I n t r o d u c t i o n
The CAP 2020 DR H is a proximity card based access control device, with hotel room economizer function, part of the CIB-tech automation system.
The unit can control the entry in a hotel room. It accepts up to 1024 users and provides entry via the use of proximity cards. It can control the power supplied to the room, based on the state of the room's proximity card holder.
Additional Equipment Required
1. Functional CIB-tech system
A minimal number of essential CIB-tech components to make a functional CIB-tech system1.
2. Proximity card and/or PIN code reader with bell button, for entry request
A proximity card reader with a 26-bit Wiegand-type output, further referred to as “Reader A”2.
NOTE: The proximity card reader must supply the bell button event in Wiegand data format.
3. Proximity card holder
Proximity card holder with built in proximity card reader (ex IBS product RFE 10 F), or any simple, contact based card holder with voltage free contacts2, further referred to as “Smart card holder” or “Simple card holder”.
4. Open door sensor (optional)
Normally open or normally closed type with voltage free contacts2.
5. Electric door lock
Fail safe (power to lock) or fail secure (power to open) strike lock/door bolt/magnetic lock2.
6. Power supply for electric door lock
Refer to the electric door lock's characteristics to choose a suitable power supply. A power supply with battery backup is recommended.
7. Circuit breaker
Miniature circuit breaker (MCB) or DIN-Rail mountable fuse must be used for over-current protection.
T e c h n i c a l S p e c i f i c a t i o n s
Electrical characteristics
Power Supply
The CAP 2020 DR H functions as a node in a CIB-tech system, being powered from the CIB-tech system's power supply via the CIB-tech connectors.
Operating voltage range: 20 to 28V DC (nominal 24V DC) Supply current
Standby current (without reader/card holder): 22mA
Maximum current (without reader/card holder): 50mA
Typical standby current (with reader and card holder): 110mA
Absolute maximum current (with reader and card holder): 300mA
Power output
The CAP 2020 DR H can provide power to the proximity card reader and card holder.
Output voltage: 12V DC
1 See “CIB-tech installation manual” for details. 2 See “Recommended equipment to be used with CIB-tech” for details
CAP 2020 DR H ©2009 - Intelligent Building Solutions 1
Maximum output current: 2 x 170mA
Relay output (for electric door lock)
If an electric door lock with a DC power supply is used, an external suppressor diode must be used3.
Rated voltage: 24V AC/DC Rated current: 2A
Relay output (for room power)
Rated AC voltage: 250V AC Rated current: 16A
Signal Input
Wiegand data input:
supported input voltage levels: 0 - 5V
input impedance: 1KOhm Open door sensor: N.O. or N.C. with voltage free contacts Contact based card holder: N.O. with voltage free contacts
Signal Output
External LED control:
output voltage levels: 0 - 5V
output current: 15mA
Mechanical characteristics
The CAP 2020 DR H has a standard 3-module wide enclosure for M36 type DIN-Rail
Dimensions: 96mm W x 52mm L x 60mm D
Weight: 130g
Environmental characteristics
Operating temperature: 0ºC to 65ºC
Storage temperature: -10ºC to 70ºC
K e y F e a t u r e s
Programmable via the CIB-tech system with dedicated software
Controls unidirectional access through one door
Provides access for up to 1024 users
Users may be members of one of up to 30 groups with different access rights, based on a weekly
schedule. Groups have individual access right expiration dates
Controls the power supply for one hotel room.
Room power is automatically enabled when a valid entry request is detected.
Programmable “keep room power on” time, after card is removed from the card holder.
Support for Simple card holder (any card may be placed in the holder and the room will be powered
on) and Smart card holder (the room will be powered on only if a valid proximity card is placed in the RFE 10 F).
Support for an open-door sensor input for detecting actual door openings.
Internal battery powered real-time clock. Clock keeps running in case of power failure
Internally stored 1024-entry access log with time stamps
Internally stored 1024-entry open door event log with time stamps
3 IBS product PS 1213 D is a dedicated power supply for door locks: 12V AC and DC output, internal suppressor
diode. Note that battery backup for door lock is not possible with it. Please verify whether it is suitable for your door lock!
CAP 2020 DR H ©2009 - Intelligent Building Solutions 2