(Caractéristiques et renseignements de sécurité à l'intérieur)
Y PRESET FOR USE WITH
(POUR INSTALLA
GES D'USINE POUR UTILISATION AVEC
A
tic Instantaneous
GL
FACTOR
RÉRÉ
TURAL GAS
P
L
ALLATION ONLY
ent Automa
NA
GAZ NATURE
. . . . . . . . . . . . . . . .
:
: Btu/hr Maximu
de gaz)
Direct-V
olt, 60 Hz, 5 Amps
(Type
Btu/hr Minimum . . .
FOR INDOOR INST
120 V
. . . . . . . . . . . .
(Entrer le Classement)
. . . . . . . . . . . .
Type of Gas
Input Rating
. . . . . . . . . . . . .
minimum (pour ajustements))
Maximum Inlet Gas Pressure:
(Pression de gaz d'arrivée maximum)
. . . . . . . . . . . . .
Minimum Inlet Gas Pressure:
(Pression de gaz d'arrivée minimum)
de gaz d'arrivée
ter Pressure:
. . . . . . . .
Wa
Minimum Inlet Gas Pressure (for adjustments): . .
(Pression
ter Pressure:
. . . . . . . . . . . . . . . . . .
Wa
Maximum
(Pression d'eau maximum)
Energy Factor:
Minimum
(Pression d'eau minimum)
ciency / :
. . . . . . . . . . . . . . . . . .
Recovery Rating:
(Caractéristique de recouvrement)
Thermal Effi
(Efficacité thermique / Facteur énergétique)
NOx Emissions:
From
Minimum Clearances
(Dégagements minimums)
(Émissions de NOx)
(Pursuant to South Coast Air Quality Management District Rule 1
Non-Combustibles
(conformément au règlement 1146.2 du "South Coast Air Quality Management District)
(Des non-combustibles)
2 in (50.8 mm)
5/8 in (15.8 mm)
6 in (15.2 cm)
Top of heater
1/2 in (12.7 mm)
(Dessus du chauffe-eau)
12 in (30.4 cm)
Back of heater
(Arrière du chauffe-eau)
Front of heater
(Avantdu chauffe-eau)
(Côté)
Side
Bottom of cabinet
(Côté canalisation)
From Combustible
5/8 in (15.8 mm)
m
146.2)
Construction
(D'une construction
combustible)
6 in (15.2 cm)
6 in (15.2 cm)
2 in (50.8 mm)
12 in (30.4 cm)
Wat
TION À L'INTÉRIEUR SEULEMENT)
. . .
(Chauffe-eau au
ter
er Hea
al Gas
Factory Preset
tur
Na
glage en usine pour gaz naturel)
(Ré
199,000
C. (3.20 kPa)
20,000
13.0 W.
W.C. (2.00 kPa)
8.0
W.C. (2.00 kPa)
8.0
150 psi (1034 kPa)
15 psi (103 kPa)
265 GPH (1003 LPH)
0.94)
98 % /
u'à
Up to 98% / 0.94
(Jusq
Less than 20 ppm
(Moins de 20 ppm)
Serial Number:
(Numéro de série)
Intellihot Green Technologies Inc
2900 W. Main St.
(877) 835- 1705
Galesburg, IL 61401
info@intellihot.com
.intellihot.com
Phone:
www
Email:
b:
We
Check
Converted to
Propane
Cocher la case si
nstantané à ventilation
tomatique i
Field Conver
sion* sur place au gaz p
r
Propane Gas
nve
o
C
(
199,000
20,000
10.5 W.
C. (0.76 kPa)
3.0 W.
W.
11.0
150 psi (1034 kPa)
15 psi (103 kPa)
265 GPH (1003 LPH)
98 % / 0.9
u'à
q
Up to 98% / 0.94
s
u
(J
Less than 20 ppm
oins de 20 ppm)
Installation and Op
(M
*Refer to
manual for c
(Se référer au manuel d'installation et
de fonctionnement pour la procédure de
conversion.)
ETL STICKER
.
Box if
ropane
az p
te)
Gas
direc
converti au g
sion* to
ropane)
C. (2.62 kPa)
C. (2.74 kPa)
)
4
eration
ocedure.
n pr
nversio
o
(Collant ETL)
IGT-LBL-0005-01
To avoid product damage, personal injury, or
even possible death, carefully read, understand,
and follow all the instructions in the Installation
and the Operation manuals before installing this
product. Improper installation, adjustment, alteration, or
maintenance can cause injury, loss of life, and/or property
damage. This water heater should be installed and
serviced by a qualifi ed technician. The lack of proper
service can result in a dangerous condition.
This manual contains safety information, installation
instructions, and maintenance procedures. It must be left
with the homeowner or placed near the water heater in a
noncombustible place. The homeowner should retain this
manual for future reference.
WARNING
If the information in these instructions is not followed
exactly, a fire or explosion could result causing
property damage, personal injury, or death.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
— Installation and service must be performed by
a qualified installer, service agency, or the gas
supplier.
If the information in these instructions is not followed
exactly, a fire or explosion could result causing
property damage, personal injury, or death.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
• Evacuate all persons from the vehicle.
• Shut off the gas supply at the gas container or
source.
• Do not touch any electrical switch, or use any phone
or radio in the vehicle.
• Do not start the vehicle’s engine or electric generator.
• Contact the nearest gas supplier or qualified service
technician for repairs.
• If you cannot reach a gas supplier or qualified service
technician, contact the nearest fire department.
• Do not turn on the gas supply until the gas leak(s)
has been repaired.
— Installation and service must be performed by
a qualified installer, service agency, or the gas
supplier.
WARNING
WHAT TO DO IF YOU SMELL GAS
3OHDVH Fall us first if you have any questions about this
product. We can help you with questions about LQVWDOODWLRQ
and operation, or if there LV damage or missing parts when
you unpack this unit.
&all 877-835-1705 between 7 am and 4 pm Central
time, Monday through Friday, before returning the unit to the
store.
Due to Intellihot’s policy of continuous product DQG
WHFKQRORJ\ improvement, the design and/or technical
specifications are subject to change without notice.
Serial Number: ___________________________________
Date of Installation: ___ / ___ / ______
AVERTISSEMENT
Assurez-vous de bien suivre les instructions données
AVERTISSEMENT
Assurez-vous de bien suivre les instructions données
dans cette notice pour réduire au minimum le
risque d’incendie ou d’explosion ou pour éviter tout
dommage matériel, toute blessure ou la mort.
— Ne pas entreposer ni utiliser d’essence ou
ni d’autres vapeurs ou liquides inflammables
à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous
servir des téléphones se trouvant dans
le bâtiment.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur,
appelez le service des incendies.
— L’installation et l’entretien doivent être assurés
par un installateur ou un service d’entretien
qualifié ou par le fournisseur de gaz.
dans cette notice pour réduire au minimum le
risque d’incendie ou d’explosion ou pour éviter tout
dommage matériel, toute blessure ou la mort.
— Ne pas entreposer ni utiliser d’essence ou
ni d’autres vapeurs ou liquides inflammables
à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ
• Évacuez le véhicule.
• Coupez l’alimentation en gaz au réservoir ou à la
source.
• Ne touchez à aucun interrupteur ; ne pas vous servir
du téléphone ou de la radio du véhicule.
• Ne pas démarrer le moteur du véhicule ni aucune
génératrice électrique.
• Appelez le fournisseur de gaz le plus proche ou un
technicien qualifié.
• Si vous ne pouvez rejoindre ni un fournisseur ni un
technicien qualifié, appelez le service des incendies le
plus proche.
• Ne pas rétablir l’alimentation en gaz tant que la fuite
n’a pas été réparée.
— L’installation et l’entretien doivent être assurés
par un installateur ou un service d’entretien
qualifié ou par le fournisseur de gaz.
To avoid product damage, personal injury, or even
possible death, carefully read, understand, and
follow all the instructions in the Installation and
Operation manual and on the water heater before
installation, operation, or service.
Intellihot cannot anticipate every circumstance that might
involve a potential hazard and our warnings are, therefore, not
all-inclusive. Proper installation, operation, and service is your
responsibility.
You must be satisfied that the operation and settings of the
water heater are safe for you and for others.
Pour éviter un dommage au produit, une blessure personnelle
ou même la mort, lire avec soin, comprendre et suivre toutes
les instructions dans le manuel d'installation et de fonctionnement et sur le chauffe-eau avant l'installation, le fonctionnement ou l'entretien.
Intellihot ne peut pas prévoir toutes les circonstances qui
pourraient impliquer un danger potentiel et par conséquent,
nos avertissements ne comprennent pas tout. L'installation, le
fonctionnement et l'entretien correct sont votre
responsabilité.
Vous devez être certain que le fonctionnement et les réglages
du chauffe-eau sont sécuritaires pour vous et pour les autres.
IGT-LBL-0001-01
SAFETY
Hazards are identifi ed by the “Safety Alert Symbol”
and followed by a signal word such as “DANGER”,
“WARNING”, or “CAUTION”.
DANGER
Indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury. This signal word is limited to
the most extreme situations.
WARNING
Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
Safety Alert Symbols
This is the safety alert symbol. It is used to alert
you to potential personal injury hazards. Obey
all safety messages that follow this symbol to
avoid possible injury or death.
This manual contains DANGERS, SAFETY
INSTRUCTIONS, CAUTIONS, IMPORTANT NOTICES,
and NOTES which must be followed to prevent the
possibility of improper service, damage to the equipment,
personal injury, or death. The following key words call the
readers’ attention to potential hazards.
NOTICE
Indicates that equipment or property damage can result if
instructions are not followed.
SAFETY
INSTRUCTIONS
Safety instructions (or equivalent) signs indicate specific safetyrelated instructions or procedures.
NOTE: Contains additional information important
to a procedure.
IMPORTANT
Indicates that equipment or property damage can
result if instructions are not followed.
NOTE: Provides additional information that is
helpful for installation or operation of the water
heater.
Intellihot Green Technologies, Inc. 5
www.intellihot.com (877-835-1705)
Safety Icon Nomenclature
Icons signal a type of hazard and warn of personal
protection issues, prohibited actions, and hazard
avoidance.
SAFETY
Slipping injury
Tripping injury
Personal Protection
Read the manual
Eye protection
High water temperature
Fill water tank before connecting to electrical
power
Disconnect power
Connect power
Close gas valve
Open gas valve
Wait fi ve minutes
5
Use two people when lifting heavy objects
Prohibited Actions
No open fl ame
Use proper tools
Do not use if submerged under water
No liquid around electrical component
Fire hazard
Explosion hazard
Provide proper ventilation
Operation and Installation Warnings
To avoid serious injury or death, read, understand and
follow all the precautions listed here.
DANGER
Vapors from flammable liquids will explode and can
cause a fire, resulting in personal injury or death. The
water heater has a burner that can come on at any
liquids around the water heater.
for safe operation. Inspect the exterior exhaust gas outlet port and
fresh air inlet port on a regular basis to ensure they are functioning
properly.
the exhaust gases with a fully functional and calibrated flue gas
analyzer.
time and ignite vapors. DO NOT use or store flammable
Improper venting can cause a build-up of carbon monoxide.
Breathing carbon monoxide can result in brain damage or
death. DO NOT operate the water heater unless it is properly
vented to the outside and has an adequate fresh air supply
A concentration of carbon monoxide as small as 0.04% (400
parts per million) in the air can be fatal. When making high
fire
low fire adjustments, CO levels must be monitored
or
using a flue
than 400SSPLVH[FHHGHGDWDQ\WLPHGXULQJRSHUDWLRQ
Adjusting the “low fire offset” or the “main flow restrictor” in
small increments can result in a significant increase in CO
concentration. To avoid serious injury or death, DO NOT
make any adjustments to the gas valve without monitoring
gas analyzer sXFK that D &2 level of no more
Hazard Avoidance
Disconnect power electrical hazard
Electrocution RUVKRFNhazard
Hot liquid, burn hazard
Hot surface
Lifting hazard
Pressurized liquid
Safety alert symbol
WARNING
The Intellihot water heater must be installed by a licensed
plumber, licensed gas fitter, and/or professional service
technician. Improper installation and/or operation can cause
a potentially hazardous situation, which, if not avoided, could
result in serious injury or death, and will void the warranty.
Proper care is your responsibility. Carefully read and
understand the Operation Information in this manual before
operating the Intellihot water heater.
Make sure you know the location of the gas shut-off valve
and how to operate it. Immediately close the gas shut-off
valve if the water heater is subjected to fire, overheating,
flood, physical damage, or any other damaging condition that
might affect the operation of the unit. Have the water heater checked
by a qualified technician before resuming operation.
6Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WARNING
Do not power up the unit unless the gas and water supply
valves are fully opened. Make sure the fresh air intake port
and exhaust gas port are open and functional.
DO NOT attempt to install, service, or repair this water heater
yourself. There are no serviceable parts which can be
changed by the owner. Contact a qualified technician if your
water heater needs repair or maintenance. Ask your gas
supplier for a list of qualified service providers.
Keep the area around the water heater clean and free of all
materials that can burn. DO NOT store or place gasoline, oils,
spray paint, or other flammable products near the water heater.
DO NOT use spray paint, hair spray, or any other flammable
spray near the water heater or near the exterior fresh air inlet
port. DO NOT place any items in or around the exterior
exhaust gas outlet port and/or fresh air inlet port that could
restrict or block the flow in or out of the vent system.
DO NOT store or place newspapers, laundry, or other
combustible items near the water heater or the exterior
exhaust gas outlet and/or fresh air inlet port.
The owner should inspect the system monthly for damage,
water stains, signs of rust, corrosion, and exhaust vent and
air intake blockage. If inspection of the unit shows signs of
damage, the water heater should be shut off until the problem
is repaired by a qualified technician.
DO NOT allow children to operate this unit. DO NOT use this
unit if it does not appear to be operating correctly.
A qualified technician should service and inspect the water
heater annually.
The water heater temperature is factory set to 120°F (49°C).
