Integra PRO-VISION User Manual

O
X
TION IS POWER
PRO-VISION
Temperature controller
User’s Manual
Current conditions
Set Point
Minim um ventilation
On/Off Settings
Inlets/Vents
Main Menu
Start flock / Egg
Light Programs
Alarms
History
Set-u p
M 890-00515 rev.07
MAIN MENU
BACK
B
BOX
INFORMATION IS POWER
1
2
3
4
5
6
ENTER
360
DEL
7
8
9
+/-
0
AM/PM
REV.09
PRO-VISION
WARNINGS
The warranty can be void if this product is used in a manner not specified by the manufacturer.
Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information con­tained in it is however subject to change without notice due to further developments.
2
PRO-VISION rev.07
PRO-VISION

TABLE OF CONTENTS

1. INTRODUCTION .................................................................................. 6
1.1. Precautions ................................................................................................. 6
1.2. Symbols of the Manual ................................................................................. 6
1.3. Controller’s Overview ................................................................................... 6
1.4. Main Features .............................................................................................. 7
2. MOUNTING INSTRUCTIONS ................................................................. 7
2.1. Installing the Controller on the Wall ................................................................ 7
2.2. Connections ................................................................................................ 7
2.2.1. Main Wiring ...........................................................................................7
2.2.2. Alarm Connection ...................................................................................8
2.2.3. Sensor Inputs .........................................................................................8
2.2.4. 0-10V Output Connection ........................................................................8
3. USER INTERFACE ................................................................................ 8
3.1. Location of the Controls ................................................................................ 8
3.2. Adjusting a Parameter ................................................................................... 8
4. INSTALLATION SETUP ......................................................................... 9
4.1. Setting the Time & Date ................................................................................ 9
4.2. Password ................................................................................................... 9
4.2.1. Entering a Password ...............................................................................9
4.2.2. Changing / Retrieving a Password .............................................................9
4.3. Controller Programs ................................................................................... 10
4.4. Set-up Menu .............................................................................................. 10
4.5. Sensor Assignment ..................................................................................... 14
4.5.1. Assigning the Sensors ...........................................................................14
4.5.2. Assigning the Digital Inputs ...................................................................14
4.5.3. Selecting the Attic Sensor .....................................................................15
4.5.4. Egg Room Sensors ................................................................................15
4.5.5. Main Breaker Sensor .............................................................................15
4.6. Calibrating the Inputs .................................................................................. 15
4.7. Relays ....................................................................................................... 16
4.7.1. Relay Assignment .................................................................................16
4.7.2. Relays with Current Sensors ..................................................................16
4.8. Non-Brood Zones & Clean Mode ................................................................... 17
4.9. Test Mode ................................................................................................. 18
4.10. Version ..................................................................................................... 18
5. SET POINTS .......................................................................................19
5.1. Temperature & RH Set Points ...................................................................... 19
5.2. Set Point Ramp .......................................................................................... 19
6. VENTILATION & COOLING ..................................................................20
6.1. Overview of the Ventilation Concepts ........................................................... 20
6.2. Minimum Ventilation .................................................................................. 21
6.2.1. Minimum Ventilation Timer ....................................................................21
6.2.2. Min Ventilation Timer Ramp ...................................................................22
PRO-VISION rev.07
3
PRO-VISION
6.2.3. Minimum Ventilation Fans ......................................................................22
6.2.3.1. Fan Selection ...............................................................................22
6.2.3.2. Stir Fans in Minimum Ventilation .....................................................22
6.2.3.3. Fan Cycling ..................................................................................23
6.2.4. Air Intake in Min Ventilation ...................................................................23
6.3. Lateral Ventilation ...................................................................................... 25
6.3.1. Lateral Ventilation Fans ........................................................................25
6.3.2. Attic & Sidewall Vents based on Temperature ..........................................26
6.3.3. Attic & Sidewall Vents based on Static Pressure ......................................27
6.3.3.1. Compensation on Pressure Set Points ..............................................27
6.3.3.2. Settings .......................................................................................28
6.4. Natural Ventilation ...................................................................................... 29
6.5. Tunnel Ventilation ...................................................................................... 30
6.5.1. Principle of Operation ............................................................................30
6.5.2. Tunnel Ventilation in Standby .................................................................30
6.5.3. Tunnel Fans .........................................................................................31
6.5.4. Tunnel Inlets ........................................................................................32
6.5.4.1. Temperature-based Tunnel Inlet .....................................................32
6.5.4.2. Pressure-based Tunnel Inlets .........................................................33
6.6. Stir Fans ................................................................................................... 34
6.7. Cooling Output .......................................................................................... 35
6.8. Fogger Output ........................................................................................... 36
7. HEATING ...........................................................................................37
8. LIGHTS .............................................................................................38
8.1. Principle of Operation .................................................................................. 38
8.2. Settings .................................................................................................... 39
8.2.1. Light Program Settings ..........................................................................39
8.2.2. Light Peak Settings ...............................................................................39
9. TIME CLOCKS ..................................................................................40
9.1. Regular Time Clocks ................................................................................... 40
9.2. Time Clocks in a Breeder Facility .................................................................. 41
10. WATER LINE FLUSH ...........................................................................42
11. EGG ROOM OUTPUTS ........................................................................43
12. RELATIVE HUMIDITY (RH) COMPENSATION ..........................................44
12.1. High RH Comp.on the Min Vent. Timer ......................................................... 44
12.2. High RH Comp. with Heaters in Min Vent. ..................................................... 44
12.3. RH Comp. with Cooling & Foggers ............................................................... 45
4
PRO-VISION rev.07
PRO-VISION
13. ALARMS ...........................................................................................46
13.1. Alarm Log ................................................................................................. 46
13.2. Temperature Alarms ................................................................................... 46
13.2.1. High/Low Temperature Alarms ...............................................................46
13.2.2. Temperature Alarms in Clean Mode ........................................................46
13.2.3. Outdoor Temperature Compensation .......................................................47
13.2.4. Temperature Alarm Settings ...................................................................47
13.2.5. Critical Temperature Ramp .....................................................................48
13.2.6. Static Pressure Alarms ..........................................................................48
13.2.7. Water Spill Alarms ................................................................................49
13.2.8. Feeder Alarms ......................................................................................49
13.2.9. Amperage Draw Alarms .......................................................................50
14. MONITORING FUNCTIONS ..................................................................51
14.1. Current Conditions ..................................................................................... 51
14.1.1. Current Condition Screen Saver ..............................................................51
14.1.2. Current Input/Output Status ...................................................................51
14.2. History Menus ........................................................................................... 52
14.3. Animal Age & Count ................................................................................... 52
14.4. Egg Count ................................................................................................. 53
14.5. Operation Costs & Current Consumption ....................................................... 53
15. UPDATE & BACKUP ............................................................................53
16. DIAGNOSTIC .....................................................................................54
17. TECHNICAL SPECIFICATIONS ..............................................................55
18. INDEX ...............................................................................................56
PRO-VISION rev.07
5
PRO-VISION

