Intellihot iB301, iB3001 Operation & Installation Manual

Operation & Installation Manual
iB301
iB3001
Thank you for purchasing this Intellihot unit.
This unit is designed for years of trouble free operation, and I urge you to read and follow the instructions in this “Operation & Installation Manual.”
Our mission to create a better heating system began back in the winter of 2005 when a tank water heater broke down and  ooded my basement. By combining the principles of a diesel engine’s robustness, robotics intelligence, and marine environment durability, we set out to design a unit from the ground up that would outperform and outlast all others.
Quickly, our goal grew from not just making a better water heater, but creating an intelligent water heating and delivery system. Innovation is our hallmark and simplicity, e ciency, and durability are at the core of every lntellihot product.
Our products are proudly engineered and built in Galesburg, Illinois. lntellihot has helped commercial customers throughout the nation save thousands of dollars while eliminating downtime. Our talented team of dedicated professionals is ready to assist you and help your business succeed.
I thank you for purchasing our lntellihot products.
Sincerely,
Sri Deivasigamani CEO, lntellihot Inc.
Table of Contents
DANGER
1. General Information
1.1 Items Shipped With Condensate Neutralizer . 4
1.2 Serial Number Plate Locations . . . . . . . . . . . . 4
1.3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.1 telliBot Monitoring Service . . . . . . . . . . 4
1.3.2 Data and Monitoring . . . . . . . . . . . . . . . 5
1.3.3 Security . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.4 Units Without Wi-Fi Connection . . . . . . 5
1.3.5 Wi-Fi Connections. . . . . . . . . . . . . . . . . 5
2. Safety
2.1 Safety Signal Words. . . . . . . . . . . . . . . . . . . . . 6
2.2 Installation Warnings . . . . . . . . . . . . . . . . . . . . 6
2.3 Gas Leak Noti cation Alarm . . . . . . . . . . . . . . 7
2.4 Carbon Monoxide Hazard . . . . . . . . . . . . . . . . 7
3. Technical Speci cations
3.1 Speci cations Chart . . . . . . . . . . . . . . . . . . . . 8
3.2 Clearance Requirements . . . . . . . . . . . . . . . . . 8
3.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Dimensional Speci cations . . . . . . . . . . . . . . . 9
3.5 Wi-Fi Technical Requirements. . . . . . . . . . . . . 9
3.6 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.6.1 Carbon Monoxide (CO) Sensor. . . . . . 10
3.6.2 Gas Sensor . . . . . . . . . . . . . . . . . . . . . 10
3.6.3 pH Sensor . . . . . . . . . . . . . . . . . . . . . . 10
3.6.4 Leak Sensor. . . . . . . . . . . . . . . . . . . . . . 11
3.6.5 Temperature Sensors . . . . . . . . . . . . . . 11
3.7 Boiler Interlock . . . . . . . . . . . . . . . . . . . . . . . . 11
3.8 Accessory Relay Kit . . . . . . . . . . . . . . . . . . . .11
To avoid product damage, personal injury, or even possible death, carefully read, understand, and follow all the instructions in this Operation
and Installation Manual before installing this product. Improper installation, adjustment, alteration, or maintenance can cause injury, loss of life, and/or property damage. This unit should be installed and serviced by a qualified technician. The lack of proper service can result in a dangerous condition.
Due to Intellihot’s policy of continuous product improvement and technology, the design and/or technical specifications in this manual are subject to change without notice.
This manual contains safety information, installation instructions, and maintenance procedures. It must be left with the product user or placed near the gas-fired appliance in a noncombustible location. The product user should
retain this manual for future reference.
Contact Information
Call us, your dealer, first if you have any questions about this product. We can help answer questions about installation, operation, or if there are damaged or missing parts when unpacking this unit from the shipping box.
4. Preparation Before Installation
4.1 Selecting an Indoor Installation Site . . . . . . . . 11
5. Piping Con guration Examples
6. Condensate Drain Line
7. Electrical
7.1 Electrical Code Requirements . . . . . . . . . . . . 14
7.2 Electrical Connections . . . . . . . . . . . . . . . . . . 14
8. Setup and Operation
8.1 Overview of Operation. . . . . . . . . . . . . . . . . . 14
8.2 Attaching Temperature Sensors . . . . . . . . . . 14
8.3 How to Test Carbon Monoxide Alarm . . . . . . 15
8.4 Mobile Application . . . . . . . . . . . . . . . . . . . . . 15
9. Maintenance
9.1 Neutralizer Media. . . . . . . . . . . . . . . . . . . . . . .17
9.2 Replacement Procedure . . . . . . . . . . . . . . . . .17
10. Troubleshooting
10.1 Troubleshooting Guide . . . . . . . . . . . . . . . . . . 18
11. Warranty
11.1 Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
12. Product Warranty Card
12.1 Warranty Card . . . . . . . . . . . . . . . . . . . . . . . . 21
Dealer Contact Information.