To avoid scalding, always check the temperature of the hot
water before bathing, showering, washing, etc. DO NOT
adjust the water temperature while the Intellihot water heater
is being used by other persons.
SAFETY
IMPORTANT
Do not use the water heater if any part has
been under water. Immediately call a qualified service
technician and have the unit inspected. Replace any
components that have been under water.
The Intellihot water heater is equipped with a three prong plug. It
should only be plugged directly into a properly grounded three
prong receptacle. DO NOT remove the ground prong from the plug.
DO NOT alter or modify the water heater or water heater controls.
This can be dangerous and will void the warranty.
Intellihot Green Technologies, Inc. 7
www.intellihot.com (877-835-1705)
SAFETY
Always read and follow all warnings on water heater
safety decals and in the manual. If the Installation and
Operation manual is missing, go to www.intellihot.com
or contact Intellihot (877) 835-1705 for a replacement.
DANGER
Use this water heater at your own risk. The outlet
temperature of the Intellihot water heater is factory preset
to 120°F (49°C). The temperature can only be changed by
using the control panel on the front of the water heater.
Hot water temperature over 125°F (52°C) can
cause severe burns instantly or death from
scalding. Children, disabled, and elderly are at
the highest risk of being scalded. Do not leave
children or the infi rm unsupervised. Check
temperature of hot water before taking a shower
or bath. To control water temperature to a
particular faucet, temperature limiting valves can be installed
by your service professional.
WARNING
Do not store or use gasoline or other
fl ammable vapors and liquids in the
vicinity of this or any other appliance.
Flammable vapors can ignite and
cause serious damage or injury.
This water heater is factory preset for NATURAL GAS.
For propane conversion, refer to the manual.
Connecting the water heater to any other gas supply can result
in property damage, serious injury, and even death.
Suitable for water (potable) heating and
space heating. The water heater MUST NOT be
connected to any heating system or components previously
used with a nonpotable water heating appliance.
Do not use toxic chemicals, such as used for boiler
treatment, in potable water space heating systems.
This appliance must be installed in accordance with
local codes or, in the absence of local codes, the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the
CSA B149.1, Natural Gas and Propane Installation Code.
A pressure relief valve complying with the Standard for
Relief Valves for Hot Water Supply Systems, ANSI Z21.22
or CAN1-4.4 Temperature, Pressure, Temperature and Pressure
Relief Valves and Vacuum Relief Valves must be installed in a
proper outlet port of water heater at the time of installation
according to local codes.
No valve is to be placed between the relief valve and the
water heater.
The discharge from the temperature/pressure relief valve
should be directed to the ground or into a drain system
which will prevent a burn hazard or property damage. The
piping must not have a reducing coupling or other restriction
in the discharge line. The discharge line must be installed to
allow complete drainage of both the valve and line.
If the system requires water for space heating at
temperatures higher than required for other uses, a
mixing valve must be installed to temper the water for those
other uses in order to reduce scald hazard potential.
The pressure relief valve must not be removed or
plugged.
Intellihot Green Technologies Inc. Phone: 877-835-1705
www.intellihot.com
Pressure Relief Valve
IGT-LBL-0002-01
FOR YOUR SAFETY READ BEFORE OPERATING
DANGER
If you do not follow these instructions exactly, a fi re or explosion
may result, causing property damage, personal injury, or loss of life.
A.
B.
settle on the fl oor.
C.
service technician. Force or attempted repair may result in a
fi re or explosion.
D.
system and any gas control which has been under water.
If water heater is not operating, follow these instructions. This
appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner manually.
1.
2.
3.
4.
5.
6.
7.
8.
If water heater will not operate, follow instructions “To Turn Off
Gas To Water Heater” and call your service technician or gas
supplier.
1. Turn OFF electrical power to water heater.
2. Turn manual gas shut-off valve to OFF position.
This water heater does not have a pilot. It is
equipped with an ignition device which automatically
lights the burner. Do not try to light burner manually.
BEFORE OPERATING, smell all around the water
heater area for gas. Be sure to smell next to the
fl oor because some gas is heavier than air and will
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone
in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re or police
department.
Use only your hand to turn manual gas shut-off valve.
Never use tools. If manual gas shut-off valve will not
turn by hand, don’t try to repair it, call a qualifi ed
Do not use this water heater if any part has been under
water. Immediately call a qualifi ed service technician
to inspect water heater and replace any part of control
OPERATING INSTRUCTIONS
STOP! Read the safety information above on this
label.
Never use water heater unless it is completely fi lled
with water.
Turn OFF electrical power supply to the water heater.
Turn gas shut-off valve clockwise to “OFF” position.
Do not force.
Wait fi ve (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow step “B” above on this
5
label. If you don’t smell gas, go to next step.
Turn manual gas shut-off valve to “ON” position.
Turn ON electrical power to unit.
Wait until default temperature (120°) is displayed.
Set desired water temperature. Turn on hot water
faucet.
TO TURN OFF GAS TO WATER HEATER
8Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
Toujours lire et suivre tous les avertissements sur les
décalcomanies de sécurité sur le chauffe-eau et dans le
manuel. Si le manuel d'installation et de fonctionnement
n'est pas disponible, visiter le www.intellihot.com ou
contacter Intellihot (877) 835-1705 pour un remplacement.
DANGER
Utiliser ce chauffe-eau à vos propres risques. La température
de sortie du chauffe-eau Intellihot est réglée en usine à 49 °C
(120 °F). La température peut être modifiée seulement en
utilisant le panneau de commande à l'avant du chauffe-eau.
Une température d'eau chaude de plus de 52 °C
(125 °F) peut causer des brûlures sévères instantanément ou la mort par ébouillantage. Les enfants,
les personnes handicapées et les personnes âgées
sont les plus à risque d'être ébouillantées. Ne pas
laisser les enfants ou les infirmes sans supervision.
prendre une douche ou un bain. Des vannes régulatrices de
température peuvent être installées par votre professionnel
d'entretien afin de contrôler la température de l'eau sur un robinet en
particulier.
Vérifier la température de l'eau chaude avant de
AVERTISSEMENT
Ne pas entreposer ou utiliser de gazoline
ou autres vapeurs ou liquides
inflammables à proximité de cet appareil
Vapeurs inflammables
Ce chauffe-eau est préréglé en usine pour le GAZ
NATUREL. Pour la conversion au propane, se référer au
manuel. Connecter le chauffe-au à toute autre alimentation
en gaz peut causer un dommage à la propriété, une blessure
sérieuse et même la mort.
Convient pour le chauffage de l'eau (potable) et le chauffage
des locaux. Le chauffe-eau NE DOIT PAS être connecté à un
système de chauffage ou à des composants utilisés pour un
appareil de chauffage d'eau non potable.
Ne pas utiliser de produits chimiques toxiques, comme
ceux utilisés pour le traitement de chaudière, dans des
systèmes de chauffage de locaux et d'eau potable.
Cet appareil doit être installé conformément aux codes
locaux, ou , en l'absence de codes locaux, selon le National
Fuel Gas Code, ANSI Z223.1/NFPA 54 ou le Code
d'installation du gaz naturel et du propane, CSA B149.1.
Une soupape de surpression conforme à la norme Relief
Valves for Hot Water Supply Systems, ANSI Z21.22 ou
CAN1-4.4 Temperature, Pressure, Temperature and
Pressure Relief Valves and Vacuum Relief Valves doit être
installée dans le bon port de sortie du chauffe-eau au moment de
l'installation conformément aux codes locaux.
Aucune vanne ne doit être placée entre la soupape de
surpression et le chauffe-eau.
La décharge de la soupape de température/surpression
devrait être dirigée vers le sol ou dans un système de drain
qui empêchera un risque de brûlure ou un dommage à la
propriété. La tuyauterie ne doit contenir aucun raccord réducteur
ou autre restriction dans la ligne de décharge. La ligne de
décharge doit être installée afin de permettre un drainage complet
de la vanne et de la ligne.
Si le système exige de l'eau pour le chauffage de locaux à
des températures plus élevées que celles pour d'autres
usages, une vanne de mélange doit être installée pour
tempérer l'eau pour ces autres usages afin de réduire la possibilité de blessure par ébouillantage.
La soupape de surpression ne doit pas être retirée ou
bouchée.
Intellihot Green Technologies Inc.Téléphone: 877-835 1705
www.intellihot.com
Intellihot Green Technologies, Inc. 9
www.intellihot.com (877-835-1705)
ou autre. Les vapeurs inflammables
peuvent s'enflammer et causer un
dommage sérieux ou une blessure.
Soupape de surpression
GT-LBL-0003-01
SAFETY
POUR VOTRE SÉCURITÉ, LIRE AVANT D'UTILISER
DANGER
Si vous ne suivez pas ces instructions exactement, un incendie ou
une explosion pourrait résulter causant des dommages à la
propriété, une blessure personnelle ou une perte de vie.
Ce chauffe-eau n'a pas de pilote. Il est muni d'un
A.
B.
• Ne pas essayer d'allumer aucun appareil.
• Ne toucher aucun interrupteur électrique; n'utiliser aucun
• Appeler immédiatement votre fournisseur de gaz à partir du
• Si vous ne pouvez pas rejoindre votre fournisseur de gaz, appeler
C.
D.
Si le chauffe-eau ne fonctionne pas, suivre ces instructions. Cet
appareil est muni d'un dispositif d'allumage qui allume automatiquement le brûleur. Ne pas essayer d'allumer le brûleur manuellement.
1.
2.
3.
4.
5.
6.
7.
8.
Si le chauffe-eau ne fonctionne pas, suivre les instructions
« Pour arrêter l'alimentation en gaz au chauffe-eau » et appeler
votre technicien d'entretien ou votre fournisseur de gaz.
1. METTRE HORS FONCTION l'alimentation électrique au chauffe-eau.
2. Tourner la vanne d'arrêt manuelle du gaz à la position d'arrêt (OFF).
dispositif d'allumage qui allume automatiquement
le brûleur. Ne pas essayer d'allumer le brûleur
manuellement.
AVANT D'UTILISER, sentir tout autour du chauffe-eau
pour détecter une odeur de gaz. S'assurer de sentir
près du plancher parce que certains gaz sont plus
lourds que l'air et retombent sur le plancher.
QUE FAIRE SI VOUS SENTEZ DU GAZ
téléphone dans votre édifice.
téléphone d'un voisin. Suivre les instructions du fournisseur de gaz.
le service d'incendie ou de police.
Utiliser seulement votre main pour tourner la vanne
d'arrêt manuelle du gaz. Ne jamais utiliser d'outils. Si la
vanne d'arrêt manuelle du gaz ne peut pas être tournée
à la main, ne pas essayer de la réparer, appeler un
technicien d'entretien qualifié. Une réparation forcée ou tentée
pourrait causer un incendie ou une explosion.
Ne pas utiliser ce chauffe-eau si une partie de celui-ci a
été sous l'eau. Appeler immédiatement un technicien
d'entretien qualifié pour inspecter le chauffe-eau et
remplacer toute partie du système de commande et
toute commande de gaz qui a été sous l'eau.
INSTRUCTIONS DE FONCTIONNEMENT
ARRÊTEZ! Lire les renseignements de sécurité
ci-dessus sur cette étiquette.
Ne jamais utiliser le chauffe-eau à moins qu'il soit
entièrement rempli d'eau.
METTRE HORS FONCTION l'alimentation électrique au
chauffe-eau.
Tourner la vanne d'arrêt manuelle du gaz dans le sens
des aiguilles d'une montre à la position d'arrêt (OFF).
Ne pas forcer.
Attendre cinq (5) minutes pour laisser le gaz s'évaporer.
Si vous sentez du gaz, ARRÊTEZ! Suivre l'étape « B »
ci-dessus sur cette étiquette. Si vous ne sentez pas de
5
gaz, passer à l'étape suivante.
Tourner la vanne d'arrêt manuelle du gaz à la position
de fonctionnement (ON).
METTRE EN FONCTION l'alimentation électrique à
l'appareil
Attendre jusqu'à ce que la température
par défaut (120°) soit affichée. Régler la température
désirée pour l'eau. Ouvrir le robinet d'eau chaude.
POUR ARRÊTER L'ALIMENTATION
EN GAZ AU CHAUFFE-EAU
g
TECHNICAL SPECIFICATIONS
Parameters
Type
Fuel
i200i200Pi250i250P
Indoor, Wall hung, Fully Condensing
Preset for NG / LP Convertible
Models
Minimum / Maximum Input (Btu/h)
Combustion Efficiency
98%
Thermal Efficiency
Energy Factor
Dimensions H x W x D (inches)
Water Inlet / Outlet Connection
Gas Inlet Connection
Minmum Flow Rate
Ignition
Venting Type
Venting Materials
Max 3” Vent Length - Single Pipe / Power Vent
Max 3” Vent Length - Two pipe / Direct Vent
Max 2” Vent Length - Single Pipe / Power Vent
(2” not allowed at elevations above 4,000 ft)
Max 2” Vent Length - Two Pipe / Direct Vent (2”
not allowed at elevations above 4,000 ft)
Common Venting
No minimum flow rate for "P" models / 0.6 GPM
Direct Vent (2 pipe - intake & exhaust), Power vent (1 pipe - exhaust only)
Note: Reduce the maximum equivalent length above by 5 feet per 90° elbow used and by 2 feet per 45° elbow.
Do not exceed the above set limits.
Intellihot Green Technologies, Inc. 11
www.intellihot.com (877-835-1705)
EXHAUST
HOT WATER
OUT
GAS LINE
CHECK
VALVE
TEMPERATURE
AND PRESSURE
VALVE
CHECK
VALVE
INLET
SPECIFICATIONS (NOMENCLATURE)
HOT WATER
COLD WATER
INLET
GATE VALVE
GAS LINE
WATER TRAP
STRAINER
TO USAGE
POINT
CHECK
VALVE
GAS
LINE
COLD WATER
IN
Safety
in
f
o
rm
a
ti
on
a
n
d
w
i
r
in
g
d
i
a
g
r
a
m
i
nsi
de
o
f fro
nt
c
o
ver
.
