100F Rise14.118.7
Hot Water Capacity, 140F Rise10.113.4
Warranty
Note: Due to Intellihot's Policy of continuous product improvements, design and
technical specifications are subject to change without notice
Direct Vent (2 pipe - intake & exhaust), Power vent (1 pipe - exhaust only)
System with no storage tank and without mixing valve
SHOWERS FOR ILLUSTRATION PURPOSES ONLY
MAIN COLD WATER SHUT OFF
N/O - TANKLESS DESIGN
MAIN GAS SHUT OFF
RECIRCULATION
LINE SHUT OFF
1-1/4”
BUILDING RECIRCULATION PUMP
W/ ISOLATION VALVE AND CHECK VALVE
SHOWERS FOR ILLUSTRATION PURPOSES ONLY
MIXING
VALVE
HOT OUTLET SHUT OFF
COLD SUPPLY TO INTELLIHOT
2”
2”
1-1/4”
2”
2”
HOT SUPPLY
1-1/4”
2”
2”
Multiple unit system with mixing valve but no storage tank.
iQ751 - iQ1001 Technical Data 12
SHOWERS FOR ILLUSTRATION PURPOSES ONLY
BUILDING RECIRCULATION PUMP
W/ ISOLATION VALVE AND CHECK VALVE
MAIN COLD WATER SHUT OFF
V1 - N/O - TANKLESS DESIGN
TANK RECHARGE PUMP
W/ ISO VALVES
CHECK VALVE
V2 - N/C - FULL FLOW DESIGN
EXPANSION
TANK W/
SHUT OFF VALVE
MAIN GAS SHUT OFF
1-1/4”
2”
2”
Multiple unit system with mixing valve and storage tank.
1-1/4”
MIXING
VALVE
COLD SUPPLY TO TANK/TANK RECHARGE LINE
COLD SUPPLY TO INTELLIHOT
2”
TANK ISOLATION
VALVES
UNIONS
TANK BY-PASS N/C
TANK OUTLET
SHUT OFF
RECIRCULATION
LINE SHUT OFF
HOT SUPPLY TO TANK
2”
2”
1-1/4”
2”
2”
1-1/4”
2”
13 iQ751 - iQ1001 Technical Data
4.Preparation Before Installation
4.1 Selecting an Installation Site
Note: When installing the water heater, follow all local
building codes and the current edition of the National
Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA, or
National Gas and Propane Installation Code (CAN/CGA
B149.1) in Canada when installing this product.
Note: For water heater installations in Massachusetts, the
unit must be installed by a plumber or gas-fitter
licensed within the Commonwealth of Massachusetts.
Refer to the Requirements for the State of
Massachusetts section in this manual for additional
information.
1. Select an interior location for the installation. Each
installation is unique; therefore, take the time to find the
best location for the water heater.
a. Install the water heater near locations that use hot
water, such as bathroom, kitchen, or laundry room
faucets.
b. Select a location that minimizes the length of the water
pipe.
c. If the distances are long or if the faucet or appliance
requires “instant” hot water, we recommend running
a recirculation line back to the water heater from the
farthest fixture.
d. Insulate the hot water supply and recirculation lines.
e. Select a location away from foot traffic and away from
areas where dust, debris, chemical agents, or other
combustible materials could accumulate.
f. Allow sufficient space for service and maintenance
access to all gas, water, and drain connections.
g. Make sure the location meets all building code
requirements.
2. Minimize the distance that the exhaust gas vent and fresh
air intake must travel to an exterior wall.
a. The exhaust vent outlet must not be located next
to a walkway, near soffit vents, crawl space vents,
or other areas where condensate (water vapor)
could cause damage or create a hazard. Refer to the
Venting Clearance Speci cations section for additional
information.
b. The fresh air inlet vent must be located at least 12”
from the exhaust vent.
c. Contaminated or dirty air drawn into the intake pipe
can damage the water heater. The warranty does not
cover damage caused by airborne contaminants.
3. Locate the unit close to a drain and near gas and water
connections.
The water heater produces a significant amount of
condensate during normal operation and should be
located near a suitable drain where damage from a
possible leak will be minimal. Installing the water heater
in a location without a drain will void the warranty
and the manufacturer will not be responsible for any
resulting water damages that may occur. For additional
information, refer to the Condensate Line Installation
section.
4. Locate the water heater and all the water pipes in an area
where the ambient temperature always remains above
freezing.
a. When the water heater is connected to an electrical
power supply, it will automatically prevent the water
from freezing inside the unit.
b. The unit’s freeze protection system will not prevent the
water in surrounding pipes from freezing.
NOTICE
In cold climates, if there is a power failure, the unit’s freeze
protection system will not operate and can result in water freezing
inside the heat exchanger. To prevent damage to the water
heater, turn OFF the gas supply and inlet water valve. Completely
drain the unit. Damage caused by freezing water is not covered
by the warranty.
5. Select an appropriate location for the combustion air and
exhaust pipes to exit the building, as shown in the Venting
Clearance Speci cations section in this manual.
iQ751 - iQ1001 Preparation Before Installation 14
5. Gas Connection
5.1 Gas Pressure Requirements
iQ series models are designed to operate at gas pressures as
low as 2.5” WC (at maximum firing rate). Gas inlet pressures
to each unit should not exceed 14” WC under any condition
(when unit is firing or not firing).
5.2 Gas Pressure Regulator
Depending on the gas inlet pressure at your facility, it may
be necessary to install a gas pressure regulator to lower gas
pressures to an acceptable level. Please ensure that the
gas pressure regulator has the same or higher minimum to
maximum modulation range as the iQ model it is connected
to. For example, a gas pressure regulator connected to
an iQ1001 should have a modulation range of 30,000
BTU/h to 1,001,000 BTU/h. In the case of multiple units it is
recommended to use a dedicated gas pressure regulator for
each unit.
5.3 Connection Recommendations
WARNING
FIRE AND/OR EXPLOSION HAZARD
To avoid serious injury or even death, the gas line
installation and the gas line inlet pressure test must be
done by a licensed professional.
Always match the water heater with the type of gas
supplied to the unit (natural gas or LP gas). The water
heater is factory preset for natural gas.
Make sure the gas line pressures are within normal
limits. Pressures outside normal limits can result in poor
performance and hazardous operating conditions.
1. Determine if the water heater will use natural gas (factory
preset) or LP (propane) gas.
a. To convert the unit to propane, refer to the Propane
(LPG) Conversion section in this manual.
b. Make sure your gas supply matches the rating decal
located on the side of the water heater.
2. Make sure the gas pressure meets the requirements for
the unit, as shown in the tables.
Parameters
NG/LP- Minimum Static
Gas Pressure
NG/LP - Maximum Static
Gas Pressure
Gas Pressure for
Adjustments
2.5” (non-corrugated, black iron)
14”
8” for NG, 11” for LP
3. Select the proper gas piping.
a. All gas piping and components must comply with
NFPA local codes, and utility requirements minimum.
Only gas approved fittings, valves, or pipe should be
utilized.
b. Standard industry practice for gas piping is Schedule
40 iron pipe and fittings. All high and low gas pressure
piping systems must comply with local utility and
building codes.
c. Assembled piping should be clean of all scale, debris,
metal particles, or foreign material.
d. The piping must be supported from the floor, ceiling,
or walls and by the water heater itself.
4. Make sure the supply line (diameter) is correctly sized for
the maximum output of the water heater(s) being installed.
The water heater should be the first appliance to be
connected to the gas supply line.
a. Determine the gas requirement of the water heater(s)
and other appliances requiring gas. The supply line
must be sized according to the COMBINED total
maximum BTUH volume for all the appliances as if they
were all operating at the same time.
Header Sizing for Multiple iQ Units
Number of
Heaters
Sch 40 Iron
Pipe
1234
2”2”3”3”
b. Gas pipe sizing, for either a single or multiple unit
installation, must be sized for a maximum pressure
drop of 0.3” W.C., from the source to the final water
heater.
c. The maximum gas flow rate required is the sum of
the maximum inputs of each unit divided by the heat
of combustion of the fuel supplied at the location,
(approximately 1,030 BTU per cubic foot for natural gas
or 2,520 BTU per cubic foot for propane).
d. The fuel supplier or utility should be consulted to
confirm that sufficient volume and normal pressure is
provided to the building at the discharge side of the
gas meter or supply pipe.
15 iQ751 - iQ1001 Gas Connection
5.Make sure the supply line (length) is correctly sized.
a. Measure the length of the gas supply line from the gas
meter to the water heater or other appliances requiring
gas. The diameter of the pipe must be in relation to
the length.
b. The total length of gas piping, as well as fitting pressure
drop, must be considered when sizing the gas piping.
Total equivalent length should be calculated from the
meter or source location to the last heater connected.
c. Gas pipe size should be selected on the total
equivalent length. The gas volume for cfh flow will be
the input divided by the calorific value of the fuel to be
supplied.
d. Use the Gas Pipe Sizing tables in this manual or refer
to the gas line manufacturers sizing information to
determine the correct diameter for the supply pipe.
e. The diameter of the gas lines, shown in the illustration,
will vary according to the specific installation
requirements.
6.Install a drip leg on the gas piping.
c. The bottom of the gas drip leg should be removable
without disassembling any gas piping.
d. The weight of the gas pipe should not be supported
from the bottom of the drip leg or to support any of
the gas piping.
5.4 Connecting the Gas Line
Main Supply
Line
Manual
Shut-off
Valve
Drip Leg
Drip Leg
a. Drip legs are typically required at the gas supply of
each heater to prevent any dirt, condensation, or debris
from entering the gas inlet.
b. When multiple heaters are installed, some utilities and
local codes require a full size drip leg on the main gas
supply line in addition to the drip leg at each unit.
To Unit
Manual
Main Supply
Manual
Shut-off
Valve
Drip Leg
Manual
Shut-off
Valve
Drip Leg
Shut-off
Valve
Line
Drip Leg
Manual
Shut-off
Valve
Note: Always clean the inside of the gas line of any dirt or
debris before connecting the piping to the unit.
1. Install a 4-5/8” OD flanged steel coupling and gasket with
a short piece of 1-1/4” NPT black pipe.
To Unit
iQ751 - iQ1001 Gas Connection 16
2. Following local building codes, install a manual shut-off
valve.
Manual Shut-off Valve
3. Using a tee fitting, install a drip leg and continue the
piping to the gas supply connection.
5.5 Venting of Gas Supply Regulators
Below are the general guidelines for venting a gas regulator.