3 iB301 / iB3001
October 2017 - Revision 00
1. General Information
1.1 Items Shipped With Condensate Neutralizer
The following items are shipped with the unit.
• Media bag
• 2 temperature sensors
• 2 temperature clips
• 2 temperature sensor harness
• Manual
• Power supply
WARNING
The condensate drain line(s) from the gas­fired appliance must have a p-trap or some other form of a vapor trap to prevent exhaust
gas from being forced into the condensate neutralizer. The p-trap forms an air block (trap) which prevents carbon monoxide from exiting the gas-fired appliance and flowing into the condensate neutralizer through the condensate drain line or the gas exhaust outlet pipe. Improper installation of the condensate drain line(s) leading to the unit can result in excessive levels of carbon monoxide, which can lead to severe personal injury or death.
1.2 Serial Number Plate Locations
The unit’s serial number is located near the inlet and outlet port, as shown. Please provide this serial number whenever inquiring about service or warranty solutions.
Serial Number: ________________
Date of Installation: ___ / ___ / ______
1.3 Features
1.3.1 telliBot Monitoring Service
The telliBot Monitoring Service is a Wi-Fi enabled, prognostics and predictive maintenance service for the telliBot (unit). Many of the automatic features help transform any gas-fired appliance into a smart device which can be remotely monitored. With or without this service the unit monitors room conditions and warns about potentially damaging or hazardous conditions. Using the paid service allows Intellihot to monitor the unit and control it either remotely or on-site using the app on a mobile device.
Benefits of the Service
1. Monitoring - Units are monitored 24/7/365 by Intellihot, who is able to remotely perform appropriate actions if problems arise.
2. Free Media - Proactively monitors the neutralizer media and ships replacement media prior to needing to be changed.
3. Notifications - Monitors various parameters and sends appropriate notifications alerting of potential issues.
4. Automatic Firmware Updates - Unit is updated with the latest software and updates whenever connected to the Internet.
iB301 / iB3001 General Information 4
November 2017 - Revision 00
5. Prognostics and Predictive Analytics - These reports are available on any smart phone.
a. pH Sensor – Unit measures the pH level of
condensate generated by the gas-fired appliances on a daily, weekly, and monthly basis.
b. Water Temperature Monitoring - The inlet/outlet
water temperatures are monitored and recorded.
c. Gas Sensor – Leakage of combustion gas is actively
monitored and the unit provides visual and audible alerts.
d. CO Sensor – The presence of CO (carbon monoxide)
gas is actively monitored and the unit provides visual and audible alerts when levels exceed recommended standards.
e. Leak Sensor – Water leakage is actively monitored and
the unit provides visual and audible alerts. This feature only monitors the surface on which the unit is sitting on.
1.3.2 Data and Monitoring
With the telliBot monitoring service, the unit automatically generates and sends data to Intellihot servers. The data is gathered electronically and is sent to Intellihot’s servers via secured HTTPS. The monitored data includes operational parameters such as inlet and outlet temperatures, pH values, any gas leakage, any CO leakage, and any water leakage. If the unit experiences any problems or error codes, the user is notified of the issue immediately.
1.3.3 Security
The unit communicates via the Internet using an encryption protocol to keep any monitored information secure.
1.3.4 Units Without Wi-Fi Connection
This unit operates effectively to continuously monitor all the programmed functions with or without a Wi-Fi connection.
1.3.5 Wi-Fi Connections
Wi-Fi connection must meet the technical requirements of “3.5 Wi-Fi Technical Requirements” on page 9 to use the automated telliBot Monitoring Service.
All smart phones are compatible with the telliBot Monitoring Service. If the user does not have Wi-Fi service, but has cell service (3G/4G), Intellihot can connect to the unit with a cellular hotspot. If the user has neither cell service or Wi-Fi, contact technical services.
5 iB301 / iB3001 General Information
October 2017 - Revision 00
2. Safety
2.1 Safety Signal Words
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is limited to the most extreme situations.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
NOTICE
Indicates that equipment or property damage can result if instructions are not followed.