CONTROL
PANEL
WATER HEATER
DRAIN VALVE
IH-01
CONDENSATE
DRAIN
Typical installation of i200P piped with storage tank.
DIP Switch Locations on Control Board
Sa
f
ety inf
or
mat
i
o
n
a
n
d wi
ring
di
ag
ra
m
i
n
s
i
d
e
o
f
f
ront
c
over.
WATER
STORAGE
TANK
HOT
DIP Switch Settings
SW
SW
Cascade 7HUPLQDWLRQ21
(7HUPLQDLVRQHQFDVFDGH21)
(Réglages des commutateurs DIP)
Propane
Natural Gas
(Gaz naturel)
&DVFDGH7HUPLQDWLRQ2))
7HUPLQDLVRQHQFDVFDGH2))
12Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
DIMENSIONAL SPECIFICATIONS
Selecting a Location
IH-79
68,86
[2 3/4”]
155,4
[6 1/8”]
35,36
[1 3/8”]
442,6
[17 7/16”]
Top View
Left
Side
Side
Right
Bottom View
59,11
[2 5/16”]
Out
3/4 NPT
Hot Water
Exhaust Port
3” PVC
64,6
[2 9/16”]
3/4 NPT
Gas Inlet
102,4
[4 1/8”]
185,1
[7 5/16”]
57,79
[2 1/4”]
347,3
361 ,3
[14 1/4”]
[13 11/16”]
14
Mounting
Wall Surface
Intellihot Green Technologies, Inc. 13
www.intellihot.com (877-835-1705)
[9/16”]
198,7
[7 25/32”]
Drain Port/PRV
107,1
[4 7/32”]
Front View
3/4-NPT
Power Cord
Condensate Drain
59,94
[2 3/8”]
L/H Side View
QUICK REFERENCE INSTALLATION GUIDE
The quick reference illustrations show the installation
of two i200P water heaters connected together with a
storage tank. Installation of a single unit or up to five
units is basically the same. When installing multiple
units, refer to the Multiple Units section for additional
information.
1. Select a location. Note that the piping can be
confi gured to enter or exit the unit from either the left or
right side, as viewed from the front.
2. Mount the water heater(s) to the wall.
a.
Attach two 2x4 mounting blocks (at least 23” for a
single unit or 46” long for two units) to the wall. The
uppermost mounting bRDUGV should be at the
desiredheight for the top of the unit.
IH-80
e. Hang the unit on the mounting bracket. If multiple
units are installed, the spacing between the units
should be approximately 6”.
Safety
i
nformati
on
and
wi
ri
ng
diagram inside o
f
fron
t
c
o
v
er.
Safety information and wirin
g d
iagram inside of
front co
ver.
3. Install the gas lines, as shown in the illustration.
IH-81
b.
Attach a second mounting block 1”FHQWHUWRFHQWHUbelow the upper mounting block.
c. Attach metal mounting bracket(s) to the upper
mounting block approximately 3” on either side
of the center and 1/2” down from the top of the
mounting block.
d.
$GMXVWDQGWLJWKHQWKHERWWRPEUDFNHWWRWKHXQLWVVR
WKDW the unitto hangV vertically on the wall.
Safety information and wiri
ng diagram inside o
f front cover.
Safety information a
nd wiring diagram i
nside of front cover.
IH-82
a. Temporarily place a short section of 3” schedule
40 PVC pipe on one of the air inlets in order to
judge clearance allowances as the gas piping is
assembled.
b. Due to limited wall clearance, connect the union as
your fi nal step of gas piping.
c. Check for gas leaks at this point in the assembly
process.
14Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
QUICK REFERENCE INSTALLATION GUIDE
Water Connections
4. Install the combustion air inlet and fl ue gas outlet PVC
piping.
Note: The inlet and outlet pipes from the unit are
3” diameter while the header piping is 4” diameter,
as shown in the illustration. The larger header
piping is required whenever multiple units are
installed.
Safety information an
d wiring diagram insid
e o
f front cover.
Safety information and wiring diagram inside of front cover.
IH-83
6. Install and connect the cold water lines.
S
a
f
e
t
y
i
n
f
o
r
m
a
t
i
o
n an
d
w
ir
in
g dia
g
r
a
m
in
s
ide
of
f
ron
t
c
ove
r
.
S
a
f
e
t
y
in
form
a
tion
a
n
d w
iri
n
g
d
ia
g
ra
m
in
side o
f
f
ro
n
t c
o
ve
r
.
IH-85
7. Connect and route the condensate trap and drain line
to an appropriate discharge site or drain.
5. Install and connect the hot water lines. If an optional
hot water storage tank is required, connect the hot
water lines to this tank. If required, install a pressure
relief valve or a temperature and pressure relief valve.
IH-84
Safety information a
nd wi
ring dia
g
ra
m inside of
front cov
er.
Safety informatio
n and wiri
ng
d
i
agram insid
e o
f
f
ront
cover.
S
afet
y inform
ation and
w
ir
ing
diag
r
am insid
e of
front cove
r
.
Safet
y info
r
ma
tion and wiring diag
ra
m
inside of
fr
ont
cov
er.
IH-85a
8. Verify gas pressure.
9. Connect the 120 Volt power supply.
10. Test fi re the unit by opening all hot water faucets.
Intellihot Green Technologies, Inc. 15
www.intellihot.com (877-835-1705)
Gas Connection
PREPARATION BEFORE INSTALLATION
Selecting an Installation Site
IMPORTANT
When installing this water heater, follow all local
building codes and the current edition of the National
Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or
National Gas and Propane Installation Code (CAN/CGA
B149.1) in Canada, when installing this product.
1. Select an interior location for the installation. Each
installation is unique; therefore, take the time to fi nd the
best location for the water heater.
a. Install the water heater near locations that use hot
water, such as bathroom, kitchen, or laundry room
faucets.
b. Select a location that minimizes the length of the
water pipe.
c. If the distances are long or if the faucet or appliance
requires “instant” hot water, we recommend running
a recirculation line back to the water heater from the
furthest fi xture. Insulate the hot water supply and
recirculation lines.
d. Select a location away from foot traffi c and away
from areas where dust, debris, chemical agents, or
other combustible materials could accumulate.
e. Allow suffi cient space for service and maintenance
access to all gas, water, and drain connections.
f. Make sure the location meets all building code
requirements.
IMPORTANT
Reduce the maximum equivalent length by 5 feet
per 90° elbow and by 2 feet per 45° elbow. Intake
and exhaust venting pipes have the same allowable
lengths. Do not exceed these set limits.
EXAMPLE: A 3” vent line or fresh air intake line
(Model i200) with the six 90 degree elbows would
be limited to a length of 70 feet in a WZLQSLSH
FRQILJXUDWLRQ
3. Locate the unit close to a drain and near gas and water
connections.
The water heater produces a signifi cant amount of
condensate during normal operation and should be
located near a suitable drain where damage from
a possible leak will be minimal. Installing the water
heater in a location without a drain will void the
warranty and Intellihot will not be responsible for
any resulting water damages that may occur as a
result. For additional information, refer to the Install
Condensate Drain section.
The water heater should be located in an area where
leakage from the unit or water pipes will not result in
damage to the area around the appliance or to lower
fl oors of the structure. When such locations cannot
be avoided, it is recommended that a suitable drain
pan, adequately drained, be installed under the water
heater. The pan must not restrict combustion air fl ow.
g. Make sure the wall surface the water heater is
mounted onto will support the weight of the unit.
SAFETY
INSTRUCTIONS
The Intellihot i200 and i250 water heaters weigh 90 lbs. The i200P
and i250P weigh 98 lbs.
2. Minimize the distance that the exhaust gas vent and
fresh air intake must travel to an exterior wall.
a. The exhaust vent outlet must not be located next to
a walkway, near soffi t vents, crawl space vents, or
other areas where condensate (water vapor) could
cause damage or create a hazard.
b. The fresh air inlet vent must be located at least 12”
from the exhaust vent.
c. Contaminated or dirty air drawn into the intake
pipe can damage the water heater. The Intellihot
warranty does not cover damage caused by
airborne contaminants.
16Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
PREPARATION BEFORE INSTALLATION
4. Locate the water heater and all water pipes in an area
where the ambient temperature always remains above
freezing.
NOTICE
In cold climates, if there is a power failure, the unit’s
freeze protection system will not operate, and can
result in water freezing inside the heat exchanger.
To prevent damage to the water heater, turn OFF the gas
supply and inlet water valve. Open the drain valve and
completely drain the unit.
Damage caused by freezing water is not covered by the
Intellihot warranty.
a. When the water heater is connected to an electrical
power supply, it will automatically prevent the water
inside the unit from freezing.
b. The unit’s freeze protection system will not prevent
the water in surrounding pipes from freezing.
5. Select an appropriate location for the combustion air
and exhaust pipes to exit the house. Use the diagram
and chart on the next page to make this determination.
High Elevation Installations
For operation at elevations above ,00 feet, Intellihot
model ratings should be reduced by 4% for each 1,000
feet above sea level.
Water Quality
3RWDEOHZDWHULVGHILQHGDVGULQNDEOHZDWHUVXSSOLHGIURP
XWLOLW\RUZHOOZDWHULQFRPSOLDQFHZLWK(3$VHFRQGDU\
PD[LPXPFRQWDPLQDQWOHYHOV&)5SDUWDV
VKRZQLQWKHWDEOHEHORZ,I\RXUZDWHUFRQWDLQV
FRQWDPLQDQWVKLJKHUWKDQRXWOLQHGE\(3$WKHQZDWHU
WUHDWPHQWLVUHFRPPHQGHGDQGDGGLWLRQDOPDLQWDLQHQFH
PD\EHUHTXLUHGIf you suspect that your water is
contaminated in any wayRUZDWHUKHDWHUHUURUVRFFXU,
discontinue use of the water heater and contact an
authorized technician or licensed professional.
ContaminantMaximum Allowable Level
Total Hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5-8.5
Sulfate205 mg/l
Total Dissolved Solids (TDS)500 mg/l
Zinc205 mg/l
Intellihot Green Technologies, Inc. 17
www.intellihot.com (877-835-1705)
Venting Connections
D
IH-31
V
G
A
Inside Corner
Detail
E
V
Air Inside Inlet
X
V
Vent Terminal
Area Where Terminal is Not Permitted
PREPARATION BEFORE INSTALLATION
H
V
Closed
A
Fixed
J
B
V
I
X
Operable
Fixed
Closed
C
V
V
F
B
L
B
V
Operable
B
B
B
M
V
X
V
K
ANSI Z223.1 / NFPA 54 for USA and CAN/CSA B149.1 for Canada - Venting Requirements
USA Clearance Canada Clearance
Item Description Specification Specification
A Above grade, veranda, porch, deck, or balcony 1 ft 1 ft
B Window or door that may be opened 1 ft** 3 ft
C Permanently closed window * *
D Vertical clearance to a ventilated soffit, eves, or overhang 3 ft*** *
E Unventilated soffit, eves, or overhang 3 ft*** *
F Outside corner * *
G Inside corner * *
H Each side of centerline extended from meter/regulator * 3 ft within a height 15 ft above the
meter/regulator assembly
I Service regulator vent outlet * 3 ft
J Non mechanical air supply inlet or combustion air inlet
to any other appliance 1 ft** 3 ft
K Mechanical air supply inlet 3 ft above if 6 ft
within 10 ft
horizontally
L Above paved sidewalk or paved driveway on public property * 7 ft
M Under veranda, porch, deck, or balcony * 1 ft
*
Not specified in ANSI Z223.1 / NFPA 54 or CAN/CGA-B146.
Use clearances in accordance with local building codes and local gas supplier.
**
4 feet (1.2 m) below or to the side of opening and 1 foot (300 mm) above opening.
*** Intellihot recommendation.
18Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WALL MOUNTING
Secure the unit to the wall using either two wood
mounting blocks or one piece of 3/4” plywood, as
described in this section.
Mounting Block Installation Method
1. Attach two 2x4 or 2x6 mounting blocks (horizontal
framing), at least 18 inches long, to the wall.
a. In wood or steel construction, use adequate wood/
metal screws and secure the mounting blocks with
at least two screws in each vertical wall stud (four
screws total).
b. In concrete block or solid concrete wall construction,
attach the mounting blocks with at least four
masonry screws or suitable masonry wall anchors in
each mounting block.
IH-26
1
2
CAUTION
Lifting Hazard
According to the National Institute for Occupational
Safety and Health, the recommended maximum safe
lifting weight is 51 pounds, with all lifting conditions perfect—
minimal forward reach, steady load close to the body, straight back,
load between knees and shoulders, and good grips. To avoid
personal injury, always use these proper lifting techniques and use
two people to move the water heater which weighs 80 pounds.
3. With assistance, hang the unit on the upper wall
bracket, interlocking bracket (1) on the back of the unit
and wall bracket (2).
4. Install two appropriately sized wood screws in lower
bracket (3) to secure the unit to the wall.
5. Make sure the unit is plumb and level and tighten the
four sheet metal screws on bottom bracket (3). When
properly installed, there should be a 5/8” air space
between the back of the water heater and the mounting
blocks.
21”
3
2. Level upper bracket (2) and attach it to the mounting
block with at least four appropriately sized wood
screws (do not use drywall screws).
SAFETY
INSTRUCTIONS
The Intellihot water heaters weigh 90 to 100 lbs (40.8 to 45.4 kg)
and must be securely attached to the wall. Mounting hardware is
included and should be used to mount the unit.
Plywood Installation Method
1. Mount a piece of 3/4” plywood (at least 32” high x 20”
wide) to the wall.
a. In wood or steel construction, use adequate wood/
metal screws and secure the plywood with at least
two screws in each vertical wall stud.
b. In concrete block or solid concrete wall construction,
attach the plywood with at least four masonry
screws or suitable masonry wall anchors.