The manufacturer recommends these guidelines be followed
to ensure reliable and proper operation of the water heater.
Local codes and the gas regulator manufacturer should also
be consulted for additional installation information.
1. When venting the gas supply regulator, the vent pipe
must be at least the same size as the regulator vent.
2. When multiple units are connected, each regulator must
have a separate vent line.
3. Vent lines must not be connected together or connected
with any other appliance requiring external venting.
4. When selecting the size, the pipe diameter must be
increased by one size for every 20 feet of pipe.
5. Each 90° elbow is equivalent to approximately:
4.5 feet for nominal pipe sizes of up to 1-1/2”
10.5 feet for nominal pipe sizes of up to 4”
6. Each 45° elbow is equivalent to approximately:
2 feet for nominal pipe sizes of up to 1-1/2”
5 feet for nominal pipe sizes of up to 4”
Tee Fitting
Drip Leg
4. All the gas pipe connections should be tested as
prescribed in NFPA 54. In multiple water heater
applications, each unit should be isolated before testing
any piping system over the allowable pressure. DO NOT
EXCEED 14.0” W.C. on the inlet side of the water heater at
any time.
NOTICE
Do not fire (operate) the water heater until all connections have
been completed and the heat exchanger is filled with water.
17 iQ751 - iQ1001 Gas Connection
5.6 Gas Pipe Sizing Tables
This information is for reference only. Refer to gas pipe manufacturer specifications for actual delivery capacity. Contact the
local gas supplier for actual BTU/ft3 rating. This data copied from the National Fire Protection Association Article 54 (NFPA 54).
Pipe Sizes and BTU/h Capacity (Natural Gas). Use this table for static gas pressure less than 5”
Note: For 1/2” line BTU/h capacities are based on specific gravity of 0.6, pressure drop of 4.6” WC and 5.0” WC. For all other line sizes, capacities are based on
specific gravity of 0.6, pressure drop of 3.0” WC
1/2"3⁄4"1"1-1/4"1-1/2"2"2-1/2"3"4"
iQ751 - iQ1001 Gas Connection 18
Pipe sizes and BTU/h capacity (Propane). Use this table for static gas pressure greater than 5”
Note: The line BTU/h capacities are based on specific gravity of 1.5, pressure drop of 0.5” WC.
1/2"3⁄4"1"1-1/4"1-1/2"2"2-1/2"3"4"
5.7 Gas Pressure Regulator
Depending on the gas inlet pressure at your location, it may
be necessary to install a gas pressure regulator to lower gas
pressures to an acceptable level. Please ensure that the
gas pressure regulator has the same or higher minimum
to maximum modulation range as the water heater
model it is connected to. In the case of multiple units, it is
recommended to use a dedicated gas pressure regulator for
each unit.
Regulators should be mounted with a minimum of 12” of
straight length pipe on either side.
5.8 Venting of Gas Supply Regulators
Below are the general guidelines for venting a gas regulator.
The manufacturer recommends these guidelines be followed
to ensure reliable and proper operation of the water heater.
Local codes and the gas regulator manufacturer should also
be consulted for additional installation information.
1. When venting the gas supply regulator, the vent pipe
must be at least the same size as the regulator vent.
2. When multiple units are connected, each regulator must
have a separate vent line.
3. Vent lines must not be connected together or connected
with any other appliance requiring external venting.
4. When selecting the size, the pipe diameter must be
increased by one size for every 20 feet of pipe.
5. Each 90° elbow is equivalent to approximately:
4.5 feet for nominal pipe sizes of up to 1-1/2”
10.5 feet for nominal pipe sizes of up to 4”
6. Each 45° elbow is equivalent to approximately:
2 feet for nominal pipe sizes of up to 1-1/2”
5 feet for nominal pipe sizes of up to 4”
19 iQ751 - iQ1001 Gas Connection
6. Venting and Materials
WARNING
Improper venting of the water heater can result in excessive
levels of carbon monoxide, which can lead to severe
personal injury or death. This water heater must be vented
in accordance with the “Venting of Equipment “section of
the latest edition of the ANSI Z223.1 / NFPA 54 (Natural
Fuel Gas Code) in the USA, or in Canada refer to the
“Venting Systems and Air Supply for Appliances” section
in the latest version of CAN/CGA B149.1 (Natural Gas and
Propane Installation Code), and all applicable local
building codes. Vent installation should be performed
only by a licensed professional.
6.1 Venting Guidelines
•This water heater must be properly vented to ensure
there is a constant supply of clean intake air, and the
exhaust is properly evacuated from the building. All seal
connections should be airtight.
•The unit should be located as close to the vent
termination, and the vents kept as short and straight as
possible.
•Do not connect the water heater vent to a vent of any
other non-water heater appliance.
•Combustion air may be drawn from the room where the
unit is installed (single pipe/power vent) or directly from
the outside (two pipe/direct vent).
•Ensure a sufficient supply of clean combustion air, free
of any contaminants, such as dust, chemical fumes
(i.e. aerosols, chlorine, paint), grass, or other airborne
contaminants. If necessary, purchase and install the
appropriate air screens, and follow a regular cleaning
program to ensure an adequate supply of clean
combustion air.
•Do not operate the unit in an area that is or will be under
construction or renovation.
•The warranty does not cover damage caused by
contaminants in the installation area. If you must install
the water heater in an area with contaminated air, use
direct venting to supply the air from the outside of the
building.
•All horizontal runs should be sloped upwards towards
the vent termination at a rate of 1/4” per foot.
•To avoid moisture and frost build-up to openings on
adjacent homes, use 45° elbows, 90° elbows, or tees for
the vent termination to direct the exhaust fumes away
from the building.
6.2 Exhaust Vent Materials
The materials listed in the table below outline the acceptable
exhaust vent materials:
United States Exhaust Vent Pipe Standards
MaterialDescription*
Exhaust
Vent Pipe
Canadian Exhaust Vent Pipe Standards
MaterialDescription (approved to ULC-S636)**
Exhaust
Vent Pipe
*Note: Do not use cellular foam core pipe for the exhaust.
**Note: The components (pipe, fittings, primers, and glues) must be from a
single manufacturer; do not interchange. Follow the vent manufacturer’s
certified instructions.
Type BH Special Gas Vent Class IIA (PVC)
Type BH Special Gas Vent Class IIB (CPVC)
Type BH Special Gas Vent Class IIC (Polypropylene)
PVC Schedule 40
CPVC Schedule 40, 80
Approved Polypropylene
This water heater has a built-in exhaust vent temperature
control that limits the exhaust temperature to a maximum of
149°F (65°C).
If the temperature approaches the upper limit, the burner
will turn off automatically to protect the vent pipe. As a
result, this water heater can be vented with PVC pipe. Once
the exhaust temperature has dropped to a normal operating
level, the unit will automatically restart.
If the inlet/return water temperature will exceed 150°F
(66°C), do not use PVC venting. Refer to the Programming
section for Flue Type Selection (PVC or CPVC) for additional
information.
Both the iQ751 and the iQ1001 come factory installed with
6 inch polypropylene (PP) venting. A polypropylene to PVC
adapter is included with each unit to enable the use of PVC
exhaust vent. The maximum allowable venting distances are
the same regardless of vent material selected.
6.3 Air Intake Vent Materials
The air intake vent can be of any plastic or metal vent
material available. ABS, PVC, Polypropylene, galvanized steel,
and flexible corrugated ducting are all examples. If you are
using a corrugated material, ensure there is no inadvertent
crimping or blockage to the air intake pipe.
iQ751 - iQ1001 Venting and Materials 20
6.4 Combustion Air Requirements
The iQ water heaters have the following combustion air
volume requirements per heater:
ModelRequired CFM
iQ751135
iQ1001180
Do not operate the unit in an area that will draw in outside air
contaminated with high levels of dust, sawdust, aerosols such
as paint, or other airborne contaminants.
If necessary, purchase and install appropriate air screens and
follow a regular cleaning program to ensure an adequate
supply of clean, outside combustion air.
6.5 Venting Configurations
Water heaters may be installed with:
two pipes (direct vent) configuration or with
one pipe (power vent) configuration.
6.6 Two Pipe Vent System (Direct Vent)
The water heater can be direct vented without any
modification using a 6 inch diameter pipe.
The following diagrams represent some typical direct venting
configurations and are included to assist in designing the
vent system. Possible configurations are not limited to the
following diagrams.
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
21 iQ751 - iQ1001 Venting and Materials
6.6.1 Single Pipe Venting System (Power Vent)
When using the single exhaust pipe/power vent method, the
following table outlines the required opening sizes for the
combustion and ventilation air coming into the room:
Required Combustion & Ventilation Air Opening Sizes (sq. in) Per Heater Per Boiler Room:
Air is drawn directly from outside into the mechanical room
ModelInputAir Type
iQ751751,000
iQ10011,001,000
*Where two openings are used, one must be within 12 inches of the floor and the other opening must be within 12 inches of the ceiling of the mechanical
room.
**Where one opening is required, it must be located within 12 inches of the ceiling. See figures below.
Combustion Air188
Ventilation Air188375750
Combustion Air250
Ventilation Air2505001000
through two
openings*, direct
or vertical
through one
opening**
250
333
through two
horizontal
ducts***
375750
5001000
Air is drawn from
another interior
space inside the
building
MAKE
UP AIR
Combustion Air Direct from Outside
2 Direct Openings or through Vertical Duct
1 sq. in. per 4000 btu/h
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
Combustion Air Through Ducts
2 Openings through Horizontal Duct
1 sq. in. per 2000 btu/h
MAKE
UP AIR
Combustion Air Direct from Outside
1 Direct Opening
1 sq. in. per 3000 btu/h
MAKE
UP AIR
MAKE
UP AIR
Combustion Air from Interior Space
2 Direct Openings or through Vertical Duct
1 sq. in. per 1000 btu/h
iQ751 - iQ1001 Venting and Materials 22
The following illustrations represent some typical power
venting configurations and are included to assist in designing
the vent system. Possible configurations are not limited to
these designs.
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
23 iQ751 - iQ1001 Venting and Materials
6.7 Venting Termination
6.7.1 Side Wall Termination
1. Terminate the air intake with a 90° elbow (angled down).
Use a flange and PVC screen (not supplied).
2. Terminate the exhaust on the exterior wall at least 12”
above ground and at least 12” away from the air intake, or
as required by local building codes. In areas of high snow
fall, protect the vent terminations from blockage. Use a
flange and PVC guard.