SAFETY INSTRUCTIONS
DANGER
Contact with electricity while on a wet surface will result in an electrical shock which can result in death. Never work on or around this unit when water is present on the floor.
WARNING
DO NOT operate this unit unless it has a properly connected condensate drain(s). Improper connection can cause a release of carbon monoxide into the living space, which can result in brain damage or death. Exhaust gases must be completely expelled out of the building.
Do not route the condensate drain(s) through any area that is exposed to freezing temperatures.
Never allow children or animals to access the pellets in the media bag (Calcite and Magnesium Oxide mixture). These chemicals are not for human or animal consumption. These chemicals can be a slight irritant the skin or eyes, or if ingested or inhaled. If ingested, do not induce vomiting unless directed to do so by medical personnel. Contact a physician immediately.
Safety instructions (or equivalent) signs indicate specific safety-related instructions or procedures.
Note: Contains additional information important to a
procedure.
2.2 Installation Warnings
WARNING
DO NOT use this condensate neutralizer for any purpose other than its intended use.
Read, understand, and follow the Installation and Operation Manual, including all warnings and precautions, before operating this unit. If you do not follow these instructions property damage, personal injury, or loss of life could result.
This unit must be installed by a licensed service technician. Installation by unqualified person(s) voids the warranty.
CAUTION
In case of an emergency, know the location of the electrical panel and how to switch off the power to the unit.
SAFETY INSTRUCTIONS
DO NOT use this unit if it has been submerged in water.
DO NOT reverse the inlet and outlet connections to the unit as this will damage the unit.
The unit should be located in an area where leakage within the unit or at its connections will not result in damage to the surrounding area. The manufacturer will not be responsible for any water damage resulting from inadequate drainage.
iB301 / iB3001 Safety 6
November 2017 - Revision 00
2.3 Gas Leak Notification Alarm
DANGER
This unit will only identify that a gas leak exists. It does not identify which gas-fired appliance may have the leak.
Activation of the built-in “Gas Alarm” indicates the presence of either natural gas or propane gas which can cause death.
Once the alarm sounds immediately move outdoors. Be aware that natural gas is heavier than air and will settle on the floor or in low areas of the building. Make sure everyone has evacuated the building and do not reenter the building until the leak has been stopped and repaired by a professional service provider.
WHAT TO DO IF YOU SMELL GAS:
1. Immediately move outdoors.
a. Do not try to light a gas-fired appliance.
b. Do not touch an electrical light switch or use any
device that could cause a spark.
c. Make sure everyone has evacuated the building.
d. Do not reenter the building until the leak has
been stopped and repaired.
2. Call 911 from outside the building.
2.4 Carbon Monoxide Hazard
WARNING
Early symptoms of carbon monoxide poisoning can mimic many common ailments and may easily be confused with food poisoning, viral infections,  u, or simple tiredness.
Symptoms include:
Mild exposure can create:
• slight headache
• dizziness
• nausea (flu-like symptoms)
• vomiting
• fatigue or tiredness
Medium exposure can create:
• throbbing headache
• visual problems
• drowsiness
• confusion
• fast heart rate
• erratic behavior
Extreme exposure can create:
• pains in the chest or stomach
• convulsions
• unconsciousness
• heart and lung failure
• brain damage
• death.
Carbon Monoxide (CO) Hazard
Combustion of natural gas or propane gas produces poisonous carbon monoxide
(CO) gas that can build up to dangerous levels in enclosed areas. Breathing carbon monoxide can cause unconsciousness, brain damage, and death. Never use a gas- red appliance with a known carbon monoxide leak.
Some individuals are more sensitive to carbon monoxide than others, including people with cardiac or respiratory problems, infants, unborn babies, pregnant mothers, or elderly people can be more quickly and severely affected by carbon monoxide.
Carbon monoxide is odorless, colorless, and tasteless, which makes it di cult to detect. Most cases of carbon monoxide poisoning is due to inadequate ventilation or poor maintenance of a gas- red appliance.
7 iB301 / iB3001 Safety
October 2017 - Revision 00
3. Technical Specifications
3.1 Specifications Chart
iB301 / iB3001 Series Condensate Neutralizer Specifications
Technical Data iB301 iB3001
Maximum rated (BTU/hr) Up to 300,000 BTU/hrUp to 3,000,000
BTU/hr
Gallons per Hour (GPH) max.