IH-27
1
20”
2
8”
32”
Intellihot Green Technologies, Inc. 19
www.intellihot.com (877-835-1705)
3
2. Follow Steps 2 through 5 in the above procedure to
complete the installation.
GAS CONNECTION
WARNING
FIRE AND/OR EXPLOSION HAZARD
To avoid serious injury or even death, the gas line
installation and the gas line inlet pressure test
must be done by a licensed professional.
Always match the water heater with the type of gas supplied to the
unit (natural gas or LP gas). The water heater is factory preset for
natural gas.
Make sure the gas line pressures are within normal limits. Pressures
outside normal limits can result in poor performance and hazardous
operating conditions.
1. Determine if the Intellihot water heater will use natural
gas (factory preset) or LP (propane) gas.
a. To convert the unit to propane, refer to the Propane
(LPG) Conversion section in this manual.
b. Make sure your gas supply matches the rating decal
located on the side of the water heater.
2. Make sure the gas pressure meets the requirements
for the unit, as shown in the tables.
b. Measure the length of the gas supply line from the
gas meter to the water heater or other appliances
requiring gas.
c. Use the Gas Pipe Sizing tables in this manual or
refer to the gas line manufacturers sizing information
to determine the correct diameter for the supply pipe.
d. The diameter of the gas lines, shown in the
illustration, will vary according to the specifi c
installation requirements.
NOTE: Always clean the inside of the gas line of
any dirt or debris before connecting the piping to
the unit.
4. Install a gas union connection with a short piece of 3/4”
NPT pipe.
5. Following local building codes, install a manual shut-off
valve.
6.
Connect the manual shut-off valve to the gas supply
line. Also install a GLUWSRFNHWGULSOHJ off of the main
supplyline, as shown.
Models
Parameters
NG/LP- Minimum Static
Gas Pressure 1/2"
NG/LP- Minimum Static
Gas Pressure 3/4"
NG/LP - Maximum
Static Gas Pressure
Gas Pressure for
Adjustments
i200i200Pi250i250P
5” (non-corrugated,
black iron)
2.5” (non-corrugated, black iron)
8” for NG, 11” for LP
6” (non-corrugated,
black iron)
14”
3. Make sure the supply line is correctly sized for the
maximum output of the water heater model being
installed. The Intellihot water heater should be the
fi rst appliance to be connected to the gas supply line.
a. Determine the gas requirement of the water heater(s)
and other appliances requiring gas. The supply line
must be sized according to the COMBINED total
maximum BTUH draw for all the appliances as if they
were all operating at the same time.
1”1”1”
Manual
Main Supply Line
Shut-off
Valve
Union
'ULSOHJ
7. Leak test the gas line piping before placing the unit
in operation. Only use approved leak detector liquid
solutions to check for leaks.
IMPORTANT
Do not fire (operate) the water heater until all
connections have been completed and the heat
exchanger is filled with water.
1/2”
Gas
Meter
IH-77
Typical installation when using 1/2” gas line.
Home
Wall
Less then 40’
Intellihot
1/2”
LaundryStove
20Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
GAS PIPE SIZING TABLES
Gas Pipe Sizing
This information is for reference only. Refer to gas pipe manufacturer specifications for actual delivery capacity. The DOE
standard for Natural Gas is 1100 BTU/ft3. Contact the local gas supplier for actual BTU/ft3 rating.
1/2” Black Iron Sizing
The following table shows gas supply in cubic feet per hour (CFH) assuming a specific gravity of 0.6 for Natural Gas, 0.585
for propane, pressure drop of 4.6” WC, and 5.0” WC. Contact your gas supplier for BTU/ft3 ratings. Use 1000 BTU/ft3 for
estimates.
Length (Including fittings)
Gas Pipe Size 5 10 15 20 25 30 35 40
Natural Gas 1/2” 571 404 330 286 255 233 216 202
LP 1/2” 578 409 334 289 259 236 219 204
Natural Gas Pipe Sizing
Maximum Natural Gas Delivery Capacity — Length of Black Iron Pipe in Feet
Intellihot Green Technologies, Inc. 21
www.intellihot.com (877-835-1705)
Fresh Air and Exhaust Piping Installation
COMBUSTION (FRESH) AIR INLET EXHAUST OUTLET CONNECTIONS
SAFETY
INSTRUCTIONS
For information on combustion air, either from inside the building or
from the outside, refer to the Venting section in this manual.
1. Select an approved material for the combustion air
inlet. Refer to the table below for a list of approved
materials. Also select the appropriate diameter of pipe
based on length and number of units being installed,
as shown in the tables in the Technical Specifi cations
section.
United States Vent Pipe Standards
MaterialDescription
PVC Schedule 40
Vent Pipe
MaterialDescription
Vent Pipe
Do not use cellular foam core pipe to vent exhaust gases.
CPVC Schedule 0
Approved Polypropylene
Canadian Vent Pipe Standards
Type BH Special Gas Vent Class IIA (PVC)
Type BH Special Gas Vent Class IIB (CPVC)
Type BH Special Gas Vent Class IIC (Polypropylene)
SAFETY
INSTRUCTIONS
NOTE: Consult the following chart or the most
recent edition of ANSI Z223.1/NFPA 54 or CAN/
CGA B149.1, as well as all applicable local codes
and regulations when selecting vent pipe
materials.
For installation in Canada, installer-supplied plastic
vent piping must comply with CAN/CGA B149.1 and
be certified to the Standard For Type BH Gas Venting
Systems, ULC-S636. Components of this listed system
must not be interchanged with other vent systems or
unlisted pipes or fittings. All plastic components and
specified primers and glues must be from a single system
manufacturer and must not be intermixed with anotherV\VWHPPDQXIDFWXUHU¶VSURGXFWV
2. Install the desired confi guration of pipe for the
combustion air inlet. If the installation allows 2” pipe to
be used for this air inlet, install at least a 6” long piece
of 3” pipe with a 3” to 2” adapter.
3" Pipe
6"
IH-70
CAUTION
TOXIC FUMES HAZARD
If the inside of the pipe is not chamfered to remove all sharp
edges, the O-ring seals can be damaged during installation.
into the house.
Damaged O-rings could allow combustion gases to leak
Cut a 45 degree chamfer on the inside edge of the
D.
3” pipe. Remove any shavings.
45°
IH-70a
IMPORTANT
On multiple unit installations, the piping from the
water heater can be 4” or larger piping. Use the
tables on page 11 to determine the diameter of the
common connecting piping between each individual water
heater.
E. $SSO\DVPDOODPRXQWRIZDWHURUOLTXLGVRDSRQ
WKHFKDPIHUHGVXUIDFHVWRVHUYHDVDOXEULFDQW.
22
Intellihot Green Technologies, Inc.
ZZZLQWHOOLKRWFRP
COMBUSTION (FRESH) AIR INLET EXHAUST OUTLET CONNECTIONS
c. Install the pipe over the connector and dual o- ring
seals. Ensure that the o-ring seals are seated
correctly within the pipe and not pinched or pushed
out of the O-ring groove.
d.
Secure the pipe to the ZDOOVRUMRLVWV using a
suitable clamp(not supplied).
3. Continue the routing of the combustion air inlet.
a. For termination of the pipe to the outside, continue
installing the required pipe to a suitable outside
location. Glue all connections, making sure the
joints are sealed airtight.
4. Continue the routing of the exhaust gas outlet to a
suitable outside location.
a. Glue all connections, making sure the joints are
sealed airtight.
b. Install all horizontal exhaust gas vents with a
minimum 2 degree (1/4” per foot) slope back toward
the water heater. This allows any condensate that
accumulates in the exhaust outlet to properly drain
back into the unit.
5. Install suitable pipe support hangers every 4 to 5 feet,
or as local building codes require.
SAFETY
INSTRUCTIONS
Do not connect any other appliance vents to the water heater inlet
or outlet pipes.
IH-35a
IH-36b
b. To confi gure the unit for power vent, insert a 6”
section of 3” pipe with a 90° elbow.
3" Elbow
3" x 2” Reducer
3" PVC Tube
2" PVC Tube
6. If multiple units are installed, make sure the diameter of
the connecting exhaust outlet is properly sized for the
number of units being installed.
CAUTION
This water heater has a built-in control to limit the exhaust
temperature to 149°F (65°C). As a result, the Intellihot water
heater can be vented with Schedule 40 PVC. If the incoming (or
recirculation return) water temperature does not exceed 150°F
(66°C), the exhaust temperature will not exceed 149°F (65°C).
However, if you set the water heater at a temperature above 150°F
(66°C) and you are also incorporating either an external recirculation
loop or a combination heating system, the exhaust temperature can
exceed 149°F (65°C). In that case, you must use Schedule 0 CPVC
or Approved Polypropylene in the USA or Type BH Special Gas
Vent Class IIB (CPCV) or Class I,C (Polypropylene) that conforms to
ULC-S636 in Canada.
IH-69
Intellihot Green Technologies, Inc. 23
www.intellihot.com (877-835-1705)
VENTING
Combustion Air From the Outdoors
Intellihot water heaters may be installed using a standard
(direct vent) configuration or an optional (power vent)
configuration.
The information in this section provides the installer with
recommendations; however, venting requirements are
different in the USA and Canada for installing proper
exterior venting through the structure’s roof or exterior
wall. Therefore, the installer should also refer to local
building codes and the “Venting of Equipment” section of
the latest edition of ANSI Z223.1 / NFPA 54 Natural Gas
Code. In Canada, refer to the “Venting Systems and Air
Supply for Appliances” section in the CAN/CGA B149.1
Natural Gas and Propane Installation Code.
Do not operate the unit in an area that will draw in air
contaminated with high levels of dust, sawdust, aerosols
such as paint, or other airborne contaminants.
If necessary, purchase and install appropriate air screens
and follow a regular cleaning program to ensure an
adequate supply of clean, outside combustion air.
SAFETY
INSTRUCTIONS
The end of ducts that terminate in an attic must not be
.
screened.
Under-floor Combustion Air
Combustion air obtained from under-floor areas must
have free opening areas to the outside equivalent to not
less than twice the required combustion air opening.
Opening Requirements
Outside combustion air openings must be covered with
corrosion-resistant screen or equivalent protection having
not less than 1/4 inch (6 mm) openings, and not greater
than 1/2 inch (13 mm) openings.
Do not use cellular foam core pipe to vent exhaust gases.
Outdoor Air
When the space in which fuel-burning appliances are
located does not meet the criteria for indoor air, outside
combustion air shall be supplied as specified in the
following sections.
Size of Openings
When directly connected with the outdoors, or when
connected with the outdoors by means of vertical ducts,
each opening must have a free area of at least 1 square
inch per 4,000 Btu/per hour (550 mm
2
/kW) of total input
rating of all appliances in the space.
Minimum Recommended Air Supply
Model / SizeArea of Outside Air Vents
i200 / 199,95014 sq.in.
i250 / 250,00017 sq.in.
Attic Combustion Air
Combustion air obtained from an attic area must be in
accordance with the following:
1. The attic ventilation must be suffi cient to provide the
required volume of combustion air.
2. The combustion air opening must be provided with a
metal sleeve extending from the appliance enclosure to
at least 6 inches (152 mm) above the top of the ceiling
joists and ceiling insulation.
24Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
VENTING
WARNING
TOXIC FUMES
To avoid serious injury or even death from exhaust gases
(carbon monoxide), make sure the water heater is properly
vented. Refer to all applicable local and national regulations,
mandates, and building codes for guidelines to install proper
venting.
Connections on Bottom of Unit
1. Terminate the combustion air inlet with a 90 degree
elbow (angled down) or a tee fi tting.
a. On an exterior wall, use a fl ange and PVC
VFUHHQ(not supplied).
b. For roof top installation, a suitable roof fl ashing and
vent cap (not supplied) will be required.
2. Terminate the exhaust gas outlet on the exterior wall.
a.
Side wall outlets must be at least 12” above ground
and at least 12” apart, or as required by local
building codes. In areas of high snow fall, protect
the vent terminations from blockage.
b. For roof top installation, a suitable roof fl ashing and
exhaust vent cap (not supplied) will be required.
12”
Exhaust
12”
IH-33
Concentric Wall Venting System
If desired, an optional concentric venting system, which
uses one 5” opening in an exterior wall or roof, as
opposed to cutting two 3” openingsFDQEHXVHG
Follow all installation instructions included with the
concentric vent kit when installing this type of vent
system.
vent
Fresh air
12” USA or 18” Canada
Over maximum snow
level or as required by
local code
Exhaust
Option A
IH-34
Exhaust
IH-34a
Side Wall Termination
NOTE: Install a mesh screen made from stainless
steel or other suitable material no smaller than 1/4”
opening on both air intake and exhaust pipes.
12” USA or
18” Canada
Over maximum
snow level or
as required by
local code
3’ Minimum
IH-51a
Concentric Roof Venting System
Exhaust
Exhaust
Intake
12” Minimum
12” USA or
18” Canada
Over maximum
snow level or as
required by local
code
Intake
Venting the unit through the roof is also an option. With
this installation method, the terminations must extend
at least 12” over maximum potential snow levels, or as
required by local building codes. In areas of high snow
fall, protect the vent terminations from blockage.
Intellihot Green Technologies, Inc. 25
www.intellihot.com (877-835-1705)
VENTING
Combustion (All) Air From Inside the Building
Intellihot may be used in a power vent or direct vent
configuration. When used in a power vent configuration,
the water heater should be located in an area where there
is adequate air supply from inside the building for proper
combustion and ventilation. Please follow your local code
or NFPA54 where applicable.
Safety information and wiring diagram inside of front cover.
Mortar or Silicone Caulk
Roof Flashing
Intake
Pipe
3RVLWLYHVORSHRI
SHUIRRW
Exhaust Pipe
Pipe
Coupling
Wall
Thimble
Safety information and wiring diagram inside of front cover.
Above Grade
or Snow Level
Vent Terminal
with 1/2” Mesh
Protective
Screen Inside
12" Min.
IH-72
26Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
INSTALL HOT WATER LINES
Install and connect the hot water lines. If an optional hot
water storage tank is required, connect the hot water lines
to this tank also.