6.7.2 Roof Termination
Venting the unit through the roof is also an option. With this
installation method, the terminations must extend at least 12”
over maximum potential snow levels, or as required by local
building codes. In areas of high snow fall, protect the vent
terminations from blockage.
Terminate the air intake with a 90° elbow (angled down). A
suitable roof flashing and vent cap (not supplied) should be
installed.
Exhaust
IQ-020
Single unit.
12”
See
Note A
Intake Air
IQ-021
Single unit.
Exhaust
12” USA or
18” Canada
over maximum
snow level or
as required by
local code
3’ Minimum
Exhaust
12” Minimum
12” USA or
18” Canada
over maximum
snow level or as
required by local
code
Intake Air
Exhaust
Intake Air
IQ-020a
Multiple units.
Note A: The distance between any exhaust outlet and air
intake should be between 18 and 36 inches or
greater than 72 inches.
iQ751 - iQ1001 Venting and Materials 24
See
Note A
Intake Air
IQ-021a
Multiple units.
Note A: The distance between any exhaust outlet and air
intake should be between 18 and 36 inches or
greater than 72 inches.
If desired, an optional concentric venting system, which uses
one 5” opening through an exterior wall or roof, can be used,
as opposed to cutting two 3” openings.
Follow all installation instructions included with the
concentric vent kit when installing this type of vent system.
Intake
Air
1”
Exhaust
12” above
anticipated
snow level
Highest
or grade.
Exhaust
Intake Air
IQ-022
Concentric Venting System Through a Side Wall.
Exhaust
6.7.4 Concentric Venting Termination (Multiple
Units
In order to conform to some national codes, when two or
more water heaters are installed they must be individually
vented. When two or more units are vented near each other,
each vent termination must be installed, as shown, to avoid
recirculation of flue gases. A minimum distance of 18 inches
must be maintained between each vent termination.
Follow all installation instructions included with the
concentric vent kit when installing this type of vent system.
IQ-083
COMBUSTION AIR
1” MAXIMUM (TYP)
VENT
VENT
Intake Air
IQ-023
Exhaust
Concentric Venting System Through the Roof.
12” USA or 18” Canada
Over maximum snow
level or as required by
local code
Intake Air
12” MINUMUM
12” MINUMUM
TO MAXIMUM
TO MAXIMUM
EXPECTED
EXPECTED
SNOW LEVEL
SNOW LEVEL
See
Note A
Multiple concentric units.
Note A: The distance between any exhaust outlet and air
intake should be between 18 and 36 inches or
greater than 72 inches.
25 iQ751 - iQ1001 Venting and Materials
6.8 Venting Clearance Specifications
Utility
Equipment
Electric, Gas, etc.
Vent
Vent
Do not locate the
inlet or exhaust over
pubic walkways or
over areas where
condensate or
vapors could create
Vent
Vent
a hazard.
A
A
Vent
A
B
A
ItemDescription
AClearances above grade, veranda, porch, deck, or balcony1 foot1 foot
BClearances to window or door that may be opened1 foot**3 feet
CClearances to permanently closed window**
DVertical clearance to a ventilated soffit, eves, or overhang**
EClearances to unventilated soffit, eves, or overhang**
FClearances to outside corner**
GClearances to inside corner**
HClearances to each side of centerline extended from meter/regulator*3 feet within a height
IClearances to gas meter regulator vent outlet*3 feet
JClearances to non-mechanical air supply inlet or combustion air inlet to any other appliance1 foot**3 feet
KClearances to mechanical air supply inlet 3 feet above if within
LClearances to above paved sidewalk or paved driveway on public property*7 feet
MClearances under veranda, porch, deck, or balcony*1 foot
*Per local/gas supplier codes. Use clearances in accordance with local building codes and local gas supplier.
** For single vent pipe/direct 4 feet (1.2 m) below or to the side of opening and 1 foot above opening.
1
In accordance with Z223.1
2
In accordance with CSA B149.1
A
Venting Clearance Specifications
Clearance Distance
USA1Canada2
15 feet above meter/
regulator assembly
6 feet
10 feet horizontally
iQ751 - iQ1001 Venting and Materials 26
6.9 Common Venting for Multiple Units
Connecting multiple units together requires proper sizing of
the intake and exhaust pipes. Up to four water heaters can
be connected (cascading) together.
6.9.1 Vent Diameter Sizing and Lengths
The iQ751 and iQ1001 come factory installed with 6 inch
polypropylene (PP) venting. The following chart outlines the
maximum length of venting allowable for each model. A
vent system’s length is calculated by adding the length of all
straight pieces used (both horizontal and vertical) and then
adding the equivalent lengths of each fitting used in the
system. A vent system’s length shall not exceed the maximum
length outlined in the chart below:
Maximum Vent Length (in ft.) for Various Venting Designs for iQ751 and iQ1001
Number
of Units
1
2
3
4
PV = Power Vent
DV = Direct Vent
Venting
Type
1 pipe - PV220130500500
2 pipe - DV11065250250
1 pipe - PV36252150500440
2 pipe - DV1812775250220
1 pipe - PV12070360212500500
2 pipe - DV6035180110250250
1 pipe - PV7042212124500124
2 pipe - DV35211066225062
6”8”10”12”
iQ751iQ1001iQ751iQ1001iQ751iQ1001iQ751iQ1001
Note: Reduce the maximum equivalent length above by 5 feet per 90° elbow used and by
2 feet per
45° elbow used. Do not exceed the above set limits.
Duct Size and Model
27 iQ751 - iQ1001 Venting and Materials
6.9.2 Recommended Exhaust Pipe Transitions
45°
Do not direct gas exhaust from opposite directions. Use a 45 degree
transition, as shown.
3X DIA. MIN
1/4” Rise Per
Foot Run
Condensate
1/4” Rise Per
Foot Run
Drain
Condensate
Drain
Do not transition into a reducer or use a t- tting. Transitions should
always be directed into a straight run of pipe.
Do not use 90 degree transition into a reducer or a straight pipe.
Do not use reducers in a straight run of pipe.
iQ751 - iQ1001 Venting and Materials 28
6.9.3 Two Pipe Vent System (Direct Vent)
The water heater can be direct vented without any
modification using a 6 inch diameter pipe when installing
single units. When more than one unit is installed, refer to
“Vent Diameter Sizing and Lengths” on page 27.
The following diagrams represent some typical direct venting
configurations and are included to assist in designing the
vent system. Possible configurations are not limited to the
following diagrams.
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
29 iQ751 - iQ1001 Venting and Materials
6.9.4 Single Pipe Venting System (Power Vent)
When using the single exhaust pipe/power vent method, the
following table outlines the required opening sizes for the
combustion and ventilation air coming into the room: When
installing multiple units, refer to “Vent Diameter Sizing and
Lengths” on page 27.
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
MAKE
UP AIR
DECOMMISSIONED
AIR INTAKE AND EXHAUST
iQ751 - iQ1001 Venting and Materials 30
6.10 Combustion (Fresh) Air Inlet Exhaust Outlet
Connections
6.10.1 Recommendations
SAFETY
INSTRUCTIONS
For information on combustion air, either from inside the
building or from the outside, refer to the Venting section
in this manual.
Select an approved material for the combustion air inlet.
Refer to the table below for a list of approved materials. Also
select the appropriate diameter of pipe based on length and
number of units being installed, as shown in the tables in the
Technical Specifications section.
United States Vent Pipe Standards
MaterialDescription
PVC Schedule 40
Vent Pipe
CPVC Schedule 80
Approved Polypropylene
6.10.2 Installation Instructions
1. Install the desired configuration of pipe for the
combustion air inlet.
A power vent system is shown with a short length of intake pipe.
Canadian Vent Pipe Standards
MaterialDescription
Type BH Special Gas Vent Class IIA (PVC)
Vent Pipe
Type BH Special Gas Vent Class IIB (CPVC)
Type BH Special Gas Vent Class IIC (Polypropylene)
NOTE: Consult the following chart or the most recent edition
of ANSI Z223.1/NFPA 54 or CAN/CGA B149.1, as well as all
applicable local codes and regulations when selecting vent
pipe materials.
For installation in Canada, installer-supplied plastic vent
piping must comply with CAN/CGA B149.1 and be certified
to the Standard For Type BH Gas Venting Systems, ULC-S636.
Components of this listed system must not be interchanged
with other vent systems or unlisted pipes or fittings. All plastic
components and specified primers and glues must be from a
single system manufacturer and must not be intermixed with
another system manufacturer’s products.
SAFETY
INSTRUCTIONS
Do not use cellular foam core pipe to vent exhaust gases.
IMPORTANT
On multiple unit installations, the piping from the water heater
must be connected into the properly-sized piping. Use the table
in the Specification section to determine the diameter of the
common connecting piping between each individual water
heater.
NOTE: If PVC pipe is being used, the polypropylene-to-PVC
adapters must be installed.
IH-38
2. Continue the routing of the combustion air inlet.
a. For termination of the pipe to the outside, continue
installing the required pipe to a suitable outside
location. Glue all connections, making sure the joints
are sealed airtight.
b. To configure the unit for power vent, insert a 3’ section
of 6” pipe.
31 iQ751 - iQ1001 Venting and Materials
3. Continue the routing of the exhaust gas outlet to a
suitable outside location.
a. Glue all connections, making sure the joints are sealed
airtight.
b. Install all horizontal exhaust gas vents with a minimum
2 degree (1/4” per foot) slope back toward the water
heater. This allows any condensate that accumulates in
the exhaust outlet to properly drain back into the unit.
4. Install suitable pipe support hangers every 4 to 5 feet, or
as local building codes require.
SAFETY
INSTRUCTIONS
Do not connect any other appliance vents to the water
heater inlet or outlet pipes.
IH-39
WARNING
When the unit is set for CPVC (polypropylene pipe), flue
temperatures can reach 190°F (88°C). PVC pipe will melt
at temperatures above 149°F (65°C) and could therefore
result in a fire. Make sure the setting and the type of
material being used for the flue are compatible.
5. If multiple units are installed, make sure the diameter of
the connecting exhaust outlet is properly sized for the
number of units being installed.
CAUTION
This water heater has a built-in control to limit the
exhaust temperature to 149°F (65°C) when the PVC is
selected in the “Flue Type” programming section. As
a result, the water heater can be vented with Schedule
40 PVC. If the incoming (or recirculation return) water
temperature does not exceed 150°F (66°C), the exhaust
temperature will not exceed 149°F (65°C).
However, if you set the water heater at a temperature
above 150°F (66°C) and you are also incorporating either
an external recirculation loop or a combination heating
system, the exhaust temperature can exceed 149°F (65°C).
