15
Plumbing for Tank Installation (Dual Tank Systems)
Follow these instructions and refer to Figure 4.1:
A. Turn off the cold water feed to the existing water heater. Ensure that the existing
shut off valve is working correctly, and repair or replace it if necessary.
B. Locate the solar storage tank as close as possible to the existing water heater.
C. Set the new storage tank on a solid floor foundation and use shims as needed to
level it. Water heater tanks located in or above the living space shall be installed on
a drip pan with a drain line to a waste line or outside or have other means to safely
remove any excess liquid.
D. Position the new storage tank so that the two inspection covers and drain valve are
accessible. Building materials adjacent to solar components should not be exposed
to elevated temperatures. In a dual tank system, do not connect any element(s) in
the solar storage tank to electrical power. Backup heat is provided by the second
(existing) electric or gas water heater.
E. Install the supplied pressure and temperature valve with a 3/4" drain line to
discharge no higher than 6" from the floor, or as required by local codes.
WARNING
F. Install a tempering (mixing) valve to reduce the possibility of scalding injury to the
system users. The tempering valve must allow a range of selectability of at least
10"C (18"F) and must include a set point of 50"C (122"F).
WARNING
G. It is recommend that the cold water feed line to the mixing valve be connected to the
bottom of the valve in order to avoid unwanted thermosyphon or possible damage to
certain types of mixing valves. A heat trap is required for the hot side of the Watts
70A mixing valve. See manufacturer’s instructions
CAUTION
H. Install the cold and hot water lines to the tank. Install 3 3/4" 2 way ball valves as
shown in Figure 4.1 to allow the solar storage tank to be bypassed if ever necessary.
Install an in line thermometer in the line between the “Hot” outlet of the solar storage
tank and the “Cold” inlet of the backup tank. Dielectric unions at the tank
connections are not required in all code jurisdictions, however, they are a good idea
since the nipples supplied with most tanks are not a dielectric connection.
I. Insulate all hot water lines, and the final 5 feet of the cold water feed line (or all the
exposed cold water feed line if less than 5 feet is exposed from the wall to the tank)
with pipe insulation having a minimum R2.6 value, such as Insul-Tube® with at least
a 1/2” wall thickness.
If you are replacing the existing electric or gas water heater, follow the water heater
manufacturer’s instructions, and conform to all applicable local codes for the water heater
installation as well as the solar system installation.
Avoid heat damage to the tempering valve.
Remove the thermostatic assembly before soldering.
Once the tempering valve has cooled, reinstall the valve assembly.
T & P relief valve discharge line
must not be blocked or reduced in size.
An approved tempering valve must be used
in the hot water line to the house.