5
4. Install and route a 3/4” discharge pipe from pressure
relief valve (4) to within 6 inches of the fl oor and
directed away from walkways or other appliances.
5. Following local building codes, install a manual shut-off
valve (5) using 3/4” with 3/4” NPT fi ttings.
6. Install a drain valve on the bottom of the unit.
3
4
2
1
IH-87
1. Connect a 3/4” NPT coupler (1) to the water heater’s
hot water connection.
2. Install a 3/4” union connection (2).
3. Install a 3/4” tee fi tting (3). Install either a pressure
relief valve or a temperature and pressure relief valve
(4), as required by your local code.
Safety
inf
ormation an
d
wiring
dia
gram inside of front cover.
Safety information and w
iring diagram insid
e
of fr
o
n
t c
over.
5
IH-88
7. Connect the unit to the existing hot water lines.
If the existing plumbing is 1/2” pipe, adapters may be
used to transition from the 3/4” pipe. If multiple water
heaters are being installed, the diameter of both the
cold water lines and the hot water lines need to be
sized appropriately.
8. Leak test the water piping before placing the unit in
operation.
5
IH-86
Temperature and Pressure Relief Valve
IMPORTANT
The pressure relief valve must be rated at 150 psi,
the maximum btu/h input of the unit, and comply
with all local building codes and standards. Do not
install any restrictions or other valves in the
pressure relief line.
Intellihot Green Technologies, Inc. 27
www.intellihot.com (877-835-1705)
NOTE: For energy conservation, the hot water
pipes should be insulated. Also insulate any
recirculation water lines.
Connecting Multiple Units
Install and connect the cold water line. If an optional hot
water storage tank is required, connect the hot water lines
to this tank also.
NOTE: If the incoming water is known to have a
high mineral content or “hardness” (>1 ppm),
treatment is recommended upstream from the
water heater.
INSTALL COLD WATER LINES
1. Connect a 3/4” NPT coupler to the water heater’s cold
water connection.
2. Install a 3/4” union connection.
3. Install an inline wye-strainer. Make sure the strainer is
positioned to allow servicing of the strainer screen.
IH-62
4. Following local building codes, install a manual shut-off
valve with 3/4” NPT fi ttings.
5. Connect the unit to the existing cold water lines.
If the existing plumbing is 1/2” pipe, adapters may be
used to transition from the 3/4” pipe. If multiple water
heaters are being installed, the diameter of both the
cold water lines and the hot water lines need to be
sized appropriately.
6. Leak test the water piping before placing the unit in
operation.
28Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
INSTALL CONDENSATE DRAIN
Due to its efficient design, the Intellihot water heater
produces condensate (water) as a normal by-product of
heating the water. This condensate is acidic, with a pH
level between 3 and 4. Local building codes may require
an in-line neutralizer to be installed (not included) to treat
this water.
1. Connect 3/4” I.D. fl exible drain line (2) to the
condensate nipple located on the bottom of the unit.
Tighten hose clamp (1).
2. If required, install an in-line neutralizer (3) to treat
the acidic condensate. Follow all the installation
instructions included with the neutralizer.
NOTE: If a nearby laundry tub is used as a
disposal for waste water from a washing machine,
draining the condensate into this tub allows the
soapy water discharge to neutralize the acidic
condensate.
3. Route the drain line to nearby laundry tub (6), fl oor
drain (5), or condensate pump (4).
1
3
2
4
5
6
IH-30
Intellihot Green Technologies, Inc. 29
www.intellihot.com (877-835-1705)
CONNECT ELECTRICAL POWER / INITIAL STARTUP
WARNING
To avoid serious injury or even death, follow all applicable
local, state, and national regulations, mandates, and
building codes for guidelines to install the electrical power
supply.
Electrical code requirements are different in the USA and
Canada. Refer to and follow the local building codes, the
latest edition of the National Electrical Code (NFPA 70) in
the USA, or the CGA C22.1 Canadian Electrical Code Part 1.
1. Make sure the electrical outlet being used is wired with
at least 12 gauge wire and grounded. It should also
be connected to at least a 5 Amp circuit breaker. The
electrical power required for the water heater is 120V
AC at 60 Hz.
2. Recheck the water, gas, condensate drain line,
combustion (fresh) air inlet, and gas exhaust outlet to
make sure they are properly connected.
3.
Before connecting the water heater to power, open
the gas supply valve, cold water valve, and hot water
valve. Also make sure the drain line valve is closed.
5. Plug the 60 inch power cord into the outlet. The
water heater’s display panel should turn on. DO NOT
disconnect the power supply while the unit is operating
(heating water).
NOTE: For additional electrical protection, the use
of a whole house surge protector is
recommended. Damage caused by power surges
is not covered by the Intellihot Warranty.
IMPORTANT
If the water heater display does not come ON, first
check the plug. Also check the electrical panel
circuit breaker and reset it if necessary. If the
circuit breaker trips again, do not reset. Disconnect
the plug and have a qualified technician diagnose
the problem.
30Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
MULTIPLE UNITS
Gas Valve Adjustments Section
All Intellihot water heaters are designed to connect
multiple units together. Multiple units increase the
volume of hot water and also ensures that hot water is
always available, even if one unit is shut down due to
maintenance.
Connecting several units together requires proper sizing
of water and gas piping, as well as increased sizLQJ in
the intake and exhaust pipes.
Up to ten water heaters can be connected (cascading)
together. Use the steps in this section along with the
basic installation procedure for installing a single unit.
The water heaters will communicate, via the cable
provided with the water heater, during normal operation:
• When demand for hot water is low, fewer units will
operate.
• If one unit has an error code, the others will continue to
operate.
• Changing the settings (temperature, time, etc.) on one
unit changes settings on all the units.
• It is possible to shut one unit down for maintenance
while the others continue to operate.
1. Connect all the units to a gas supply pipe. Make sure
the pipe is properly sized in accordance with the BTU
draw and number of units being operated.
Saf
e
ty information and wiri
ng diagram inside
o
f fro
nt
cover.
Safet
y i
nf
o
rmation a
nd wiring diagr
am
i
ns
i
de of f
r
ont cover.
IH-82
Intellihot Green Technologies, Inc. 31
www.intellihot.com (877-835-1705)
MULTIPLE UNITS
2.
Install the combustion (fresh) air intake and exhaust
outlet pipes. Make sure the pipes are properly sized in
accordance with the number of units being operated.
Refer to the table.
Safety information an
d wiring diagram inside of front cover.
Safety info
rmation and wiring d
i
agram
inside of front cover.
IH-83
a. Connect the 3” I.D air inlet from the unit to a
properly sized (large) common trunk line using
suitable adapters, wye fi ttings, and elbows.
b. Connect the 3” I.D exhaust outlet from the unit to
a properly sized (large) common trunk line using
suitable adapters, wye fi ttings, and elbows.
c.
For proper fl ow, DOZD\V use 90 degree tee-fi ttings
on the common trunk lineWhat have a sweeping
intersection. Also make surethefi ttings are
installed so the air fl ow will fl ow pastthe
intersection and not into it.
Note: Reduce the maximum equivalent length above by 5 feet per 90° elbow used and by 2 feet per 45° elbow.
Do not exceed the above set limits.
32Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
MULTIPLE UNITS
3. Install and connect the hot water lines. If an optional
hot water storage tank is required, connect the hot
water lines to this tank. Make sure the pipe is properly
sized in accordance with the number of units being
operated.
IH-84
Safety informa
tion and wi
ring diagra
m
i
nside of
front co
ver.
Safety informatio
n
a
nd wiri
ng diagram inside of front
cover.
6.If necessary, press the Power button to turn
OFF the water heater.
Disconnect the power.
7. On each water heater, remove the three screws from
both the top and bottom of the unit. Remove the front
cover and locate the main circuit board.
8.
If equipped, close the bypass valve, as shown. This
valve should only be in the Rpen positionLQDVLQJOHXQLWLQVWDOODWLRQ.
OPEN
6LQJOHXQLWLQVWOODWLRQ
&ORVHG
0XOWLXQLWLQVWOODWLRQ
4. Install and connect the cold water lines. Make sure the
pipe is properly sized in accordance with the number of
units being operated.
S
afet
y inform
ation and
wiring diagr
am inside of
front cove
r.
Safety information and wiring diag
ra
m inside of fr
ont cover.
IH-85
5. Connect the condensate drain lines.
CGN-009
WARNING
SHOCK HAZARD
Before making any adjustments inside the water heater,
make sure the power is disconnected. Unplug the water or
turn the circuit breaker OFF.
Intellihot Green Technologies, Inc. 33
www.intellihot.com (877-835-1705)
MULTIPLE UNITS
9.
Locate DIP Switch 2 on the fi rst and last unitsDQGSXW the switch in the 21position (up). On themiddle
unit(s), position the switch in the OFF position(down).
DIP Switch Settings
SW
Cascade 7HUPLQDWLRQ21
(7HUPLQDLVRQHQFDVFDGH21)
(Réglages des commutateurs DIP)
&DVFDGH7HUPLQDWLRQ2))
7HUPLQDLVRQHQFDVFDGH2))
DIP Switch Locations on Control Board
10. Connect the units using the supplied cable(s) and
cascading jack plugs. Connect one end of a cable
into either of two jack receptacles (arrows) located on
the circuit board.
11. Pass the cable through the bottom of the unit’s wire
grommet.
13. Connect the opposite end of the cable to one of the
jack connectors of the next water heater. Continue
connecting all the units together, as shown.
Dip Switch 2 ON
IH-61
Dip Switch 2 OFF
Dip Switch 2 ON
14. Replace the front covers.
15.
Reconnect the power
NOTE: Each water heater is rated at 500 watts
(5 amps). When installing multiple units, the
electrical power supply must be sized accordingly.
Plug each water heater into a separate outlet.
Using a separate circuit for each unit allows one
circuit breaker to trip while the other units
continue to operate.
16.
Mode
34Intellihot Green Technologies, Inc.
Press and hold the Mode button until the dH
screen appears.
www.intellihot.com (877-835-1705)
MULTIPLE UNITS
17.Then use the Up/Down arrows to select
the programming mode dC on the
display.
\
18.
Enter
19.
Press the Enter button to begin
programming.
Press the Set button to select either ON or
Set
OFF.
20.Once the water heater is programmed to
ON, use the Up/Down arrows to select
the unit number (1 - 10). Each unit must
have a unique number. The units do not,
however, need to be numbered in
sequence.
21.
Mode
Press and hold the Mode button until the dH
screen appears.
22.
Enter
Press Enter to return to the main display
screen.
23. Repeat steps 6 - 22 for all units and name each unit
uniquely.
Intellihot Green Technologies, Inc. 35
www.intellihot.com (877-835-1705)
MEASURING GAS PRESSURE
A qualified service technician must use a manometer to
confirm the static and operating gas pressure to the water
heater during installation.
Models
Parameters
NG/LP- Minimum Static
Gas Pressure 1/2"
NG/LP- Minimum Static
Gas Pressure 3/4"
NG/LP - Maximum
Static Gas Pressure
Gas Pressure for
Adjustments
1.
Press the Power button to turn OFF the water
i200i200Pi250i250P
5” (non-corrugated,
black iron)
2.5” (non-corrugated, black iron)
8” for NG, 11” for LP
6” (non-corrugated,
black iron)
14”
heater.
Disconnect the power.
2. Close the gas supply inlet valve to the unit and remove
the front cover from the water heater.
3. Connect a manometer to the gas connection, as
shown.
a. Remove plug, as shown by arrow.
b. Install 1/8” barbed nipple.
5. Connect the water heater to the power source. Make
sure all faucets are closed (no fl ow).
6. Set the Max Fire CO mode.
a. Press the Mode button until CO is displayed.
b. Press Enter to select this mode.
c. Mode selection is indicated by marque scrolling.
7. Open all hot water faucets. The unit will enter “max
fi re mode” indicated by the fl ame icon on the display
screen.
8. Turn on and operate at maximum output ALL other
household gas appliances located on the same gas
pipe system.
9. Record the lowest operating gas pressure reading
RQthe manometer.
DYNAMIC GAS PRESSURE ___________WC
DATE ___________________
10. Close all hot water faucets and turn off all other
household gas appliances.
11. To return the water heater to normal operation.
a. Press and hold MODE button until dH or cH mode is
displayed.
c. Attach the rubber hose to the manometer.
4.
Open the gas supply valve and record the static gas
pressure RQ the manometer.
STATIC GAS PRESSURE _______________WC
DATE ___________________
b. Press Power button to turn off the display.
Disconnect unit from power source.
c. Close inlet gas supply valve, disconnect the
manometer, and reinstall plug.
12. To continue unit set-up, go to the Adjusting the CO
Level section. To return the unit to normal operation,
install front cover and open inlet gas supply valve.
13. Leak test the gas valve before placing the unit in
operation. Only use approved leak detector liquid
solutions to check for leaks.
IMPORTANT
A qualified service technician MUST make the
required changes to convert the water heater from
Natural Gas to LP Gas.
Refer to the Measuring Gas Pressure section RI this
manual for the procedure to confirm that there is LP Gas
inlet pressure of between 8.0” and 13.0” W.C. Record the
gas pressure here.
STATIC LP GAS PRESSURE ____________W.C.
DATE ___________________
1. Make sure all hot water faucets are OFF.
Press the control panel Power button to turn
the water heater OFF.
Disconnect the power.
)XHO
6HOHFWLRQ
6ZLWFK
2. Shut OFF gas supply inlet valve closest to the unit.
3. Remove the water heater front cover and locate main
circuit board.
4. Locate DIP Switch 1 on the circuit board and change it
to the PROPANE position.
DIP Switch Settings
SW
(Réglages des commutateurs DIP)
Propane
Natural Gas
(Gaz naturel)
5.Reconnect the power and wait for dH screen
to appear.