In that case, you must use Schedule 80 CPVC or Approved
Polypropylene in the USA or Type BH Special Gas Vent
Class IIB (CPCV) or Class IC (Polypropylene) that conforms
to ULC-S636 in Canada.
iQ751 - iQ1001 Venting and Materials 32
7. Water Connections
7.1 Water Line Connection Guidelines
Note: Ensure the water flow rate does not change faster than
1 GPM every 5 seconds. Flow rate changes faster than
this cause the unit to malfunction and result in a (E7
Error) code.
When making the water-side connections, please follow these
guidelines:
• Since each installation is different, it is up to the installer to
route the water lines in the most efficient manner.
• Keep the hot water pipes as short as possible to deliver hot
water to the fixtures quickly.
• Only materials (pipes, fittings, valves, solder, etc.) that are
approved for use in potable water systems should be used.
• When tightening any fittings to the connections on the
water heater, care should be exercised not to overtighten
these joints and damage the unit.
• Unions and manual shut-off valves on the cold water inlet
and hot water outlet are recommended.
• Isolation valve kits can be used if incoming water treatment
is anticipated (such as a water softener) due to hardness
levels or heavy usage of the unit.
• To conserve energy, insulate all hot water piping, except
the condensate drain or pressure relief valve.
• When the water heater is installed in a closed loop
recirculation system, and if the cold water supply line has
a back flow preventer, then an expansion tank should be
installed to allow for water expansion.
• After installation, test the water heater for proper flow and
inspect for leaks.
• Run the hot water for a few minutes and then clean the
inlet water strainer located on the cold water inlet fitting.
This strainer must be cleaned periodically to maintain
proper water flow.
If the incoming water is known to have a high mineral
content or “hardness” (>15 grains/gallon), treatment is
recommended upstream from the water heater.
7.3 Hot Water Connection
Install and connect the hot water lines. If an optional hot
water storage tank is required, connect the hot water lines to
this tank also.
Since each installation is different, it is up to the installer to
route the water lines using the most efficient routing. The
drawings shown here are only suggestions indicating the
items needed for the installation.
1. Connect a short section of 2” copper water line to the
water heater’s hot water connection.
a. The incoming flange, flange gasket, and stainless steel
flange bolts must be supplied by the installer.
b. The flange connection uses a 6” OD, four-bolt brass
flanged assembly.
c. The gasket material specs are an EPDM material with a
minimum rating of 210°F continuous service or higher.
d. The flange bolts are a 3/8” diameter stainless steel.
Also install stainless steel washers on both sides of the
flange.
7.2 Water Quality
Proper maintenance of the water heater is required to ensure
that your water meets EPA quality standards. The following
table shows the maximum contaminant levels allowed, based
on the EPA National Secondary Drinking Water Regulations
(40 CFR Part 143.3). If you suspect that your water is
contaminated in any way, discontinue use of the water heater
and contact an authorized technician or licensed professional.
ContaminantMaximum Allowable Level
Total Hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5-8.5 mg/l
Sulfate205 mg/l
Total Dissolved Solids (TDS)500 mg/l
Zinc205 mg/l
WARNING
To prevent serious personal injury, do not install any
shut-off device between the water heater and the pressure
relief valve. This valve is designed to release abnormally
high pressure within the water heater in the event of a
system problem.
2. Install a tee fitting with either a pressure relief valve or a
temperature and pressure relief valve, as required by your
local code.
33 iQ751 - iQ1001 Water Connections
Temperature and Pressure Relief Valve.
NOTICE
The pressure relief valve must be rated at 150 psi, the maximum
btu/h input of the unit, and comply with all local building codes
and standards. Do not install any restrictions or other valves in
the pressure relief line.
a. Route the relief valve to within 6 inches of the floor to
prevent injury in the event of a discharge.
b. The diameter of the pipe from the relief valve must be
equal to the outlet size of the relief valve.
c. Do not use reducers in the outlet piping.
d. Do not install any valves, restrictions, or other
blockages in the outlet piping.
e. For multiple unit installations, the outlet piping
must not be connected together. Each line must be
separately routed to a suitable drain.
3. Install and route a discharge pipe from pressure relief
valve to within 6 inches of the floor and directed away
from walkways or other appliances.
4. Following local building codes, install a manual shut-off
valve.
5. Connect the unit to the building’s hot water lines. If
multiple water heaters are being installed, the diameter
of both the main cold water lines and the main hot water
lines need to be sized appropriately.
6. With the unit OFF, open a nearby hot water faucet and
allow the water to run through the unit until all the air is
exhausted from the water lines and from the water heater.
7. Leak test the water piping. Repair any leaks immediately.
Note: For energy conservation, the hot water pipes
should be insulated. Also insulate any recirculation
water lines.
6”
iQ751 - iQ1001 Water Connections 34
7.3.1 Pressure Relief Valve Installation
WARNING
To prevent serious personal injury, do not install any
shut-off device between the water heater and the pressure
relief valve. This valve is designed to release abnormally
high pressure within the water heater in the event of a
system problem.
Install a customer-supplied 3/4” 150 psi maximum pressure
relief valve with the appropriate BTU/HR rating into the 3/4”
female NPT port on the back of the unit.
Note: The water heater is designed with an internal high
temperature shut-off switch and, therefore, only a
pressure relief valve is required for these units.
7.4 Cold Water Connection
Install and connect the cold water lines.
Note 1: If the incoming water is known to have a high
mineral content or “hardness” (>15 ppm), treatment
is recommended upstream from the water heater.
Note 2: A water inlet stainer must be installed prior to use.
This strainer must be inspected and cleaned after
initial operation of 3 hours. Subsequently inspect
the strainer at least every 3 months to establish a
cleaning schedule.
Since each installation is different, it is up to the installer to
route the water lines using the most efficient routing. The
drawings shown here are only suggestions indicating the
items needed for the installation.
1. Connect a short section of 2” copper water line to the
water heater’s cold water connection.
a. The incoming flange, flange gasket, and stainless steel
flange bolts must be supplied by the installer.
b. The flange connection uses a 6” OD, four-bolt brass
flanged assembly.
c. The gasket material specs are an EPDM material with a
minimum rating of 210°F continuous service or higher.
d. The flange bolts are a 3/8” diameter stainless steel.
Also install stainless steel washers on both sides of the
flange.
2. Following local building codes, install a manual shut-off
valve.
3. Connect the unit to the building’s cold water lines. If
multiple water heaters are being installed, the diameter of
the main cold water line needs to be sized appropriately.
4. With the unit OFF, open a nearby hot water faucet and
allow the water to run through the unit until all the air is
exhausted from the water lines and from the water heater.
5. Leak test the water lines. Repair any leaks immediately.
7.5 Condensate Line Installation
7.5.1 Connection Recommendations
Due to its efficient design, the Intellihot water heater
produces condensate (water) as a normal by-product of
heating the water.
1. This condensate is acidic, with a pH level between 3 and 4.
Local building codes may require an in-line neutralizer to
be installed (not included) to treat this water.
2. The maximum condensate flow rate is 20 GPH.
3. The condensate drain trap, associated fittings, and drain
line must be removable for routine maintenance.
4. The drain line must be higher than the condensate pump
of the floor drain connection to drain properly.
5.The condensate pump must be supported by the floor or
other means; it cannot be supported by the connecting
pipes.
6.The drain line should contain a union to facilitate
servicing the unit or cleaning the drain line.
35 iQ751 - iQ1001 Water Connections
7.5.2 Drain Line Installation
1. Install a 3/4” flexible hose to the hose connection on the
water heater.
Note: If a floor drain is used to remove the discharge, route
the drain pipe over or into the drain. If a condensate
pump is being used, the water heater may need to be
raised off the floor to accommodate the height of the
pump.
3. If a floor drain is not available, a condensate pump can be
used to pump the condensate to the drain.
4. Route the hose on the trap outlet to a nearby floor drain
or drain pipe.
2. If required, install an inline neutralizer to treat the acidic
condensate. Follow all the installation instructions
included with the neutralizer.
Inline
Neutralizer
iQ751 - iQ1001 Water Connections 36
8. Electrical Power
8.1 Electrical Recommendations
WARNING
To avoid serious injury or even death, follow all applicable
local, state, and national regulations, mandates, and
building codes for guidelines to install the electrical power
supply.
Electrical code requirements are different in the USA and
Canada. Refer to and follow the local building codes, the
latest edition of the National Electrical Code (NFPA 70) in the
USA, or the CGA C22.1 Canadian Electrical Code - Part 1.
Depending on the number of water heaters being installed,
the circuit breaker(s) should be at least 20 amps for each unit.
If one unit is installed, a dedicated 20 amp circuit is required.
If four units are installed, then an 80 amp circuit breaker is
required or four separate 20 amp circuits.
80 amp
Four Units
20 amp
Single Unit
8.2 Connection Instructions
1. On single unit installations, make sure the electrical
outlet being used is wired with at least 12 gauge wire
and grounded with at least a 20 Amp circuit breaker. The
electrical power required for the water heater is 120V AC
at 60 Hz.
2. Remove the cover screw and open the cover.
Use 20 Amp Breakers For Single Units Or Larger Breakers (80 Amp) For
Multiple Units.
Note: For an electrical wiring schematic, refer to the
Wiring Diagram section in this manual for additional
information.
NOTICE
The electrical connections for the water heaters are polarity
sensitive. Before connecting the water heater to the power source,
test the polarity of the electrical circuit.
3. Install a customer-supplied 1/2” conduit fitting into the
cover. The illustrations provide an example; however, the
electrician should install the electrical wiring in a manner
that is safe and efficient for the overall use of the water
heater.
37 iQ751 - iQ1001 Electrical
WARNING
To avoid serious injury or even death from electrical
hazards, an ON/OFF switch should be installed near the
water heater. The switch will allow power to be removed
from the water heater prior to service or in the case of an
emergency.
4. Route a 12 gauge wire with ground from an electrical
junction box with an ON/OFF switch through the cover
and into the water heater.
5. Connect the white wire to the white pigtail wire. Connect
the black wire to the black pigtail wire. Connect the green
ground wire to the green wire.
Note: It is recommended that a separate ON/OFF switch
or breaker box be installed near the water heater to
remove power from the unit when servicing the water
heater or in case of an emergency.
Note: If multiple units are being installed, the gauge of wire
to the junction box must be increased to meet the
additional electrical load. Consult the electrical codes
for the correct wire size.