1. INTRODUCTION

1.1. Precautions

WARNING: Read and save these in­structions!
Safety may be jeopardized if the equipment is used in a manner not specified by the manu­facturer. Carefully read and keep the following instructions for future reference.
We strongly recommend installing supplemen­tary natural ventilation as well as a backup thermostat on at least one cooling stage.
Although fuses at the input and outputs of the controller protect its circuits in case of an overload or over-voltage, we recommend installing an additional protection device on the controller’s supply circuit.
The room temperature where the controller is located must always remain between 32°F and 104°F (0°C to 40°C). Indoor use only!
To avoid exposing the controller to harmful gases or excessive humidity, it is preferable to install it in a corridor.
If the equipment is used in a manner not specified by the manufacturer, the protec­tion provided by the equipment may be impaired.

1.2. Symbols of the Manual

Warning. Read the following text carefully; it contains important information which, if ignored, may cause the controller to operate improperly.
High Voltage. Hazard of electrical shock. Read the message and follow the instructions carefully.
Pay attention. The following text contains very useful information.
Press on the proper menu selector.
Press the “Main Menu” push-button.
Both direct and alternating current (AC/DC).
Direct current (DC).
Alternating current (AC).
Earth Ground Terminal Primarily used for functional earth terminals which are generally asso­ciated with test and measurement circuits. These terminals are not for safety earthing purposes but provide an earth reference point.