Dimensions H x W x D (Inches)
Weight (lbs) 9 13
Weight of Media Bag (lbs) 2 5
Electrical Voltage 120V AC, 60 Hz (Adapter Input)
Electrical Power Consumption
Boiler Interlock Contacts 100 mA, 60 Volts AC/DC
Safety Alarms Carbon Monoxide Alarm, Natural Gas Leak
Wi-Fi Enabled 802.11 b/g
Notifications Email, SMS, App
Add-On, Accessory Kits Water Valve Kit, Gas Valve Kit,
Warranty 1 year
Note: Due to continuous product improvements, the design and technical specifications are subject to change without notice. This product complies with UL Standard (UL 60730-1) and CSA Standard (CAN/CSA-E60730-1).
2.5 25
7.2” x 6.5” x 9.6” 7.2” x 6.5” x 14”
24V DC (Electronics Input)
0.35A (Max)
Alarm, Water Leak Alarm, pH Alarm
Flow Sensor Kit
3.3 Connections
Connections
Item Description Specification
1 Condensate Inlet
2 Condensate Outlet
3 Carbon Monoxide Sensor
4 Flow Sensor
5 Water Inlet Temperature Sensor
6 Water Outlet Temperature Sensor
7 Auxiliary Temperature Sensor
8 Boiler/Water Heater Interlock
9 Power Jack
10 Accessory Relay Box
11 Test/Silence Switch
12 Gas Sensor
13 Water Leak Sensor
1
Using sizes other than specified can cause damage to the unit and will
void the warranty.
1
1
3/4” PVC (Polyvinyl
chloride) SCH 40 or CPVC
(Chlorinated Polyvinyl
chloride) SCH 80
3.2 Clearance Requirements
In order for the unit to operate properly and efficiently, the clearances specified in the table below are required.
TOP
FRONT
Location Service Clearance
Top 12” (30 cm)
Bottom 0” (0 cm)
Front 12” (30 cm)
Back 6” (15 cm) depends on condensate pipe connections
Right-side 0” (0 cm)
Left-side 6” (15 cm) required for electronic connections
RIGHT
SIDE
CONDENSATE
OUTLET
CONDENSATE
INLET
3
4
5
6
7
8
9
10
11
12
13
iB301 / iB3001 Technical Specifications 8
November 2017 - Revision 00
3.4 Dimensional Specifications
6.5 in
166 mm
3/4” Socket PVC/sch 40 3/4” Socket
CPVC/sch 80
2.8 in
70 mm
3.3 in
85 mm
1.6 in
41 mm
0.7 in
18 mm
3.5 Wi-Fi Technical Requirements
The following Wi-Fi connection is required to access the unit’s monitored data or control the unit using the Intellihot app.
1. 2.4 Ghz wireless b/g/n network. Not compatible with 5
Ghz Wi-Fi networks.
2. -75 db minimum signal strength required to connect to
wireless networks.
3. Cannot operate inside a captive web portal. If the unit
must communicate through a web portal on your network contact Technical Assistance.
4. Data communication is encrypted with HTTPS: AES
encryption.
9.6 in (243 mm) iB301
14 in (354 mm) iB3001
8.7 in (223 mm) iB301
13 in (334 mm) iB3001
7.2 in
184 mm
9 iB301 / iB3001 Technical Specifications
October 2017 - Revision 00
3.6 Sensors
Carbon Monoxide Sensor
Flow Sensor
Auxiliary Temperature Sensor
Gas Sensor
Water Leak Sensor
3.6.1 Carbon Monoxide (CO) Sensor
DANGER
Improper venting of gas-fired appliances will result in excessive levels of carbon monoxide, which can lead to severe personal injury or death.
Make sure all gas-fired appliances are vented in accordance with the “Venting of Equipment” section of the latest edition of the ANSI Z223.1 / NFPA 54 (Natural Fuel Gas Code) in the USA, or in Canada refer to the “Venting Systems and Air Supply for Appliances” section in the latest version of CAN/CGA B149.1 (Natural Gas and Propane Installation Code), and all applicable local building codes.
The built-in carbon monoxide (CO) sensor continuously measures the carbon monoxide level in the air. The unit provides both an audible and visual alarm if the carbon monoxide levels rise above safe limits. The sensor will NOT detect smoke, fire, or any other gases.
The unit only monitors the air quality inside the room where it is located, even though carbon monoxide gas may also be present in other areas of the building.
With a subscription to the telliBot Monitoring Service, the user automatically receives notification through the app or email of the presence or absence of carbon monoxide.
For additional information, refer to “10.1 Troubleshooting Guide” on page 18.