6. If multiple units are being installed, refer to the Multiple
Units section of the manual for additional information.
iQ751 - iQ1001 Electrical 38
9. Propane (LPG) Conversion
PROPANE
NATURAL
GAS
SAFETY
INSTRUCTIONS
A qualified service technician MUST make the required
changes to convert the water heater from Natural Gas to
LP Gas.
9.1 General Information
Before beginning the conversion, make sure the LP gas inlet
pressure is between 8.0” and 13.0” W.C. Record the gas
pressure here.
STATIC LP GAS PRESSURE ____________W.C.
DATE ___________________
9.2 Procedure
1. Make sure all hot water faucets are OFF. If required, press
the control panel Power button to turn the water heater
OFF. Disconnect the power.
2. Shut OFF the gas supply inlet valve closest to the unit, if
connected.
3. Remove the front cover and locate the main circuit board.
4. Locate DIP Switch 1 and change it to the PROPANE
position.
5. Reconnect the power and wait for main screen to appear.
6. Press and hold the Mode button until the rS screen
appears on the display.
7. Press the Mode button multiple times until the Ft screen
appears on the display. The current Fuel Type setting will
appear. Either nAt or Prop will be displayed to indicate
the position of the DIP switch.
NATURAL
NATURAL
GAS
GAS
PROPANE
PROPANE
DIP Switch Settings
SW1Propane
ONON
(Réglages des commutateurs DIP)
Natural Gas
(Gaz naturel)
8.Press and hold the Enter button to return to the main
display.
9.Refer to Adjusting the CO2 Level section in this manual for
instructions on connecting a calibrated CO2 analyzer to
the gas valve.
39 iQ751 - iQ1001 Propane Conversion
10. Adjusting CO2 Level
10.1 General Information
This procedure is required only during installation in a high
altitude location or when changing the unit from natural gas
to propane, or when experiencing combustion problems.
This procedure should only be done by a qualified technician.
DANGER
A concentration of carbon monoxide as small as 0.04%
(400 parts per million) in the air can be fatal. When making
high fire and/or low fire adjustments, CO levels must be
monitored using a flue gas analyzer so that the level of no
more than 400 ppm of CO is exceeded at any time during
the operation.
Adjusting the “low fire screw “ or the “high fire screw”
in small increments can result in a significant increase
in CO concentration. To avoid serious injury or death,
DO NOT make any adjustments to the gas valve without
monitoring the exhaust gases with a fully functional and
calibrated flue gas analyzer.
CO2 and CO Standards
DescriptionCO2 Range (%)Max. CO Level (ppm)
Natural Gas
High Fire8.8% to 9.1%< 200 ppm
Low Fire8.6% to 8.9%< 60 ppm
LP Gas
High Fire9.0% to 9.8%< 200 ppm
Low Fire8.6% to 8.9%< 60 ppm
10.2 Procedure
1. Locate the gas valve.
2. Use a CO2 analyzer to measure the exhaust vent gas at the
port on the main vent pipe.
3. Press and hold the Mode button for five seconds to access
the rS screen on the display.
NOTICE
The values listed in the table are for nominal conditions.
Variables such as gas pressure, heating value of the gas, and
the humidity and temperature of combustion air can all impact
CO and CO2 values. Changes in these variables can result in
different CO and CO2 values on the same water heater.
A qualified service technician must use a calibrated CO2 analyzer
to adjust the gas valve to achieve the desired CO2 and CO values.
It is recommended that before any adjustments are
made, the gas pressure to the unit be as follows:
NG - 8” W.C.
LP - 11” W.C.
The service technician must confirm Static gas pressures before
setting High Fire and Low Fire CO2 and CO values.
4. Press and release the Mode button multiple times until the
CO screen appears on the display.
iQ751 - iQ1001 Adjusting CO2 Level 40
5. Press and release the ENTER button. Lo will be displayed
indicating the unit will fire at its lowest firing rate when a
hot water faucet is opened.
6. Press the Up arrow. Hi will be displayed indicating the unit
will fire at its highest firing rate when a hot water faucet is
opened.
7. Open several hot water faucets to allow at least 5 gpm of
water flow.
8. When the unit is operating at high firing – the shower,
blower, and flame icons will be displayed.
V3 - Flow Restrictor
11. Once the desired values are achieved, record the new
HIGH FIRE CO
values in table column 2, ‘Adjusted Hi’.
2
9. Record values in table column 1, ‘Hi’. If the CO2 values are
within the 8.8%-9.1% range, proceed to step 11, otherwise
continue with Step 10.
10. Use a flat blade screwdriver to adjust the gas valve high
fire screw to achieve the desired CO
values.
2
Note: Turn clockwise to decrease CO2 and counterclockwise
to increase CO
increments. Wait three minutes for reading to stabilize
. Make adjustments by making 1/4 turn
.
2
and then record the combustion analyzer values for
CO2 and CO.
CO2 and CO Recorded Values
HiAdjusted HiLoAdjusted Lo
CO2 Value %
H1
Max CO ppm
Date
HiAdjusted HiLoAdjusted Lo
CO2 Value %
H2
Max CO ppm
Date
HiAdjusted HiLoAdjusted Lo
CO2 Value %
H3
Max CO ppm
Date
HiAdjusted HiLoAdjusted Lo
CO2 Value %
H4
Max CO ppm
Date
12. Press the Down arrow key to let the unit fire at low fire.
13. Record values in table column 3, ‘Lo’. If the CO2 values
are within the 8.6%-8.9% range, proceed to Step 15,
otherwise continue with Step 14.
41 iQ751 - iQ1001 Adjusting CO2 Level
14. Adjust the Low Fire screw while the burner operates at
low fire using a 2 mm hex wrench. Turn clockwise to
increase CO2 and counterclockwise to decrease CO
V2 - Regulator Offset
.
.
2
18. Press and release the Enter button to repeat or press and
hold the Enter button to return to home screen
19. Close all open water faucets.
20. Turn off water flow
21. Remove the combustion analyzer.
22. Plug access port.
23. Press and hold the Enter button to return to home screen
to resume operation.
15. Once the desired values are achieved, record the LOW
FIRE CO
values in table column 4, ‘Adjusted Lo’.
2
16. Press and release the Enter button to advance to the H2
display Screen.
17. Repeat steps 9-15 until all the modules are set to the
desired CO2 levels.
H1, H2 and H3 for the iQ751.
H1, H2, H3, and H4 for the iQ1001.
24. Leak test the gas valve before placing the unit in
operation. Only use approved leak detector liquid
solutions to check for leaks.
25. Install any removed side panel covers and close the front
door panel.
iQ751 - iQ1001 Adjusting CO2 Level 42
11. Operation
11.1 Control Panel
G
F
Mode
Time
E
D
A) LCD screen
The LCD display screen shows all information about the
operating functions of the water heater.
A
B) Arrow keys
Press the UP or DOWN arrows to adjust the value of the
selected feature, such as time or water temperature.
C) Enter button
To return to the Main or Home screen.
B
D) Power button
When the water heater is initially connected to an electrical
Enter
Power
power supply, the unit will automatically turn ON and the
display panel should light up. To turn the unit OFF, press
the Power button. The unit can then be turned ON again,
once the blower finishes its purge cycle (10 seconds) by
pressing the Power button.
C
E) Time button
Press this button to set the hours and minutes on the clock.
F) Mode button
Press this button to access various Modes of Operation.
G) Orange button
Used to view real time flow and temperature readings.
11.2 Display Icons
KM OPQR
J
I
H
T
H) Displays the current time in AM or PM.
I) Displays the CODE icon and the most recent digital error
code.
J) Displays the INLET icon and the actual inlet water
temperature.
K) Indicates an error has been detected and a trouble code
may be shown next to the CODE icon.
L) Not Used.
S
M) Warns of freezing conditions within the water heater. The
water heater is designed to turn ON to prevent freezing of
the internal water pipes.
N) Not Used.
O) Indicates water flow (open faucet).
P) Indicates blower is ON.
Q) Indicates burner is ON.
R) Indicates the level of energy usage. There are four “bar”
indicators and each represent 25% of gas usage.
S) Indicates outlet water temperature.
T) Indicates multiple units are daisy chained and programed.
When flashing, indicates an error in communication
43 iQ751 - iQ1001 Operation
11.3 Turning Water Heater ON and OFF
1. To turn the water heater ON press the Power button. On
applying power, the unit will automatically display the
main screen.
2. To turn the water heater OFF, press and hold the Power
button for three seconds and the display will show the
IdLE screen, and then go blank.
3. To turn the unit back on, press the Power button. The
display will show the rSt screen for 10 seconds, then the
main screen.
2. Press the Up/Down arrows to set the correct minute.
3. Press and release the Time button again.
The hour section of the time display will flash.
11.4 Resetting (Clear) Error Codes
1. To reset the water heater and clear all error codes, press
and release Power button.
11.5 Setting the Time
1. Press and release the Time button.
The minute section of the time display will flash.
4. Press the Up/Down arrows to set the correct hour. When
setting the hour, make sure you have correctly advanced
the time to either the AM or PM hour setting.
5. Press and release the Time button again.
The colon (:) between the hours and minutes should now
be flashing, indicating the time has been properly set.
iQ751 - iQ1001 Operation44
11.6 Adjusting the Water Temperature
11.6.1 General Information
These commercial water heaters are capable of heating water
to 190°F.
Note: The outlet water temperature is factory preset to
120°F.
WARNING
Hot water temperature over 125°F (52°C)
can cause severe burns instantly or death
from scalding. Children, the disabled, and
the elderly are at the highest risk of being
scalded. Do not leave children or the infirm
unsupervised. Check temperature of hot
water before taking a shower or bath. To
control water temperature to a particular faucet,
temperature limiting valves can be installed by your
service professional.
All water faucets must be closed before changing the
temperature setting. The unit must not be operating
(burner icon not on).
11.7 Real Time Temperature and Flow of the System
Press and hold the Orange button. On the left hand side the
screen will toggle between Flo, then show the flow rate in
gallons per minute, after which the words “Flue” along with
the flue temperature will appear, followed by the word Out
(water outlet temperature). These three screens will continue
to cycle as long as the set key is held down.
The flow screen Flo indicates gallons per minute (gpm). This
screen alternates between Flo and the actual gallons per
minute. The first two digits are gallons and the second two
digits are a portion of one gallon. For example 3:05 is 3.05
gallons per minute.
11.6.2 Adjustment Procedure
Press the Up/Down arrows to set the desired temperature
range from 100 to 140°F in one degree increments.
For setting the temperature above 140°F, press and
continue to hold the Orange button while pressing the Up
arrow. Continue pressing the Up button until the desired
temperature range is reached.