Intellihot Green Technologies, Inc. 37
www.intellihot.com (877-835-1705)
PROPANE (LPG) CONVERSION
6.Press and hold the Set button and
simultaneously press the Up arrow key until
the Ft screen appears.
7.Press the Enter button to display and confi rm
gas selection. Either nAt or Prop will be
displayed to indicate the position of the DIP
switch.
9.
Enter
10. Refer to Adjusting the CO
Press the Enter button to return to the main
display.
Level section in this
2
manual for instructions on connecting a calibrated CO
analyzer to the gas valve.
11.
Locate the gas valve and use a small screwdriver
to adjust gas valve high fi re main fl ow restrictor (V3)
1-1/2 turns clockwise .
12.
Refer to Adjusting the CO
Level section for
2
instructions on using the gas analyzer to measure and
set High Fire CO2 and CO levels
2
8.Press and hold the Mode button to save the
changes and return to the dH screen on the
main display.
38Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
ADJUSTING THE CO2LEVEL
This procedure is required only during installation in a
high-altitude locationRUwhen FRQYHUWLQJ the unit from
natural gas to propane, or with combustion problems.
This procedure should only be done by a qualified
technician or installer.
DANGER
A concentration of carbon monoxide as small as
0.04% (400 parts per million) in the air can be fatal.
When making high fire and/or low fire adjustments,
so that the level of no more than 400 ppm of CO is exceeded at any
time during the operation.
the exhaust gases with a fully functional and calibrated flue gas
analyzer.
High Fire 8.8% to 9.1% < 200 ppm
Low Fire 8.6% to 8.9% < 60 ppm
High Fire 8.8% to 9.1% < 200 ppm
Low Fire 8.6% to 8.9% < 60 ppm
CO levels must be monitored using a flue gas analyzer
Adjusting the “low fire offset “ or the “main flow restrictor” in
small increments can result in a significant increase in CO
concentration. To avoid serious injury or death, DO NOT
make any adjustments to the gas valve without monitoring
CO
and CO Standards
2
CO2 Range (%) Max. CO Level (ppm)
Natural Gas
LP Gas
Troubleshooting Chart
2.
Use the CO2 analyzer to measure the exhaust vent
IXPHV. Use a small screwdriver to adjust gas valve
highfi re main fl ow restrictor (V3) to achieve the
desired CO
NOTE: Turn clockwise for less CO2 and
counterclockwise for more CO2.. Make
adjustments by making 1/4 turn increments. Wait
three minutes for reading to stabilize and then
recheck.
values.
2
IMPORTANT
Values above are for climate controlled conditions.
Variables such as gas pressure, heating value of
the gas, and the humidity and temperature of
combustion air can all impact CO and CO
Changes in these variables can result in different
CO and CO
values on the same water heater.
2
values.
2
Once the inlet gas pressures are confirmed, a qualified
service technician must use a calibrated CO
analyzer to
2
adjust the gas valve to achieve the desired CO2 and CO
values.
IMPORTANT
The service technician must confirm Static and
Operating inlet gas pressures before setting High
Fire and Low Fire CO
and CO values.
2
IMPORTANT
Making High Fire Adjustments can affect the Low
Fire setting and vice versa. Therefore, double
check both the High Fire and the Low Fire CO
CO levels after making any adjustment.
and
2
3. There will be a slight time delay between the
adjustment and the response of the analyzer
instrument. Allow the reading to stabilize before
making another adjustment
4. Once the desired values are achieved, record the
HIGH FIRE CO
HIGH FIRE CO
values.
2
VALUE _______________%
2
Max CO Level Measured ____________ppm
DATE ___________________
1. Locate the gas valve, as shown.
Intellihot Green Technologies, Inc. 39
www.intellihot.com (877-835-1705)
Wiring Diagram
ADJUSTING THE CO2LEVEL
5. Press the Up/Down arrows to go to the Low Fire mode.
6. Adjust the Low Fire offset while the burner operates at
low fi re using a 2 mm hex wrench inserted into servo
regulator offset adjustment (V2). Adjust the offset
pressure to achieve the desired low fi re CO
values.
2
NOTE: Turn clockwise for more CO2 and
counterclockwise for less CO
.
2.
11.
&KHFNIRUDQ\JDVRUH[KDXVWOeakV test before
placing the unit inoperation. Only use approved
leak detector liquidsolutions to check for leaks.
7. There will be a slight time delay between the
adjustment and the response of the analyzer
instrument. Allow three minutes for the reading to
stabilize before making another adjustment.
8. Once the desired values are achieved, record the LOW
FIRE CO
LOW FIRE CO
values.
2
VALUE _______________%
2
Max CO Level Measured ____________ppm
DATE ___________________
9. Close all open water faucets.
10. Return the water heater to normal operation.
a. Press and hold Mode button until dH or cH mode is
displayed.
b. Press Enter to select this mode.
c. Press Power button to turn OFF the water heater.
d. Turn OFF the inlet gas supply valve, disconnect
the gas analyzer, and install a test port plug in the
exhaust gas vent.
e. Install front cover and open inlet gas supply valve.
40Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
Control Panel
OPERATION
Operational Diagram
G
Set
A
F
Mode
Clock
Time
E
Power
F
Enter
C
D
A) LCD screen
The LCD display screen shows all information
about the operating functions of the water heater.
B) Arrow keys
Press the UP or DOWN arrows to adjust the value
of the selected feature, such as time or water
temperature.
Also use these keys to select a program screen in
Modes of Operation.
Used to switch between options within a Mode of
Operation screen.
C)
Enterbutton
Press this button to switch the temperature display
between degrees F and degrees C. It is alsoused
to HQWHUModeVof Operation screenV in order to
set the desiredparameters.
B
C
D) Power button
When the water heater is initially connected to an
electrical power supply, the unit will automatically
turn ON and the display panel should light up.
To turn the unit OFF, press and hold the Power
button and the water heater will go through a
shutdown process. The unit can then be turned
ON again by pressing and holding the Power
button.
E) Time button
Press this button to set the hours and minutes on
the clock.
F) Mode button
Press this button to enter the Mode of Operation
screens. Once the first screen appears, use the
UP and DOWN arrow keys to select the desired
screen.
G) Set button
Used to set the daily ON/OFF times.
Intellihot Green Technologies, Inc. 41
www.intellihot.com (877-835-1705)
U
OPERATION
HIJKLMNO
V
T
P
S
R
IH-03
Display Icons
H) Error Icon
Indicates an error has been detected and a
trouble code may be shown next to the CODE
Display (T) section. The last ten trouble codes
are retained in memory.
I) Wireless Icon
Indicates the wireless mode is activated.
J) Freeze Indicator Icon
Warns of freezing conditions within the water
heater. The water heater is designed to turn ON
to prevent freezing of the internal water pipes.
K) Recirculation Indicator Icon
Indicates water is being circulated through the
system.
L) Water Usage Icon
Indicates water flow (open faucet).
M) Blower Icon
Indicates blower is operating.
N) Burner ON Icon
Indicates burner is operating.
O) Gas Consumption Icon
Indicates the level of energy usage. More bars
being visible indicates a higher consumption of
gas.
Q
P) Outlet Water Temperature Display
Displays the desired maximum temperature of the
water flowing out of the unit. This temperature
can be adjusted between 100° and 140°F for
domestic use and up to 1°F for commercial use.
If the temperature is flashing, it indicates the water
has not reached the desired maximum setting. It
also indicates the unit of measure; Fahrenheit or
Celsius.
Q) Programmed ON/OFF Times
Dark boxes below the time graph indicate a
programmed ON time in one hour increments.
R) Program Indicator
Program is displayed during set up of the ON and
OFF times.
S) Clock Display
Indicates the current time in AM or PM. Also
indicates the programmed ON (start time) or OFF
(end time) when setting programmed run times.
T) CODE Display
Displays the word CODE and the most recent
digital error code.
U) INLET Display
Displays the word INLET and the actual inlet water
temperature in degrees Fahrenheit or Celsius.
V) SET Display
Displays the word SET when changing the outlet
water temperature and/or time values. Use the
UP/DOWN arrows to adjust the variable.
42Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
OPERATION
Setting the Time
1.
Time
2.Press the Up/Down arrows to set the
Press the Time button.
The minute section of the time display will
flash.
correct minute.
4.Press the Up/Down arrows to set the
correct hour. When setting the hour,
make sure you have correctly advanced
the time to either the AM or PM hour
setting.
5.
Time
Press the Time button again.
The colon (:) between the hours and minutes
should now be flashing, indicating the time
has been properly set.
3.
Time
Press the Time button again.
The hour section of the time display will flash.
Intellihot Green Technologies, Inc. 43
www.intellihot.com (877-835-1705)
OPERATION
Adjusting the Water Temperature
NOTE: The outlet water temperature is factory
preset to 120°F (49°C).
Hot water temperature over 12°F (°C)
can cause severe burns instantly or death
from scalding. Children, the disabled, and
the elderly are at the highest risk of being
scalded. Do not leave children or the infi rm
unsupervised. Check temperature of hot
water before taking a shower or bath. To
control water temperature to a particular faucet, temperature
limiting valves can be installed by your service professional.
All water faucets must be closed
before changing the temperature
setting. The fan in the water
heater must be OFF, and the unit must not be
operating (no flame).
WARNING
Water temperatures over 120°F (49°C) can cause severe
burns. Proper care is your responsibility. To avoid scalding,
especially in households with children, elderly, or
handicapped occupants, do not adjust the outlet water
temperature above the factory setting.
Press the Enter button to select either
Enter
Fahrenheit or Celsius.
Press the Up/Down arrows to set the
desired temperature. The temperature
range for residential applications is
adjustable between 100 and 140°F (38 and
60°C) in one degree increments.
44Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WATER HEATER PROGRAMMING SECTION
Modes of Operation
The Modes of Operation screens provide set up screens
and additional information on the water heater. There are
15 Mode of Operation screens of which four screens are
used by the homeowner. The other screens are used by
the technician during installation or maintenance of the
water heater.
Customer Screens
ThedH screen provides the homeowner with the basic
set up of the water heater. It also shows the water
heater is in the dH mode which is “domestic hot water”.
ThePS screen is used by the homeowner to set the
GHVLUHGFLUFXODWLRQ timeV21DQG2)) for the water
heater.ThedE screen is used by the homeowner to view
diagnostic error codes before calling a technician with a
potential service problem.
NOTE: The PS and EC screens are on i200P and
i250P models only.
2.Then use the Up/Down arrows to select
the PS screen on the display.
3.
Enter
4. Select one of four programming modes: Manual, Auto,
24-7, or None
Auto Setting
This setting allows the water heater to automatically
set the times of usage by monitoring hot water usage
throughout the day
Press the Enter button to begin programming.
A scrolling marquee will appear when in the
programming mode.
Programming ON/OFF Run Times
The Intellihot water heater senses water usage
and will automatically provide hot water on
demand. Depending on the distance between
the unit and the open faucet, it can take some time for
existing cool water to be purged from the length of the hot
water pipe.
If desired, the water heater can be set for daily ON/
OFF run times in one hour increments. Use this feature
in conjunction with OPTIONAL recirculating valves and
systems to pre-supply heated water to specific faucets.
1.
Press and hold the Mode button.
Mode
24/7 Setting
This setting turns ON all of the blocks
None Setting
This setting turns OFF all of the blocks
Intellihot Green Technologies, Inc. 45
www.intellihot.com (877-835-1705)
WATER HEATER PROGRAMMING SECTION
Manual Setting
This setting is used to manually turn ON or OFF each
block one at a time
4.
Mode
When all times have been set, press and hold
the Mode button to save the changes and
return to the dH screen on the main display.
1.
2.
Set
NOTE: Each “block” displayed below the time line
represents an “ON” time of one hour. The default
setting is all time blocks are “OFF” (not displayed).
3.
When the desired block is flashing (9:00 AM), press the
Set button to activate it. Repeat this process to activate
all the desired “ON” time blocks.
Press the Up/Down arrows to select the
time (6:00 am).
With the desired time icon displayed, press
the Set button once to activate (ON). Press
the Set button again to deactivate (OFF).
If desired, continue to press the Up/Down
arrows to select another time block(s).
5.
Enter
Press the Enter button to return to the main
display.
Recirculation Setup
Set up the Recirculation options using the display on the
front of the water heater.
1.
Mode
Press the Mode button until the dH screen
appears.
NOTE: The time setting for 12:00 am or pm is
00:00, as shown.
2.Press the UP arrow until the EC screen
appears.
3.
Enter
4.
Press the Enter button to select the External
Circulation mode.
Use the Up/Down keys to select
thermostatic valve, dedicated line, or tank
loading.
46Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WATER HEATER PROGRAMMING SECTION
No recirculation selected
Thermostatic valve
Dedicated line
Tank loading
Cascading (Daisy Chain)
1.
Mode
2.Then use the Up/Down arrows to select
3.
Enter
4.
Set
Press and hold the Mode button.
the programming mode dC on the display.
Press the Enter button to begin programming.
Press the Set button to select either ON or
OFF.
3XPSRQFRQWLQXVRXO\
5.Once the water heater is programmed to
ON, use the Up/Down arrows to select
the unit number (1 - ). Each unit must
have a unique number. The units do not,
however, need to be numbered in
sequence.
6.
Mode
7.
Enter
Press and hold the Mode button to save the
changes and return to the dH screen on the
main display.
Press Enter to return to the main display
screen.
Intellihot Green Technologies, Inc. 47
www.intellihot.com (877-835-1705)
WATER HEATER PROGRAMMING SECTION
Technician Screens
The second type of screen should only be accessed by
a qualified technician. These screens should not be
adjusted by the homeowner.
1. Press the Mode button until dH shows on the display.
2. Press and hold the Set button and scroll using the
up/down key.
3. When the desired mode is displayed, press the Enter
button.
Pressure Booster (pump models only
Applicable only to Pump Model
In applications where the supply pressure is low
and additional pressure is desired, set the Pb mode to
ON. The default is Off.
Press the Set button.
Set
Press the Up/Down arrows to select either
ON or OFF.