SAFETY INSTRUCTIONS
• The unit has a “Silence” feature on the carbon monoxide alarm, but should only be used for momentary convenience prior to correcting the problem.
• NEVER ignore the Carbon Monoxide Alarm. After an alarm sounds, have a qualified technician check the surrounding gas-fired appliances for carbon monoxide leaks. Failure to do so can result in injury or death.
• Test the carbon monoxide alarm once a week. Refer how to test your CO alarm section in this manual. If the carbon monoxide alarm fails to test correctly, replace the unit!
• This product is intended for use in ordinary indoor applications.
3.6.2 Gas Sensor
The gas sensor is designed to detect high levels of natural gas or propane gas. It is NOT designed to detect smoke, fire, carbon monoxide, or any other gases.
The unit only monitors the air quality inside the room where it is located. The alarm is both visual and audible. For additional information, refer to “10.1 Troubleshooting Guide” on page
18.
With a subscription to the telliBot Monitoring Service, a notification of the alarm is automatically sent to the user via the app or an email.
3.6.3 pH Sensor
The built-in pH sensor monitors the pH value of the condensate water after it is treated. The unit notifies the user both visually and audibly when it is time to replace the neutralizer media bag.
The pH level of the condensate from high-efficiency condensing appliances is acidic with pH levels between 3 and
4. Plain tap water normally has a pH level of 7. The acidic
condensate is harmful to the environment and can corrode pipes and drains or other materials involving waste water treatments if not properly neutralized.
The user automatically receives notification through the app or an email when the pH levels are increasing and the neutralizer media bag should be replaced. With a
subscription to the Tellibot Monitoring Service, replacement media will be shipped automatically.
The system also monitors the effectiveness of neutralizer media. With a subscription, it sends a notification that a replacement neutralizer media bag is being shipped (free of charge) when it is time for replacement.
iB301 / iB3001 Technical Specifications 10
November 2017 - Revision 00
3.6.4 Leak Sensor
A built-in leak sensor automatically notifies the user of any water leaks. In order to work properly, the unit must be in direct contact with the floor or surface being monitored.
Units that are elevated off of the floor will not detect a leak until the water level rises to the bottom of the unit.
A visible and audible alarm notify the user of a leak. For additional information, refer to “10.1 Troubleshooting Guide” on page 18.
3.6.5 Temperature Sensors
Two temperature sensors, when connected to copper water pipes, are used to continuously measure the inlet and outlet water temperatures to the gas-fired appliance.
The unit sends temperature information to the user when it is connected to Internet.
There is no visual or audible alarm associated with these sensors.
3.7 Boiler Interlock
TelliBot provides an interlock function to disable the equipment being monitored (e.g. boiler) when a carbon monoxide, gas, or water leak alarm is detected. The telliBot automatically enables the monitored equipment when the alarm condition is no longer present. The two pins are provided as a signal level disconnect function. If no alarm conditions are detected, there is continuity between the pins. When alarm conditions are detected, the continuity is interrupted.
The maximum voltage rating for these pins is 50 VAC/DC and the maximum allowed current is 100mA. If higher voltage or higher current is required, please contact the factory for assistance.
3.8 Accessory Relay Kit
The accessory relay port connects telliBot to the accessory relay controls. The accessory relay controls module controls a gas valve and water valve. When no alarm conditions are present, the gas valve and water valve are energized, allowing the monitored equipment to function. When alarm conditions are present, telliBot signals the accessory relay controls to de-energize the gas valve and water valve, thereby isolating the monitored equipment from gas and water. When alarm conditions are no longer present, the gas valve and water valve are returned to energized condition.
The maximum voltage rating for gas and water valve control signals is 5 VAC/DC and maximum allowed current is 100mA.
4. Preparation Before Installation
4.1 Selecting an Indoor Installation Site
1. Install the unit so that the inlet and outlet connections are below the level of the condensate drain coming from the gas-fired appliance.
a. A one inch minimum distance is required.
b. In the case of a floor mounted gas-fired appliance a
riser may be required to raise the gas-fired appliance to obtain the minimum requirement.
2. Place the unit only in a horizontal position on the floor. Vertical mounting is not permitted and will void the warranty.