Release the Orange button to return to the home screen.
Once the desired temperature is selected, the unit will heat
water up to that temperature.
When the Orange button is released, the Home screen will
appear.
45 iQ751 - iQ1001 Operation
11.8 Error Screen
If an error occurs, the display will indicate an error code; E1,
E3, E7, etc. The flashing triangle will also appear in the upper
left corner of the display to indicate a potential problem with
the unit.
This screen will toggle with the main screen.
The fl ashing triangle will also appear on the main screen.
Refer to the Troubleshooting section for additional
information on the resolution of error codes.
Press and release the Power button to re-set.
11.9 Heat Exchanger Parameters
Press and release the ENTER button. The display will scroll
through flow, outlet temperature, flue temperature and
inlet temperature of heat exchanger H1. The flame and
blower status of H1 is shown on the display icons. The FLO
screen shows the flow rate in gallons per minute of the heat
exchangers.
Note: The last digit represents tenths of a gallon. The unit
does not display the decimal point. The image below
shows 7.5 gallons per minute.
The FLUE screen shows the maximum flue temperature of
the heat exchangers.
The In screen shows the inlet temperature.
Press and release the ENTER button to view the parameters
for the next heat exchanger. After the last heat exchanger
(H4 for iQ1001, H3 for iQ751) is shown, press ENTER to return
to the main screen.
The Out screen shows the outlet temperature.
iQ751 - iQ1001 Operation46
12. Initial Startup
12.1 Instructions
1. Recheck the hot and cold water lines, the gas line,
condensate and drain line, the combustion (fresh) air inlet,
and gas exhaust outlet to make sure they are properly
connected.
Exhaust
Port
Gas
Inlet
Hot Water
Outlet
3. With the unit OFF, open a nearby hot water faucet and
allow the water to run through the unit until all the air is
exhausted from the water lines and from the water heater.
4. If multiple units are being installed, follow the installation
guidelines in the Multiple Units section of the manual.
5. Turn ON the power switch at the electrical junction box
and turn ON the ON/OFF switch on the back of the water
heater cabinet. The water heater’s display panel should
turn ON. DO NOT disconnect the power supply while the
unit is operating (heating water).
Note: For additional electrical protection, the use of a surge
protection device is recommended. Damage caused
by power surges is not covered by the warranty.
Air
Intake
Cold Water
Inlet
Condensate
Drain
2. Before connecting the water heater to the power, open the
gas supply valve, cold water valve, and hot water valve.
Hot Water
Valve
Cold
Water
Valve
NOTICE
If the water heater display does not come ON, first check the
plug. Also check the electrical panel circuit breaker and reset
it if necessary. If the circuit breaker trips again, do not reset.
Disconnect the plug and have a qualified technician diagnose the
problem.
Gas
Valve
47 iQ751 - iQ1001 Initial Startup
13. Programming
13.1 Modes of Operation
The Modes of Operation screens provide set up screens and
additional information on the water heater. There are five
Mode of Operation screens which are used by the technician
during installation or maintenance of the water heater.
13.1.1 Standard Modes
1. Press and release the Mode button until the desired screen
shows on the display.
dC - Daisy Chain
FC - Flow Control
PH - Performance History
dE - Diagnostic Error
2. Follow the instructions in the specific section to enter the
desired settings.
13.1.2 Advanced Modes
1. Press and hold the Mode button for five seconds until
the rS screen appears. Now press and release the Mode
button multiple times until the desired screen shows on
the display.
rS - Burner Rate Ramp Setting
Ft - Fuel Type
CE - Common Exhaust
FP - Flue Pipe Type
Id - Heat Exchanger Identifier
CO - Adjust CO2 Level
2. Follow the instructions in the specific section to enter the
desired settings.
13.2 Viewing and Setting Modes of Operation
13.2.1 Daisy Chain
Refer to “Multiple Units” for more information.
13.2.2 Flow Control Selection
Press the Mode button multiple times until the
FC screen appears on the display.
The current setting will be shown on the display.
The water control valve is set to ON for temperature priority
and OFF for maximum flow.
Press the Up/Down arrows to select either ON or OFF.
Press and hold the Enter button for three seconds to save the
settings and return to the home screen.
Note: If the Enter button is not pressed within 30 seconds of
inactivity, the display will return to the home screen.
iQ751 - iQ1001 Programming 48
13.2.3 Performance History
The Performance History mode allows the
technician to view ignition cycles, number of ON
times, and cumulative water flow. The displayed
results are for all the water heater modules
combined within the unit.
Press the Mode button multiple times until the PH screen
appears.
The Flow-On Hours FH, Firing Counts FC, and Cumulative
Flow CF, will now begin to display for 1.5 seconds each. The
display will continue to cycle for 30 seconds and then return
to the home screen. Some examples are shown below.
Diagnostic Code FH (Flow-on hours)
shows one hour of flame. (To obtain
the total hours, multiply the number
by 10).
Error CodeDescription of Error Code
E1
E3
E7
E9
EA
EC
Ed
Flashing
Warning Icon
Flashing
Cascading Icon
* If Eb is displayed, please call the factory for service instructions.
Blower Speed Fault
Blocked Flue Fault
Ignition Failure
Temperature Sensor Shorted
Temperature Sensor Open Circuit
Flue Temperature Exceeded Set Limit
Heat Exchanger Outlet Temperature Exceeded
Set Limit
Error Code and Unit Locked Out
Loss of Communication Between Units
Press and release the Mode button multiple times until the
dE screen appears.
Diagnostic Code FC (Firing Count)
shows a flame count of 40,000. (To
obt ain the total number, multiply
the number by 1,000).
Diagnostic Code CF (Cumulative
Flow) shows 38,000 gallons of
water. (To obtain the usage in
gallons, multiply the number by
1,000).
Press and hold the Enter button for three seconds to return to
the home screen.
Note: If the Enter button is not pressed within 30 seconds of
inactivity, the display will return to the home screen.
13.2.4 Diagnostic Code and Error Log Selection
This screen provides the technician with Diagnostic
Codes and Errors recorded as the water heater
operates. These codes are used in conjunction with
the Performance History Codes.
The H1, H2, H3, and H4, codes refer to a specific water heater
module. The iQ751 will not have an H4.
With the 1:E1 type codes, the first number is the sequence
in which the error code occurred and the second number
is the error code. Refer to the examples below for further
clarification.
Example of diagnostic code Fan
Speed Error Code E1 in water heater
module H1.
Each module will scroll through up
to 10 error codes.
Example of switching between
water heater modules displays
four _ _ _ _ underline characters for
two seconds. This is an example of
the display switching from water
heater module H2 to H3.
Example of water heater module H3
with no error codes (nOnE).
Example of water heater module H4
with an E3 Blocked Flue error code.
This is the oldest recorded (number
10).
After the codes are displayed, the display will go back to the
main screen.
49 iQ751 - iQ1001 Programming
13.2.5 Blower Ramp Selection
When exhaust harmonics are observed, i.e.
resonance at low fire, adjust the water heater using
the blower ramp setting (default is rat3). Increase
the rate number until the resonance is no longer
observed.
The Blower Ramp Selection has five different settings
(rat1 - rat5):
Press and hold the Mode button for five seconds to access
the rS screen on the display. The current setting will be
displayed.
Press the Up/Down arrows to select the Blower Ramp
Selection from five different settings (rat1 - rat5).
Select a ramp rate at which the harmonics disappears during
operation.
Press the Enter button to advance to the next heat exchanger,
H2 for example. Continue to press the Enter button until all
the units have been set up.
Press and hold the Enter button for three seconds to save the
settings and return to the home screen.
Note: If the Enter button is not pressed within 30 seconds of
inactivity, the display will return to the home screen.
iQ751 - iQ1001 Programming 50
13.2.6 Fuel Type Verification
13.2.7 Adjusting CO2 Levels Selection
The Fuel Type mode screen shows the selected fuel
type; natural gas (factory preset) or Propane.
Operation with natural gas is factory preset. Refer
to the Propane (LPG) Conversion section in this
manual for additional set up information.
Press and hold the Mode button for five seconds to access the
rS screen on the display.
Press and release the Mode button until the Ft screen appears
on the display. The current Fuel Type setting will appear (nAt
or PrOP) to indicate the position of DIP switch 3 on the circuit
boards. Fuel type cannot be changed from the screen.
Refer to the Adjusting the CO2 Level section in this
manual.
13.2.8 Common Exhaust Venting
Changing this setting can only be done when the
Flame ON icon is not displayed.
This mode is applicable when multiple units are connected
together. Turning the CE mode ON allows multiple units
to be vented into a common vent. Refer to the Venting for
Commercial Application section for information on common
venting guidelines.
Press and hold the Mode button until the rS screen appears.
Press and release the Mode button multiple times until the
CE screen appears. The current setting will be displayed.
The default setting for this mode in ON.
To change fuel type from factory set natural gas to propane,
follow the Propane Conversion procedure in this manual.
Press and hold the Enter button for three seconds to return to
the home screen.
Note: If the Enter button is not pressed within 30 seconds of
inactivity, the display will return to the home screen.
If the dip switches are set incorrectly an error screen will be
shown
Press the Up/Down arrows to select either ON or OFF.
Press the Enter button to save the changes and return to the
main display.
Note: If the Enter button is not pressed within 30 seconds of
inactivity, the display will return to the home screen.
51 iQ751 - iQ1001 Programming
13.2.9 Flue Pipe Selection (PVC or CPVC)
13.2.10 Heat Exchanger Identifier
Changing this setting can only be done when the
Flame ON icon is not displayed.
WARNING
When the unit is set for CPVC or polypropylene pipe,
flue temperatures can reach 190°F. PVC pipe will
lose integrity at temperatures above 149°F. Make
sure FP setting and the type of material being used for the
flue are compatible.
Press and hold the Mode button until the rS screen appears.
Press the Mode button multiple times until the FP screen
appears. The current setting will be displayed.
The default setting for this mode is PVC.
The ID or identification mode is used to program an
identifier in each of the control boards. This
procedure is not necessary unless a controller is
being replaced during service and should be carried
out by a trained service contractor. Incorrect programming
can result in communication problems and cause the unit to
malfunction. Please follow appropriate safety procedures
when replacing a control board including turning off gas,
water, and power to the unit.
Plug the display harness into the controller that is being
replaced.
Press the Up/Down arrows to select the desired setting of
either PUC or CPUC.