Press and hold the Mode button to save the
Mode
Enter
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
Fast Start Selection
Keeps water hot for five minutes after the last
use. The Fast Start mode provides hot water
faster in ON and OFF applications. This mode
is set to OFF by default.
The Fast Start mode is an ON or OFF selection.
Enter
Then use the Up/Down arrows to select the
programming mode Pb on the display.
Press the Enter button to begin programming.
Press the Set button.
Set
Then use the Up/Down arrows to select the
programming mode FS on the display.
Press the Enter button to begin programming.
Enter
48Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WATER HEATER PROGRAMMING SECTION
Mode
Enter
Press the Up/Down arrows to select either
ON or OFF.
Press and hold the Mode button to save the
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
Set
Enter
Press the Up/Down arrows to select either
ON or OFF.
Press and hold the Set button to save the
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
Flow Booster
This mode may be used to increase the overall
system recirculation flow by enabling all the
water valves open in a multiple units installation
to be open.
The Flow Booster mode is an ON or OFF selection.
Press the Set button.
Set
Then use the Up/Down arrows to select the
programming mode Fb on the display.
Press the Enter button to begin programming.
Enter
Blower Ramp Selection
When exhaust harmonics are observed, i.e.
resonance at low fire, adjust the water heater
using the blower ramp setting (default is rat0).
Increase the rate number until the resonance is no longer
observed.
The Blower Ramp Selection has six different settings
(rat0 - rat5):
Press the Set button.
Set
Then use the Up/Down arrows to select the
programming mode rS on the display.
Intellihot Green Technologies, Inc. 49
www.intellihot.com (877-835-1705)
Press the Enter button to begin programming.
Enter
Mode
Enter
WATER HEATER PROGRAMMING SECTION
Press the Up/Down arrows to select the
Blower Ramp Selection from six different
settings (rat0 - rat5):.
Press and hold the Mode button to save the
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
ON or OFF.
NOTE: If you determine the water pressure at the
faucet is too low, turn the mode to OFF.
Press and hold the Set button to save the
Set
Enter
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
Flow Control Selection
The Water Control Valve is set to ON for
SUHFLVH temperature FRQWUROand OFF for
maximum flow.
The Water Control Valve mode is an ON or OFF
selection.
Press and hold the Set button.
Set
Then use the Up/Down arrows to select the
programming mode FC on the display.
Fuel Type Selection
The Fuel Type mode screen shows the selected
fuel type; natural gas (factory preset) or
Propane. Operation with natural gas is factory
preset. Refer to the Propane (LPG) Conversion section
in this manual for additional set up information.
Blower Override
This mode may be used to manually control the
speed of the blower and should be accessed
only by an Intellihot factory technician.
Blower Override is an ON or OFF selection.
Press the Set button.
Set
Then use the Up/Down arrows to select the
programming mode bO on the display.
Press the Enter button to begin programming.
Enter
Press the Up/Down arrows to select either
ON or OFF.
50Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
Enter
WATER HEATER PROGRAMMING SECTION
Press the Enter button to begin programming.
Press and hold the Set button.
Set
Mode
Enter
Press the Up/Down arrows to select either
ON or OFF.
Press and hold the Mode button to save the
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
Then use the Up/Down arrows to select the
dE screen on the display.
Press the Enter button to view the codes.
Enter
Press the Up/Down arrows to view any one
of the ten diagnostic codes from C0 to C9.
Each code line will have an associated error
code displayed. The C0 screen is the most
recent code, while the C9 is the last
viewable code.
Diagnostic Code and Error Log Selection
This screen provides the technician with
Diagnostic Codes and Errors recorded as the
water heater operates. These codes are used in
conjunction with the Performance History Codes.
Error CodeDescription of Error Code
E0Reserved for Future Use
E1 Fan Speed Fault
E2Reserved for Future Use
E3Blocked Flue Fault
E4Reserved for Future Use
E5Reserved for Future Use
E6Reserved for Future Use
E7Ignition Failure
E8Reserved for Future Use
E9Temperature Sensor Short
EATemperature Sensor Wiring Fault
EbSoftware Fault
EcFlue Temperature Fault
EdHeat Exchanger Outlet Temperature Fault
EEReserved for Future Use
EFReserved for Future Use
Diagnostic Code C0 with no error code (nOnE).
Diagnostic Code C1 with error code (E7); ignition failure.
When finished, press and hold the Mode button
Mode
to return to the dH screen on the main display.
The software does not have a hold function.
Press the Enter button to return to the main
Enter
display.
Intellihot Green Technologies, Inc. 51
www.intellihot.com (877-835-1705)
Set
Enter
WATER HEATER PROGRAMMING SECTION
Diagnostic Code and Error Log Selection
The Performance History mode allows the
technician to view ignition cycles, number of ON
times, and accumulated water flow.
Press and hold the Set button.
Then use the arrow keys to select the
programming mode PH on the display.
Press the Enter button to begin programming.
Diagnostic Code FC (Flame Cycles) shows a flame count of 40,000.
Diagnostic Code FH (Flow-on hours) shows one hour of flame. (To
obtain the usage in gallons, multiply the number by 1,000).
Adjusting CO2 Levels Selection
For adjusting CO2 levels, refer to the Adjusting
the CO
Level section in this manual.
2
Press the Up/Down arrows to select one of
the six diagnostic codes. Each code line
has a corresponding number for each code.
Diagnostic Code CF (Cumulative Flow) shows 38,000 gallons of water.
(To obtain the usage in gallons, multiply the number by 1,000).
Diagnostic Code dS (Diagnostic Service Hours). The display can be
between 0 and 9999 hours. This code is used to determine the useful
service life of the water heater.
Commercial Heating Selection
The Commercial Heating option allows water
to be heated to a maximum of 185°F (38°C) for
commercial applications.
Hot water temperature over 125°F (52°C) can
cause severe burns instantly or death from
scalding. Children, the disabled, and the
elderly are at the highest risk of being
scalded. Do not leave children or the infi rm
unsupervised. Check temperature of hot
water before taking a shower or bath. To
control water temperature to a particular faucet, temperature
limiting valves can be installed by your service professional.
Press and hold the Set button.
Set
Then use the Up/Down arrows to select the
programming mode CH on the display.
Diagnostic Code US (Usage) is a percentage figure between 0 and
100%.
Press the Enter button to begin programming.
Enter
52Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WATER HEATER PROGRAMMING SECTION
Press the Up/Down arrows to set the
desired temperature.
When the Commercial mode is OFF, the maximum
temperature setting is 140°F. When the Commercial
mode is on the maximum temperature, setting is 185°F.
Press and hold the control panel Power button
to turn the water heater OFF.
Press control panel Power button to turn the
water heater back ON.
Watch the display for “CH”, which appears momentarily
before the display shows the actual temperature.
Then use the Up/Down arrows to select the
programming mode LA on the display.
Press the Enter button to begin programming.
Enter
P ress the Up/Down arrows to select either
ON or OFF.
NOTE: When changing the mode back to
residential hot water (dH), the temperature setting
will remain above the maximum limit until the
down arrow is pressed.
Leak Action Selection
If turned ON and a leak is detected, water will
automatically be shut off. If turned OFF, the
leak will continue. High condensation within the
tank can sometimes produce a false reading. This mode
is turned OFF by default.
The Leak Action mode is an ON or OFF selection.
Press and hold the Set button.
Set
Mode
Enter
Press and hold the Mode button to save the
changes and return to the dH screen on the
main display.
Press the Enter button to return to the main
display.
Intellihot Green Technologies, Inc. 53
www.intellihot.com (877-835-1705)
MAINTENANCE
Cleaning the Inlet Water Y-Strainer
When the Intellihot water heater is installed, an inline
Y-strainer should be installed between the shut-off valve
and water inlet. This strainer should be cleaned every
three months, or as required, to maintain full water flow to
the unit.
IH-62
1. Position a container under the Y-strainer on the water
inlet piping.
2. Close the water inlet valve (arrow) and remove the
cover plug. Allow the water to drain from the pipe.
Draining the Water Heater
CAUTION
Hot water can cause burns to the skin. The water temperature
is factory set to 120°F (49°C). To avoid burns, make sure the
water heater is OFF and the power supply is disconnected.
The water heater will remain hot for some time. Wait until the
unit has completely cooled before draining the water heater or
performing any other maintenance.
1.Press the Power button to turn OFF the
water heater.
Disconnect the power.
2. Close the water supply inlet and outlet valves. The
closed valve position is typically when the handle is
perpendicular to the pipe, as shown in the illustration.
IH-32c
3. Remove the strainer screen, clean it, and reinstall it in
the housing.
IH-62a
4. Replace the Y-strainer cover plug.
IH-32b
3. Position a bucket or other container under the drain
valve on the bottom of the unit.
4. Slowly open the drain valve and allow all the
remaining water to drain from the unit.
IH-29b
Intellihot Green Technologies, Inc. 55
www.intellihot.com (877-835-1705)
MAINTENANCE
5. Slowly loosen the air bleed screw (shown by arrow).
IH-32d
6. When all the water has drained from the water heater,
close the drain valve and close the air bleed screw.
Depending on quality of the water supply, the Water
Heater may requires descaling to provide efficient heating
of water. It is recommended that the unit be descaled
every other year, or sooner if the control panel displays a
flashing “H” icon with the code CL. A service technician
can preform this procedure during an annual inspection if
desired.
56Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
TROUBLESHOOTING CHART
ERROR CODEDESCRIPTIONREMEDY
E0Reserved for Future Use
E1 Fan Speed Fault
E2Reserved for Future Use
E3Blocked Flue Fault
E4Reserved for Future Use
E5Reserved for Future Use
E6Reserved for Future Use
E7Ignition Failure
E8Reserved for Future Use
E9Temperature Sensor Short
EATemperature Sensor Wiring Fault
EbSoftware Fault
EcFlue Temperature Fault
EdHeat Exchanger Outlet Temperature Fault
EEReserved for Future Use
EFReserved for Future Use
Turn water heater OFF, shut gas valve,
unplug unit, and contact an authorized service
technician.
Clean out debris and clean exterior inlet and
outlet screens.
Verify both air intake and exhaust vents are
clear of debris.
Verify there is an adequate gas supply to the
unit.
If the problem persists, turn control panel OFF,
shut gas valve, unplug unit, and contact an
authorized service technician.
Turn water heater OFF, shut gas valve,
unplug unit, and contact an authorized service
technician.
Turn water heater OFF, shut gas valve, unplug
unit, and contact service technician.
Turn water heater OFF, shut gas valve, unplug
unit, and contact service technician.
Turn water heater OFF, shut gas valve, unplug
unit, and contact service technician.
Turn water heater OFF, shut gas valve, unplug
unit, and contact service technician.
Intellihot Green Technologies, Inc. 57
www.intellihot.com (877-835-1705)
TROUBLESHOOTING CHART
Troubleshooting Chart
PROBLEMPOSSIBLE CAUSESCAUSE REMEDY
No electrical power to the water
heater.
No water available when a faucet is
opened.
Hot water is not available when the
faucet is opened.
The water temperature is not hot
enough or turns cold during use.
It takes a long time before hot water
flows from the faucet.
The water is not hot enough.• Is the water temperature set too low?• Adjust the temperature setting.
The water at the faucet is too hot.• Is the water temperature set too high?• Adjust the temperature setting.
A fan can be heard even when the unit
is not operating.
White “smoke” can be seen coming
out of the exterior exhaust gas vent.
• Is the plug on the power supply cord
unplugged from the electrical outlet?
• Is electrical panel’s 10 Amp circuit
breaker tripped?
• Is the fuse on the circuit board good?
• Is there a power outage to the
home?
• Is the water supply valve shut off
at the meter (do cold water faucets
work)?
• Is the water supply valve near the
unit open?
• Is the water pipe frozen?
• Is an error code flashing on the
display panel (leak detected)?
• Does the water heater have power
(plugged in)?
• Is the water heater turned ON?
• Is an error code flashing on display
panel?
• Is the gas supply valve open or shut
off at the meter (do other gas devices
work)?
• Is the faucet open far enough to draw
at least 0.6 gallons (2.3 L) per minute
through the water heater?
• Is an error code flashing on the
display panel?
• Is the outlet water temperature set
too low?
• Is the faucet some distance from the
water heater?
• The fan continues to operate after
the burner shuts off to clear the
exhaust vent of combustion gases.
• The fan may run to help prevent
freezing.
• Depending on the outside
temperature, water vapor can be
produced as the exhaust is vented.
• Reset the plug.
• Reset the circuit breaker.
• If the display panel is blank, unplug
the unit or contact an authorized
service technician.
• Contact the power company.
• Open the closed supply valve.
• Open the water supply valve.
• Turn OFF the unit, close all water
valves and gas valve. Contact an
authorized service technician.
• Refer to error code information
and contact an authorized service
technician.
• Restore electrical power to the unit.
• Press and hold the Power button to
turn the unit ON.
• Refer to the Diagnostic and Error
Codes section in this manual.
• Open the gas supply valve.
• Open the faucet to allow more water
flow.
• Refer to the Diagnostic and Error
Codes section in this manual.
• Adjust the outlet water temperature
(refer to the procedure in this
manual).
• Allow time for the cold water already
in the pipes to flow from the faucet.
• Have recirculation valves and/or
plumbing return line(s) installed and
program the unit for recirculation
mode.
• Normal operation, no action required.
• Protect the water heater from
freezing temperatures or shut off and
drain the unit.
• Normal operation, no action required.
58Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WIRING DIAGRAM
Pump
BRN
BRN
RED
RED
WHT
BLK
Jumper
Wire
6:
NG
PR
S
6:
Cascading
Connectors
Intellihot Green Technologies, Inc. 59
www.intellihot.com (877-835-1705)
Air Switch
COMMERCIAL OPTIONS
Commercial Option #1
Multi-Unit “P” Models with Building Recirculation and No
Storage
Commercial Option #2
Multi-Unit “P” Models with Internal ‘Tank-Loading’,
Storage, and Building Recirculation
Commercial Option #4
Multi-Unit Non “P” Models with Storage using External
Building Recirculation Pump
Commercial Option #5
Single Unit “P” Models with Internal ‘Tank-Loading’,
Storage, and Building Recirculation
Commercial Option #3
Multi-Unit “P” Models with External ‘Tank-Loading’,
Storage, and Building Recirculation
Commercial Option #6
Single Unit “P” Models with Internal ‘Tank-Loading’ and
Storage (without Building Recirculation)
60Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
OPERATIONAL DIAGRAM
Intellihot Green Technologies, Inc. 61
www.intellihot.com (877-835-1705)
IH-56
WARRANTY
General
This water heater is warranted by Intellihot Green
Technologies Inc. (Intellihot), and covers defects in
materials and workmanship, subject to the applicable
time periods and terms below. This warranty begins on
the date of installation or on the date of possession in
the case of new construction. This warranty is extended
to the original purchaser and any subsequent owner
at the original install location, and applies only when
properly installed by a licensed contractor and operated
in accordance with the instruction manuals. This warranty
is limited to repairs or replacement of parts, at Intellihot’s
option that are proven to be defective under normal use
and connected only to potable water systems.
Effective Start Date
Intellihot requires proof of purchase and warranty
registration in order to obtain warranty service. You
can show proof of purchase with a dated sales receipt.
Register the warranty within 30 days of purchasing the
product by going online at www.intellihot.com.
Residential DHW Warranty
Heat Exchanger - 15 years
Other Parts - 5 years
Commercial Warranty
Heat Exchanger - 6 years
Other Parts - 3 years
Residential Domestic Hot Water (DHW) means potable
water heating in a single family residence, not connected
with any space heating. Commercial means all other
applications including any space heating applications.
Heat Exchanger Coil
The warranty period for a heat exchanger coil failure,
when installed in a residential DHW application (including
recirculation), is fifteen (15) years from the effective start
date. The warranty period for a heat exchanger coil,
when installed in a commercial application (including
recirculation) or any space heating application, is six (6)
years from the effective start date.
All other Parts and Components
The warranty period for any original parts (excluding
the heat exchanger coil) against failure, when installed
in a residential DHW application (including domestic
recirculation) is five (5) years from the effective start date.
The warranty period for any original parts (excluding the
heat exchanger coil) against failure, when installed in a
commercial application (including recirculation) or any
space heating application is three (3) years from the
effective start date. A replacement part will be warranted
for the unexpired term of the original warranty. Defective
parts submitted may not be returned. No returns will be
accepted without prior authorization from Intellihot.
Labor
The applicable period of this limited labor warranty is
one (1) year from the effective start date. This applies
to all water heater models. The payment and amount of
any payment are subject to approval at Intellihot’s sole
discretion. The Labor allowance will be paid based on the
following schedule:
Repair or Replacement of Any
Parts
Replacement of Entire Unit
$75/hour up to maximum of
$150
$75/hour up to maximum of
$225
Replacement parts must be genuine Intellihot parts
and warranty service must be performed by a licensed
contractor.
Shipping Costs
If a replacement part is supplied under the terms of this
warranty, Intellihot will provide ground service delivery for
the part free of charge. Any expedited shipping expense
will be paid by the customer.
Definition of Potable Water
Potable water is defined as drinkable water supplied from
utility or well water in compliance with EPA secondary
maximumcontaminant levels (40 CFR part 143.3)
as shown in the table.Intellihot will warrant the heat
exchanger coil for hardness up to 15 Grains per gallon
(257ppm as Calcium carbonate)
ContaminantLevel
Aluminum0.05 to 0.2 mg/l.
Chloride250 mg/l.
Color15 color units
Copper1.0 mg/l.
CorrosivityNon-corrosive
Fluoride2.0 mg/l.
Foaming Agents0.5 mg/l.
Iron0.3 mg/l.
Manganese0.05 mg/l.
Odor3 threshold odor number
pH6.5-8.5
Silver0.1 mg/l.
Sulfate250 mg/l.
Total dissolved solids (TDS)500 mg/l.
Zinc5 mg/l.
.
62Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
WARRANTY
Not Covered by this Warranty
This warranty does not cover product failure or problems
due to:
• Failure to install in accordance with applicable
building codes, ordinances, normal plumbing and
electrical trade practices;
• Improper installation, improper use, improper
maintenance, improperly made replacements or
repairs;
• Accidents or abuse;
• Sediment deposits, fire, flood, lightning, freezing,
and acts of God, or any causes other than defects in
materials and workmanship.
This warranty will be void and have no effect if:
• The water heater is modified or altered in any way;
• Appliance(s) or equipment are attached to the water
heater that have not been approved by Intellihot
Green Technologies;
• The serial number is altered, defaced, or discarded.
Warranty Limitations
This warranty applies only when the water heater is used
in the United States or Canada. Except for the limited
warranties provided above, Intellihot Green Technologies
disclaims any and all other warranties, including but
not limited to warranties of merchantability and fitness
for a particular purpose; provided however, that implied
warranties of merchantability and fitness for a particular
purpose are not disclaimed during the one-year period
from the effective date.
Intellihot shall not be liable for indirect, special, incidental,
consequential, or other similar damages, including lost
profits, arising from or relating to the water heater.
This warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.
All parts claimed to be defective may be requested to
be returned to Intellihot for examination prior to full claim
settlement. Please include the following information on
your warranty claim:
1. Model number and serial number of the water heater;
2. Date of original purchase;
3. Owner’s name and address;
4. A description of the problem with the part and water
heater.
Intellihot Green Technologies Inc. reserves the right
to make improvements in design or changes in
specifications at any time, without incurring any obligation
to owners of units previously sold.
Some states or provinces do not permit limitations
or exclusions of implied warranties or incidental or
consequential damages, so the limitations or exclusion
in this warranty may not apply. No one is authorized to
alter, modify, or enlarge this warranty, nor the exclusion,
limitations, and reservations.
Please use the model number located on the water heater
when contacting us with questions concerning this unit.
How to Make a Claim
Please Call (877) 835-1705, 7:30 – 4:00 CST
Proof of purchase in the form of a dated sales receipt
and warranty registration is required in order to obtain
warranty service, and should be included with your claim.
The product owner should submit the warranty claim
directly to Intellihot at the following address or online at
www.intellihot.com:
Intellihot Green Technologies Inc.
Attn: Warranty Claims
2900 W. Main St.
Galesburg, IL 61401
Phone: 877-835-1705
Fax: 309-296-8984
Email: info@intellihot.com
NOTES
Requirements for the State of Massachusetts
Notice Before Installation
This appliance must be installed by a licensed plumber or
gas fitter in accordance with the Massachusetts Plumbing
and Fuel Gas Code 248 CMR Sections 2.00 and 5.00.
IMPORTANT: In the State of Massachusetts (248 CMR
4.00 & 5.00)
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven
(7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
5. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gasfi tter shall observe that a hard wired carbon
monoxide detector with an alarm and battery backup
is installed on the fl oor level where the gas equipment
is to be installed. In addition, the installing plumber
or gasfi tter shall observe that a battery operated
or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the
dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be
the responsibility of the property owner to secure the
services of qualifi ed licensed professionals for the
installation of hard wired carbon monoxide detectors
7. SIGNAGE.
A metal or plastic identifi cation plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in
line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2)
inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
8. INSPECTION.
The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a)1 through 4.
a. In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or
an attic, the hard wired carbon monoxide detector
with alarm and battery back-up may be installed on
the next adjacent fl oor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30)
day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
6. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply
with NFPA 720 and be ANSI/UL 2034 listed and IAS
certifi ed.
64Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
NOTES
Intellihot Green Technologies, Inc. 65
www.intellihot.com (877-835-1705)
NOTES
66Intellihot Green Technologies, Inc.
www.intellihot.com (877-835-1705)
Intellihot Green Technologies Inc.
2900 W. Main St.
Galesburg, IL 61401
Phone: 877-835 1705
Fax: 309.296.8984
Email: info@intellihot.com
www.intellihot.com
Intellihot Green Technologies Inc.
Dealer / Installer Contact Information:
Rating and safety information inside.
(
Ca
ra
ct
é
r
i
sti
q
u
e
s
e
t
r
e
ns
e
Box if
ropan
p
z
)
a
e
t
Check
c
re
i au g
i
d
ert
n
Converted to
io
conv
at
l
ti
Propane Gas
n
case si
ve
à
a
l
né
Cocher
)
stanta
e
in
pan
sion* to
e
u
ro
p
er
tiq
az
a
g
m
u
a
uto
e
a
lac
p
r
u
s
ffe-eau
Field Conv
opane Gas
sion*
(Chau
ver
Pr
)
T
r
Con
(
EN
M
E
S
)
SEUL
el
199,000
ur
0
t
EUR
I
er Heate
R
na
É
T
Pa)
gaz
IN
y Preset
k
20,00
AVEC
Wat
N
TIO
ne pour
al Gas
si
actor
SA
u
LI
F
10.5 W.C. (2.62 kPa)
C. (0.76
en
tur
e
g
TALLATION À L'
Na
INS
C. (2.74 kPa)
(Régla
3.0 W.
OUR
W.
INE POUR UTI
P
Y PRESET FOR USE WITH
(
D'US
S
11.0
GE
199,000
tic Instantaneous
ÉGLA
R
FACTOR
É
C. (3.20 kPa)
20,000
kPa)
TION ONLY
TURAL GA
PR
. . .
150 psi (1034 kPa)
m
ALLA
TUREL
s
13.0 W.
C. (2.00
A
15 psi (103 kPa)
N
. . . . . . . . . . . . . .
NA
Amp
)
GAZ
8.0 W.
: . .
C. (2.00 kPa)
)
az
g
e
d
e
n
p
y
me
(T
lasse
C
er le
r
t
n
(E
ressur
P
aximum)
m
)
e
é
riv
r
mum
i
'a
as Pressure:
d
min
e
um (pour ajustements))
rivé
m
r
a
'
ini
d
m
e
é
v
ri
ar
ter Pressure:
ximum)
ter Pressure: . . . . . . . . . . . . .
um)
m
)
t
ni
i
n
m
me
q
re
i
t
:
Energy Facto
rgé
recouv
y /
e
d
cienc
Facteur éne
. . . . . . . . . . . . . . . . . .
que /
i
n
a
ty M
i
l
a
.2 du
6
)
4
Qu
x
r
i
t 11
A
n
leme
me
g
rè
age
u
g
a
Minimum Clearances
(Dé
Non-
Des
(
2 i
5/8 in
in
6
au)
1/2 i
hauffe-e
-eau)
e
12 in (30.4 cm)
ion)
: Btu/hr Maximu
)
t
e:
. . . . . . . . . . . . .
. . . . . . . . . . . . .
.
e)
u
gement
a
"South Coast A
ts m
n
Combustibles
n-combus
o
n
(50.8 mm)
n
(
n (1
Btu/hr Minimum . . .
From
(1
5
1
)
94
265 GPH (1003 LPH)
0.
8.0W.
ation
er
p
)
O
Up to 98% / 0.94
de
m
d
e
tion et
n
r
Jusqu'à 98 % /
a
pp
(
a
u
l
. . . . . . . . . . . .
d
0
al
procedure.
é
t
150 psi (1034 kPa
2
c
s
tion
e
n
a
ro
i
ion
l
d
p
s
d'
al
rs
Less than 20 ppm
l
n
e
v
ue
. . . . . . . . . . . .
n
Inst
n
o
(Moi
o
15 psi (103 kPa)
c
r
ma
o
u
Refer t
ment pour la
*
e
rer a
n
n
éfé
manual f
94)
.
265 GPH (1003 LPH)
0
/
Se r
nctio
(
ion.)
fo
de
convers
Up to 98% / 0.94
Jusqu'à 98 %
.
(
ppm)
20
ETL)
de
t
s
n
. . .
n
Less than 20 ppm
a
l
l
o
(Moi
(C
ETL STICKER
. . . .
t)
r:
ric
t
is
D
t
n
146.2)
1
y Manageme
Rule
t
ric
Qualit
t
r
i
is
ustible
D
b
on
i
e)
l
b
From Com
ti
Construction
s
ne construct
mums)
'u
i
)
n
i
(D
combu
rie
é
s
e
d
.
m)
éro
Serial Number:
m
m
6 in (15.2 cm)
tibles)
(Nu
)
2 cm
5/8 in (15.8
GT-LBL-0005-01
I
(15.
in
6
m)
m
5.8
2 in (50.8 mm)
)
om
2 cm
.
12 in (30.4 cm)
m)
m
ntellihot Green Technologies Inc
I
llihot.c
2.7
77) 835- 1705
nte
2900 W. Main St.
Galesburg, IL 61401
Phone: (8
www.intellihot.com
Email: info@i
b:
We
ect-Vent Automa
Dir
olt, 60 Hz, 5
FOR INDOOR INST
120 V
pe of Gas
Ty
Input Rating
de gaz
nlet G
I
sion
Maximum Inlet Gas
Pres
e gaz
(
mum
n d
o
i
s
s
Mini
e
r
P
(
Wa
Minimum Inlet Gas Pressure (for adjustments): . .
eignem
ent
s
d
e
s
é
cur
i
t
é
à
l
'
in
té
r
ie
ur)
(Pression de gaz d'
d'
n
ximum
Ma
ressio
(P
Minimum
(Pression d'
érist
t
c
ra
Recovery Rating: . . . .
Ca
(
t
é
t
caci
i
Thermal Effi
Eff
(
ons
i
s
s
NOx Emissions:
o
(Émi
t
t
n
a
rmém
o
f
ursu
P
(
(con
Top of heater
(Dessus d
Back of heater
(Arrière du c
Front of heater
(Avantdu chauff
(Côté)
Side
canalisat
é
Bottom of cabinet
t
(Cô
au ma
e
Wa
au
e
e
qu
i
herm
de NO
South Coast
ent
u chauffe-eau)
Serial Number: _________________________________
Date of Purchase: ___ / ___ / ______