3. Any condensate drain connection must have a p-traps between the gas-fired appliance outlet and the unit’s inlet.
4. Locate the unit where pipes are not subjected to freezing temperatures.
5. Locate the unit close to a floor drain or use a condensate pump.
6. Ensure that all connections are water tight.
7. Follow all local codes for handling flue gas condensate.
8. Locate the unit near an electrical outlet.
11 iB301 / iB3001 Preparation Before Installation
October 2017 - Revision 00
5. Piping Configuration Examples
Boiler / Furnace / Water Heater
Vent Condensate Trap
Vent
Vent Condensate Trap
Tellibot
To D rai n
Vent Condensate
Trap
Mounting Pad
Vent
Vent Condensate Trap
Boiler / Furnace / Water Heater
Tellibot
To Drain
iB301 / iB3001 Piping Configuration Examples 12
November 2017 - Revision 00
Vent Condensate Trap
Boiler / Furnace / Water Heater
Vent
Vent Condensate
Trap
Condensate Pump
6. Condensate Drain Line
Due to the efficient design of many gas-fired appliances they produce condensate (water) as a by-product of normal operation. This condensate is acidic, with a pH level between 3 and 4. Local building codes may require an in-line neutralizer, such as the iB301 or iB3001, to be installed to treat this water.
The maximum treatable condensate flow rate is 2.5 or 25 GPH depending on the unit.
1. Follow applicable local codes to treat the acidic condensate. Follow all the installation instructions included with the neutralizer.
2. Route the drain line to nearby floor drain, neutralizer, or condensate pump.
a. If a floor drain is used to remove the discharge, route
the drain hose over or into the drain.
b. Long drain lines should contain a union to facilitate
servicing the unit or cleaning the drain line.
3. If a floor drain is not closely available, a condensate pump can be used to pump the condensate to a remote drain.
a. Route the hose from the condensate pump to a
nearby floor drain or drain pipe.
b. The condensate pump must be supported by the
floor or other means; it cannot be supported by the connecting pipes.
Tellibot
To Drain
13 iB301 / iB3001 Condensate Drain Line
October 2017 - Revision 00
7. Electrical
WARNING
To avoid serious injury or even death, follow all applicable local, state, and national regulations, mandates, and building codes for guidelines to install the electrical power supply.
7.1 Electrical Code Requirements
Electrical code requirements are different in the USA and Canada. Refer to and follow the local building codes, the latest edition of the National Electrical Code (NFPA 70) in the USA, or the CGA C22.1 Canadian Electrical Code - Part 1.
7.2 Electrical Connections
1. Before plugging the unit into an electrical outlet, make sure that the condensate inlet and outlet pipe connections are watertight and there is no leakage.
2. Make sure all cables are correctly connected. Damage caused due to improper connections will void the warranty. Do not route any cable through an area that is exposed to water. Always keep the cables dry.
8. Setup and Operation
8.1 Overview of Operation
All high-efficiency gas-fired appliance produce an acidic condensate and a typical 100,000 BTUH gas-fired appliances produces approximately 1 gallon of acidic condensate per hour.
This condensate enters through inlet port, flows through the neutralizing media, and pH neutral water is discharged from the outlet port into the drainage system.
8.2 Attaching Temperature Sensors
1. Place the cold water temperature sensor clip (blue) on the copper cold water pipe.
2. Place the hot water temperature sensor clip (red) on the copper hot water pipe.
iB301 / iB3001 Electrical 14
November 2017 - Revision 00
3. Attach one end of the 14 foot long wire harness to the sensor clip and the other end into the appropriate cold water or hot water port on the unit.
Note: Do not cross the wires or the temperature readings
will be reversed.
8.3 How to Test Carbon Monoxide Alarm
1. Press and hold the test/reset button.
8.4 Mobile Application
The unit gathers and has the capability to send data to Intellihot on its monitored functions. The monitored data includes inlet and outlet water temperatures and pH values. It also sends leak detection data for gas, carbon monoxide, and water. Using this services allows the unit to communicate any problems or error codes with Intellihot which in turn automatically sends the appropriate notifications to the user through the app or an email.
1. Download the telliBot app, available on both iOS and Android devices.
Note: Installing the app will guide the user to connect the
telliBot to the Internet. Once connected, the Intellihot will automatically monitor the unit and notify the user with appropriate messages.
2. For new users, create an account by selecting “Need an Account?” and follow the prompts.
2. Once a beeping (chirping) sound is heard, release the test button.
3. Wait for 10 seconds.
4. Listen for the audible code:
a. If sensor is working correctly the sound of two
consecutive short chirps with one second between the chirps will be heard.
b. If sensor is NOT working correctly the continuous
sound of one short chirp every thirty seconds will be heard.