Note: The flue temperature for PVC material must not
exceed 149°F. The flue temperature for CPVC or
Polypropylene material must not exceed 190°F.
Press the Enter button to save the changes and return to the
main screen.
Note: If the Enter button is not pressed within 30 seconds of
inactivity, the display will return to the home screen.
Turn power on.
Press and hold the Mode button for more than 5 seconds till
the rS screen is shown.
Press the Mode button multiple time until Id is displayed.
Use the Up/Down arrows to set the appropriate ID. For
example if controller #2 is being replaced, then the
replacement controller should be set with an ID of “H2”.
Press and hold the Enter button for three seconds to save the
setting and return to the home screen.
iQ751 - iQ1001 Programming 52
14. Multiple Units
14.1 General Information
Water heaters are designed to connect multiple units
together. Multiple units increase the volume of hot water
and also ensures that hot water is always available, even if
one unit is shut down due to maintenance.
Connecting several units together requires proper sizing of
water and gas piping, as well as increased size in the intake
and exhaust pipes.
Up to four water heaters can be connected (cascading)
together. Use the steps in this section along with the basic
installation procedure for installing a single unit.
BUILDING RECIRCULATION PUMP
W/ ISOLATION VALVE AND CHECK VALVE
SHOWERS FOR ILLUSTRATION PURPOSES ONLY
RECIRCULATION
N/O - TANKLESS DESIGN
MAIN GAS SHUT OFF
LINE SHUT OFF
1-1/4”
COLD SUPPLY TO INTELLIHOT
1-1/4”
2”
2”
2”
HOT SUPPLY
1-1/4”
2”
2”
2”
MAIN COLD WATER SHUT OFF
The water heaters will communicate through a cable
connection between each water heater. Do NOT connect
the communication cable until instructed to do so in the
procedure. The benefits of connecting the units are as
follows.
• When demand for hot water is low, fewer units will operate.
• If one unit has an error code, the others will continue to
operate.
• Changing the settings (temperature, time, etc.) on one unit
changes settings on all the units.
• It allows possible the shut down of one unit for maintenance
while the others continue to operate.
14.2 Installation Procedure
1. Connect all the units to a gas supply pipe. Make sure the
pipe is properly sized in accordance with the BTU draw
and number of units being operated.
2. Connect all the units to the power supply.
Note: Each water heater is rated at 2000 watts
(20 amps). When installing multiple units, the
electrical power supply must be sized accordingly.
Plug each water heater into a separate outlet. Using a
separate circuit for each unit allows one circuit breaker
to trip while the other units can continue to operate.
MIXING
VALVE
HOT OUTLET SHUT OFF
Manual
Valve
Main Supply
Line
Drip Leg
Manual
Shut-off
Valve
Manual
Shut-off
Valve
Drip Leg
Manual
Shut-off
Valve
Shut-off
Drip Leg
3. Install the combustion (fresh) air intake and exhaust
outlet pipes. Make sure the pipes are properly sized in
accordance with the number of units being operated.
Refer to the sizing table in this manual.
a. Connect the 6” air inlet from the unit to a properly
sized (large) common trunk line using suitable
adapters, wye fittings, and elbows.
b. Connect the 6” exhaust outlet from the unit to a
properly sized (large) common trunk line using suitable
adapters, wye fittings, and elbows.
4. Install and connect the hot water lines. If an optional hot
water storage tank is required, connect the hot water lines
to this tank. Make sure the water pipe is properly sized in
accordance with the number of units being operated.
5. Install and connect the cold water lines. Make sure the
water line is properly sized in accordance with the number
of units being operated.
6. Connect and route the condensate drain lines to a suitable
discharge location.
Do NOT connect communication cables yet. Power up all
7.
the heaters Set dC Mode to unique number. (e.g. if 3
heaters, set unique heater to 1,2,3) Repeat for each unit.
Wait for 30 seconds.
8.
WARNING
Before making any adjustments or connections inside the
water heater cabinet, make sure the power is disconnected.
Unplug the water and/or turn the circuit breaker OFF.
If necessary, press the Power button to turn OFF each
9.
water heater in the system.
Disconnect power from all the units in the system.
10.
53 iQ751 - iQ1001 Multiple Units
11. Open the front cover and locate the main circuit boards.
14
23
1
14
23
iQ1001 Shown (Four Circuit Boards). iQ751 Has Only Three Circuit Boards.
12. Connect a communication cable from the upper port on
circuit board 3 (iQ751) or 4 (iQ1001) of the first water
heater to the upper port of circuit board 1 of the second
water heater. Repeat this step as required by the number
of water heaters being installed.
Ft
Field Installed Cable
(30’ maximum length)
Unit 1Unit 2
iQ751
iQ751 - iQ1001 Multiple Units 54
Field Installed Cable
(30’ maximum length)
Unit 1Unit 2
iQ1001
13. On the fi rst water heater, locate DIP Switch 3 on circuit
board 1. Position the switch in the ON position (left).
Refer to the illustrations for additional clarifi cation.
14. Position the switches on other two or three circuit
boards in the OFF position (right). There are two
additional switches on Model iQ751 and three
additional switches on Model iQ1001.
15. On any water heater unit between the fi rst and
last unit, Unit 2 and/or Unit 3, position all DIP SW3
switches in the OFF position (left).
16. On the last water heater, locate DIP Switch 3 on circuit
board 3 or 4 depending on the model and position the
switch in the ON position (right). All the other switches
should be in the OFF position.
17. Once the communication cables are routed and
connected and the DIP switches are correctly
positioned, close and lock the front cover.
18. The water heaters, should now be ready to
communicate with each other and operate as a single
system.
Note: Whenever a change is made to one water heater, all
the other units in the system will be automatically
updated to the new settings.
55 iQ751- iQ1001 Multiple Units
14.3 DIP Switch Configuration Drawings
ON
SW3
SW3
SW3SW3
SW3SW3
OFFOFF
iQ751
ONOFF
SW3SW3
SW3
SW3SW3
Unit 1
Unit 1
SW3
OFF
SW3
SW3
SW3SW3
SW3SW3
Unit 2
OFFOFF
Unit 2
OFFOFF
SW3SW3
SW3
SW3SW3
OFF
SW3
SW3
SW3SW3
SW3SW3
OFFOFF
OFF
SW3
SW3
SW3SW3
SW3SW3
OFFON
Unit 4Unit 3
Unit 4Unit 3
OFFOFF
SW3SW3
SW3
SW3
SW3SW3
SW3
OFFON
SW3SW3
SW3
SW3SW3
SW3
SW3SW3
OFFOFF
iQ1001
SW3SW3
OFFOFF
SW3SW3
OFFOFF
SW3SW3
OFFOFF
iQ751 - iQ1001 Multiple Units 56
15. Maintenance
15.1 Air Filter
15.1.1 Inspection
Check the filter every six months for dirt and duct build-up.
Clean and re-oil the filter annually. If the filter is dirty, follow
the cleaning procedure.
Note: The air filter is manufactured by K&N. Contact K&N at
800-858-3333 or online at
www.knfilters.com for the necessary supplies to clean
the filter.
1. Loosen the band clamp and remove the air filter.
15.1.2 Cleaning Procedure
1. Liberally spray K&N Air Filter Cleaner and Degreaser (99-
0606) onto both sides of filter and allow to soak for 10
minutes to loosen the dirt. Do not allow cleaner to dry on
air filter.
NOTICE
2. Inspect the inside of the filter for dirt and dust build-up.
Clean the filter, if needed.
3. After inspection and/or cleaning, replace the air filter and
snugly tighten the band clamp.
K&N Air Filter Cleaner is the only cleaner formulated to safely
clean K&N air filters with cotton media. The use of any other
cleaning solution could damage the cotton material.
2. Rinse the air filter with cool low-pressure water applied
from the inside out in order to flush the dirt out of the
filter. Continue to rinse the filter until all traces of cleaner
are gone. It may be necessary to repeat Steps 1 and 2
57 iQ751 - iQ1001 Maintenance Section
3. After rinsing, gently shake off the excess water and air dry
the filter.
NOTICE
Do not use compressed air to dry the filter. Do not apply oil to the
filter until it is completely dry.
4. Spray K&N Aerosol Air Filter Oil (99-0504) evenly along
the crown of each pleat holding nozzle about 3” away.
Allow oil to wick for approximately 20 minutes. Touch up
any light areas on either side of the filter until there is a
uniform red color at all areas.
1. Twist the bottom of the sediment cup to release the
locking clips.
15.2 Condensate Sediment Cup Cleaning
There are four (iQ751) and five (iQ1001) sediment cups
located inside the water heater cabinet. These cups should
be removed and cleaned annually.
2. Pull down on the sediment cup and pull it away form the
upper portion of the unit. The sediment cup will normally
be full of condensate. Carefully, pour the condensate into
a container and properly dispose of it.
iQ751 - iQ1001 Maintenance Section 58
3. Remove the sediment cup from inside the lower portion of
14
23
34
12
the unit.
4. Remove any dirt and debris build-up using soap and warm
water.
5. Replace the sediment cup in the lower portion of the unit
and reattach it to the upper portion.
WARNING
To avoid serious injury or even death, follow all applicable
local, state, and national regulations, mandates, and
building codes for guidelines to install the electrical power
supply.
1
14
23
Front
3
34
15.3 Maintenance-Free Circulation Pump
The circulation pump is maintenance-free and therefore does
not require any servicing. The only adjustment is the speed
setting, which must be set to Speed 3 (III).
15.4 Water Heater Control Boards
Each water heater heat exchanger is controlled by a separate
control board. Whenever making a setting for a specific
water heater heat exchanger, use the following diagram to
identify which control board controls which heat exchanger
module. The control boards and heat exchanger modules
should also have corresponding numbers attached to them.
• Check exhaust termination. Check exhaust
connection at water heater. Install screens.
• Check slope of drain. Check for double loops, air
locks, or debris in loop.
• Check wiring.
• Check pump, check cross over solenoid. Electrical
noise (DSI).
• Replace part.
• Adjust gas pressure at regulator, check / upsize gas
line, check for gas line blockage.
• If the problem persists, turn control panel OFF, shut
gas valve, unplug unit, and contact an authorized
service technician.
• Check for nicked or broken sensor wiring or
connectors. Also check for corroded or wet
connectors.
• Measure resistance of sensor at connector (18 Kohm
at 50°F, 10 Kohm at 77°F, 3 Kohm at 140°F)
• Replace controller
Temperature Sensor
Open Circuit
iQ751 - iQ1001 Troubleshooting Section 60
• Unplugged connectors
• Faulty sensor wiring
• Faulty sensor
• OUt - heat exchanger water
outet temperature sensor.