5. If the carbon monoxide sensor fails, the entire telliBot unit must be replaced.
3. Once connected to the Internet, the unit sends operating information to the app allowing the user to monitor the system.
15 iB301 / iB3001 Electrical
October 2017 - Revision 00
4. Unit’s app screens.
iB301 / iB3001 Electrical 16
November 2017 - Revision 00
9. Maintenance
9.1 Neutralizer Media
The usage and replacement of the neutralizer media can be monitored by a factory representative by subscribing to the telliBot Monitoring Service. Notification is automatically sent to the user through the app or by email prior to the time of the neutralizer media bag needing replacement.
The unit provides the user with visual and audible signals whenever the neutralizer media bag must be replace. Refer to Alarm Characteristics section in this manual to know more about telliBot’s alarms.
Once the user is subscribed to the service, a neutralizer media bag is shipped, free of charge, in advance by predicting the usage of media.
9.2 Replacement Procedure
SAFETY INSTRUCTIONS
The use of protective rubber or plastic gloves, low level respirator mask, and eye protection to replace the media is recommended.
3. Remove the cover from the neutralizer media compartment.
4. Remove the used neutralizer media bag.
1. Remove the power supply adapter from the electrical outlet.
2. Open the top cover of the unit by lifting the right side, as viewed from the front. The cover is hinged on the left side.
5. Place the new neutralizer media bag inside compartment.
6. Make sure the inlet and outlet water slots in the bottom of the neutralizer media container are not blocked.
7. If necessary, fill the compartment with tap water.
8. Replace the media compartment cover and close the top cover.
9. Dispose the used condensate neutralizer media bag properly and obey local disposal codes. In most cases, the bag can be disposed of with daily garbage going to the landfill.
17 iB301 / iB3001 Electrical
October 2017 - Revision 00
10. Troubleshooting
10.1 Troubleshooting Guide
Description Alert Remedy
No Power
Unit is not working. Is the power supply adapter
plugged into the electrical receptacle?
Is the power supply connector plugged into the Power port on the side of the unit?
Does the receptacle have power?
Is the power supply damaged in any way?
pH Sensor
Detects pH value when less than
5 for 1 hour or more.
pH sensor is not providing a
reading or seems to provide an inaccurate reading.
• Flashes red and white (1 second ON and 1 second OFF) and/or
• 0.05 seconds ON and 0.05 OFF every 30 seconds (four chirps)
Is wire, plug, or sensor damaged?
Is sensor connected to circuit board?
Sensor is malfunctioning?
Plug the adapter into the receptacle.
Plug the power supply connector into the side of the unit.
Check electrical panel fuse or circuit breaker. Replace the power supply adapter.
• Replace the media bag and resume operation.
• Plug sensor into circuit board connector.
• Replace telliBot.
Temperature / Flow Sensor
Temperature sensor is not
providing a reading or seems to provide an inaccurate reading.
CO Sensor
Detecting elevated levels of CO
(carbon monoxide).
• 70 ±5 for 60 to 240 minutes.
• 150±5 for 10 to 50 minutes.
• 400±10 for 4 to 15 minutes.
Sensor is not working. • Audible only – Chirps once 0.05
Gas Sensor
Detects gas level is between 5%
and 25%.
Sensor is not working. • Audible only – Chirps twice 0.5
Is wire, plug, or sensor pad cut or corroded?
Is sensor placed on top of COPPER pipes?
Sensor is malfunctioning?
• Visual – Flashes red and white (1 second ON and 1 second OFF) and/or
• Audible – Chirps 0.01 seconds ON and 0.01 OFF for four cycles and repeats every 5 seconds.
seconds every 30 seconds.
• Visual – Flashes red and white (1 second ON and 1 second OFF) and/or
• Audible – Chirps 0.5 seconds ON and 0.5 OFF continuously.
seconds ON and 0.5 OFF and repeats every 30 seconds.
• Attach sensor to COPPER pipes.
• Replace telliBot.
• De-energizes gas and water valves if optional kits are installed. Turns OFF gas fired unit if Boiler Interlock Switch is connected.
• Correct cause of high CO levels and resume operation.
Replace telliBot.
• De-energizes gas valve if optional kit is installed.
• Correct cause of high gas levels and resume operation.
Replace telliBot.
iB301 / iB3001 Troubleshooting 18
November 2017 - Revision 00
Description Alert Remedy
Water Sensor
Detects water leak. • Visual – Flashes red and white
(1 second ON and 1 second OFF) and/or
• De-energizes water valve if optional kit is installed.
• Correct cause of water leak, allow sensor to dry completely and resume operation.
• Audible – Chirps three times 0.5 seconds ON and 0.5 OFF and repeats every 30 seconds.
Sensor is not working. Replace telliBot.
Wi-Fi Connection
Wi-Fi is connected. • Visual – Continuous white light
and
• Audible – None.
Wi-Fi is not connected. • Visual – Flashes blue and white
(1 second ON and 1 second OFF)
Gas and water valves are energized and gas fired unit is not isolated.
and
• Audible – None.
Wi-Fi is connected, but unit is not
working properly.
• Is unit set up using the telliBot app?
• Was correct network password
Download app and follow connection instructions.
Enter correct password.
entered?
• Was network password changed
Enter correct password.
after unit was set up?
Is network offline.
Wi-Fi signal strength is weak.
Unit is still not working correctly.
Restore network connection. Increase signal, remove blockages, or move router closer to
tellibot Contact service technician.
19 iB301 / iB3001 Troubleshooting
October 2017 - Revision 00
11. Warranty
11.1 Warranty
General
This unit is warranted by Intellihot, and covers defects in the materials and workmanship. The warranty effective start begins on the date of installation or on the date of possession in the case of new construction.
This warranty is extended to the original purchaser and any subsequent owner at the original install location, and applies only when properly installed by a licensed contractor and operated in accordance with the instruction manuals. This warranty is limited to repairs or replacement of parts, at Intellihot’s option that are proven to be defective under normal use.
The warranty period for any original parts against failure is 1 year from the effective start date. A replacement part will be warranted for the unexpired term of the original warranty. Defective parts submitted may not be returned. No returns will be accepted without prior authorization from Intellihot.
Shipping Costs
If a replacement part is supplied under the terms of this warranty, Intellihot will provide ground service delivery for the part free of charge. Any expedited shipping expense will be paid by the customer.
Not Covered by this Warranty
This warranty does not cover failures or problems due to:
• Failure to install in accordance applicable building codes, ordinance, normal plumbing and electrical trade practices
• Improper installation, improper use, improper maintenance, improperly made replacements or repairs, accidents or abuse
• Sediment deposits, fire, flood, lightning, freezing and acts of God or any causes other than defects in materials and workmanship
This warranty will be void and have no effect if:
• The unit is modified or altered in any way
• Appliances or equipment attached to the unit that
have not been approved by Intellihot, Inc.
• The serial number is altered, defaced, or discarded
Warranty Limitations
This warranty applies only when the unit is used in the United States or Canada. Except for the limited warranties provided above, Intellihot Inc. disclaims all other warranties, including but not limited to warranties or merchantability and fitness for a purpose; provided however, that implied warranties or merchantability and fitness for a purpose are not disclaimed during the one-year period from the effective date. Intellihot shall not be liable for indirect, special, incidental, consequential, or other similar damages, including lost profits, arising from or relating to the unit. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
How to Make a Claim
Please Call (877) 835-1705. Proof of purchase in the form of a dated sales receipt or warranty registration should be included with your claim. The product owner should submit the warranty claim directly to Intellihot at the following address:
Intellihot Inc. Attn: Warranty Claims 2900 W. Main St. Galesburg, IL 61401
All parts claimed to be defective may be requested to be returned to Intellihot for examination prior to full claim settlement. Please include the following information on your warranty claim:
• Model number and serial number of the unit.
• Date of original purchase.
• Owner’s name and address.
• A description of the problem with the part and unit.
iB301 / iB3001 Troubleshooting 20
November 2017 - Revision 00
12. Product Warranty Card
12.1 Warranty Card
To facilitate service, please fill out the information in the form below and mail to the following address:
Warranty Registration Intellihot Inc. 2900 W. Main Street Galesburg, IL 61401
Make a copy or cut here to remove page.
Model: _____________________________________________________
Serial Numbers (up to 4):
______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________
Owner Information:
Name: _______________________________________________________ Address: ______________________________________________________ City, State, Postal Code: _______________________________________ Phone Number: _______________________________________________
Dealer Information:
Sold By: _____________________________________________________ Address: ______________________________________________________ City, State, Postal Code: _______________________________________ Phone Number: _______________________________________________
21 iB301 / iB3001 Troubleshooting
October 2017 - Revision 00
iB301 / iB3001 Troubleshooting 22
November 2017 - Revision 00
Revised 11-2017
Part#: IGT-MNL0031