• FL - Flue temperature sensor.
• IN - inlet water temperature
sensor.
• Faulty Controller
• Check connectors and ensure they are securely
connected
• Check for nicked or broken sensor wiring or
connectors. Also check for corroded or wet
connectors
• Measure resistance of sensor at connector (18 Kohm
at 50°F, 10 Kohm at 77°F, 3 Kohm at 140°F)
• Replace controller
ERROR CODEDESCRIPTIONPOSSIBLE CAUSEREMEDY
Flue Temperature
Exceeded Set Limit
• Incorrect vent set up
• High inlet temperature
• If vent pipe material is CPVC or Polypropylene, ensure
that CPVC is selected in the FP (Flue Pipe) mode.
• Ensure inlet temperature is lower than 150°F if vent
pipe material is PVC or lower than 190°F if vent pipe
material is CPVC or Polypropylene.
• Faulty sensor wiring
• Check for nicked or broken sensor wiring &
connectors. Also check for corroded or wet
connectors
• Faulty sensor
• Measure resistance of sensor at connector (18 Kohm
at 50°F, 10 Kohm at 77°F, 3 Kohm at 140°F)
• Replace controller
• Ensure the water flow rate does not change faster
than 2 GPM every 5 seconds
• Check for nicked or broken sensor wiring or
Heat Exchanger outlet
temperature exceeded
set limit
• Faulty Controller
• Flow rate changes excessive
• Faulty sensor wiring
connectors. Also check for corroded or wet
connectors
• Faulty sensor
• Measure resistance of sensor at connector (18 Kohm
at 50°F, 10 Kohm at 77°F, 3 Kohm at 140°F)
• Faulty Controller
Flashing Icon• Indicates an error code and unit
locked out
• Replace controller
• Refer to the indicated error code (E1, E2, etc) for
resolution
Flashing Cascade Icon• Loss of communication between
units
• Check for broken or nicked communication cable or
loose connector
• Ensure that the communication cable is not bundled
or tied to any high voltage lines
• Ensure dip switch (SW3) is ON in first and last units
and OFF in all other units
• Ensure each unit numbering is unique under the dC
mode
61 iQ751 - iQ1001 Troubleshooting Section
Modulate Burner To
Maintain Temperature
De-energize Ignition
Post Purge
IH-56 750
iQ751 - iQ1001 Troubleshooting Section 62
16.2 iQ751 / iQ1001 Individual Module
AIR SWITCH
GN
RD
ON
CASCADING
NG
BL
RD
CONNECTIONS
OFF
(POWER)
GREEN LED
OFF
ON
AND FLOW SENSOR
WATER CONTROL VALVE
BN
WT
OR
BL
GN
RD
BL
WT
SENSORS
BL
RD
GN
OR
GN
INTELLIHOT WATER HEATER
CONTROL MODULE WIRING DIAGRAM
MODEL: iQ751/iQ1001
HOT WATER
BL
BN
COLD WATER
GREEN
BROWN
ORANGE
WIRE COLOR CODE
BL
BN
OR
GN
iQ751: 1 OF 3 SHOWN
iQ1001: 1 OF 4 SHOWN
WT
RED
RD
WHITE
WT
RED LED
(BURNER ON)
BN
WT
RD
RD
BN
BN
BL
WT
RD
BNBN
BL
F F
GAS
VALVE
HIGH VOLTAGE CABLE
BLOWER
63 iQ751 - iQ1001 Troubleshooting Section
16.3 iQ751 / iQ1001 Complete System
&20081,&$7,21&$%/(
)86(
)86(
21
/3
1*
)8(/6(/(&7
',36:,7&+6:
*1:7%.
&$6&$',1*
&211(&7,216
2))
*5((1/('
5('/('
2))
21
',36:,7&+6:
32:(5
%851(521
&$6&$',1*
&211(&7,216
21
2))
/3
)86(
)86(
1*
)8(/6(/(&7
',36:,7&+6:
*1:7%.
*5((1/('
5('/('
L421/<
&21752/02'8/(
2))
21
',36:,7&+6:
32:(5
%851(521
%2;
-81&7,21
,17(//,+27:$7(5+($7(5
),(/':,5,1*
:,5,1*',$*5$0
&21752/02'8/(
%./,1(
:71(875$/
*1*5281'
%/8(
%/$&.
%/
:,5(&2/25&2'(
%.
02'(/L41L41
*1
:7
%.
:+,7(
*5((1
%52:1
*5((1<(//2:
%1
:7
*1
*1</
32:(5
6:,7&+
,*7/%/5(9
*1
:7
%.
)86(
)86(
21
/3
1*
)8(/6(/(&7
',36:,7&+6:
*1:7%.
&$6&$',1*
&211(&7,216
2))
*5((1/('
5('/('
2))
21
',36:,7&+6:
32:(5
%851(521
&20081,&$7,21&$%/(
&20081,&$7,21&$%/(
&$6&$',1*
&211(&7,216
21
2))
/3
1*
*5((1/('
&21752/02'8/(
)86(
)86(
)8(/6(/(&7
',36:,7&+6:
*1:7%.
5('/('
',63/$<
2))
21
',36:,7&+6:
32:(5
%851(521
%/
%1
*1</
)86(
&21752/02'8/(
%/2&.
32:(5',675,%87,21
3803
iQ751 - iQ1001 Troubleshooting Section 64
NOTES
65
17. Warranty
General
This unit is warranted by Intellihot Green Technologies Inc.
(Intellihot), and covers defects in materials and workmanship,
subject to the applicable time periods and terms below. The
warranty effective start date begins on the date of installation
or on the date of possession in the case of new construction.
This warranty is extended to the original purchaser and
any subsequent owner at the original install location, and
applies only when properly installed by a licensed contractor
and operated in accordance with the instruction manuals.
This warranty is limited to repairs or replacement of parts,
at Intellihot’s option that are proven to be defective under
normal use and connected only to potable water systems.
Warranty Period
Commercial Domestic Hot Water (DHW) Warranty: Heat
Exchanger coil - 6 years, Other Parts - 1 year
Heat Exchanger Coil
The warranty period for a heat exchanger coil failure, when
installed in a Commercial DHW application is six (6) years
from the effective start date.
ContaminantLevel
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Color15 color units
Copper1.0 mg/l
CorrosivityNon-corrosive
Fluoride2.0 mg/l
Foaming Agents0.5 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
Odor3 threshold odor number
pH6.5-8.5 mg/l
Silver0.1 mg/l
Sulfate250 mg/l
Total dissolved solids (TDS)500 mg/l
Zinc5 mg/l
All other Parts and Components
The warranty period for any original parts (excluding the
heat exchanger coil) against failure, is one (1) year from the
effective start date. A replacement part will be warranted for
the unexpired term of the original warranty. Defective parts
submitted may not be returned. No returns will be accepted
without prior authorization from Intellihot.
Definition of Potable water
Potable water is defined as drinkable water supplied from
utility or well water in compliance with EPA secondary
maximum contaminant levels (40 CFR part 143.3) as shown
in the table. Intellihot will warrant the heat exchanger coil
for hardness up to 15 Grains per gallon (257ppm as Calcium
carbonate)
Shipping Costs
If a replacement part is supplied under the terms of this
warranty, Intellihot will provide ground service delivery for
the part free of charge. Any expedited shipping expense will
be paid by the customer.
.
Warranty 66
Not Covered by this Warranty
This warranty does not cover failures or problems due to:
• Failure to install in accordance applicable building codes,
ordinances, normal plumbing and electrical trade practices.
• Improper installation, improper use, improper maintenance,
improperly made replacements or repairs, accidents or
abuse.
• Sediment deposits, fire, flood, lightning, freezing, and acts
of God, or any causes other than defects in materials and
workmanship.
This warranty will be void and have no e ect if:
• The unit is modified or altered in any way.
• Appliance(s) or equipment attached to the unit that have
not been approved by Intellihot Green Technologies.
• If the unit is used exclusively as a booster heater for a
commercial dishwasher, or if the water from a reverse
osmosis or deionized process is run directly through the
unit.
• The serial number is altered, defaced, or discarded.
Warranty Limitations
This warranty applies only when the unit is used in the United
States or Canada. Except for the limited warranties provided
above, Intellihot Green Technologies disclaims any and all
other warranties, including but not limited to warranties of
merchantability and tness for a particular purpose; provided
however, that implied warranties of merchantability and tness for a particular purpose are not disclaimed during the
1-year period from the e ective date. Intellihot shall not be
liable for indirect, special, incidental, consequential, or other
similar damages, including lost pro ts, arising from or relating
to the unit. This warranty gives you speci c legal rights, and
you may also have other rights which vary from state to state.
How to Make a Claim
Please Call (877) 835-1705. Proof of purchase in the form of a
dated sales receipt or warranty registration should be included with your claim. The product owner should submit the
warranty claim directly to Intellihot at the following address:
Intellihot Green Technologies, Inc.
Attn: Warranty Claims
2900 W Main St
Galesburg, IL 61401
All parts claimed to be defective may be requested to be
returned to Intellihot for examination prior to full claim
settlement. Please include the following information on your
warranty claim:
• Model number and serial number of the unit
• Date of original purchase
• Owner’s name and address
• A description of the problem with the part and unit.
67Warranty
13. Requirements for State of Massachusetts
Notice Before Installation
This appliance must be installed by a licensed plumber or gas
fitter in accordance with the Massachusetts Plumbing and
Fuel Gas Code 248 CMR Sections 2.00 and 5.00.
IMPORTANT: In the State of Massachusetts (248 CMR 4.00 &
5.00)
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements
shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gasfitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery backup
is installed on the floor level where the gas equipment
is to be installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building, or
structure served by the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors.
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with
alarm and battery back-up may be installed on the next
adjacent floor level.
b. In the event that the requirements of this subdivision
cannot be met at the time of completion of installation,
the owner shall have a period of thirty (30) days to
comply with the above requirements; provided,
however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an
alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector, as required in accordance
with the above provisions, shall comply with NFPA 720
and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE.
A metal or plastic identification plate shall be permanently
mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with
the exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign
shall read, in print size no less than one-half (1/2) inch in
size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION.
The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a)1 through 4.
68Massachusetts Requirements
9. Product Warranty Card
To activate your warranty, please fill out the information
in the form below and mail to the following address:
Warranty Registration
Intellihot Green Technologies, Inc.
2900 W. Main Street
Galesburg, IL 61401