1.3. Controller’s Overview

The PRO-VISION is an electronic device used for environmental control in livestock build­ings. It combines sidewall, natural and tunnel ventilation into one powerful system.
OUTPUTS — The PRO-VISION can control up to 128 relays located in external relay panels. These relays can be used to control the following outputs:
32 heaters; 16 hi-fire heaters; 5 lateral fans; 20 tunnel fans; 1 stir fan; 6 cooling outputs; 6 foggers 2 tunnel inlets; 8 natural ventilation curtains; 1 sidewall vent; 1 attic vent; 12 time clocks; 2 light outputs (0-10V); 8 water line flushing outputs; 1 egg room heater; 1 egg room cooling output; 1 egg room humidity output; 1 alarm output; 1 backup relay; 4 feeder cut-off relays.
Do not spray water on the controller! In order to clean the control, wipe it with a damp cloth.
Before servicing or cleaning unit, switch power off at service panel and lock the switch disconnecting means to prevent power from being switched accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
6
PRO-VISION rev.07
For Customer Use: Enter below the serial number located on the side of the alarm system and keep this information for future reference.
Model: PRO-VISION
Serial number:
Date installed:
BUILT-IN INPUTS:
32 inside temperature sensors (8 basic
temperature inputs & up to 24 additional
inputs with the expansion cards); 1 outside temperature sensor; 1 relative humidity sensor; 1 static pressure sensor; 1 NH3 sensor; 1 wind speed sensor; 6 digital inputs (water meters and/or feeder
monitoring inputs).
Refer to the end of this manual to con­nect the sensors and loads.
PRO-VISION

1.4. Main Features

Easy-to-Use Controller — With its conve-
nient menu selectors and its large graphic LCD screen, the PRO-VISION is certainly the most easy-to-use temperature controller on the market.
10 Controller Programs — The controller al­lows using 10 different programs to control the room temperature. It is thus possible to activate a specific program that uses par­ticular temperature settings according to the animal age for instance.
32 Indoor Temperature Sensors — Up to 32 temperature sensors can be connected to the controller to obtain an accurate read­ing of the average room temperature and a faster reaction time. The controller comes with 8 basic temperature inputs and 24 ad­ditional inputs can be added with the optional extension cards.
Minimum Ventilation Cycle — When ven­tilation is not required to reduce the room temperature, fan outputs can run either con­tinuously or intermittently to reduce humidity levels and supply oxygen to the room.
Recuperation of the Warm Attic Air — In order to make energy savings, the controller can extract the warm air from the attic and send it back into the room.
Natural Ventilation — This is a ventilation mode that uses existing air currents and natural convection to move and distribute air through the building.
Humidity Control — The control offers many ways to compensate for high or low humid­ity levels.
Control of the Air Inlet Movement — The movement of the air inlets (sidewall vents or tunnel inlets) can be coordinated with the operation of the fans or according to the pressure level. This allows the inlets to be adjusted correctly, without the influence of uncontrollable factors such as wind or air from adjoining rooms.
Egg Room — In addition to controlling the ambient temperature in the house, the PRO­VISION can control the temperature and humidity conditions in an egg room. It can also keeps a tally of the number of eggs produced each day.
Operation Cost Monitoring — The control­ler can monitor the amperage draw of the outputs and give you daily reports of the operation costs.
History Menus — The history menus allow monitoring the sensor readings and verify the run time of some outputs. Below is a list of all available histories menus:
Static pressure sensor ...............400 days
Heater run time ..........................400 days
Feeder run time .......................... 400 days
Water consumption .....................400 days
Mortality ................................... 400 days
Alarm Management — The controller provides alarms for high-low temperatures, defective sensors and other system failures. It keeps in memory the 75 latest alarm conditions.
Password Protection — Different passwords levels can be enabled to restrict access to some menus of the controller.
Backup Battery — A backup battery allows the unit to keep time in case of a power failure.
USB Connector — Controller backups and updates can be made easily with a standard USB memory card.
Overload and Over-voltage Protection — Re­settable fuses are provided at low-voltage inputs of the controller to protect its circuitry in the case of an overload or over-voltage.
Computer Control — The controller can be connected to a computer, thus making it possible to centralize the management of information and diversify control strategies.
Tunnel Ventilation — When the room tem­perature rises, tunnel ventilation reduces the actual temperature perceived by the animals.
2. MOUNTING INSTRUC­TIONS
2.1. Installing the Controller
on the Wall
Fasten the two metal brackets on the mount­ing holes located behind the controller using four screws. Then, mount the enclosure on the wall using four other screws. Leave a clearance of at least 16” to the left of the enclosure to allow the cover to be removed for maintenance.
Minimum and maximum sensor readings:
Ambient temperature ................400 days
Inside temperature sensors ............7 days
Outside temperature sensor .......400 days
Relative humidity sensor ...........400 days
Test Mode — A test mode allows simulat­ing temperature changes and verifying the controller‘s performances.

2.2. Connections

2.2.1. Main Wiring
Refer to the wiring diagram enclosed with this user’s manual to connect the controller. Drill holes at the bottom of the enclosure to pass the wires and install watertight connectors to prevent water from entering in the enclosure. Do not make any holes at the side and top of the enclosure.
All wiring must be done by an autho­rized electrician and must comply with applicable codes, laws and regulations. Make sure power is off before doing any wiring to avoid electrical shocks and equipment damage.
PRO-VISION rev.07
7
PRO-VISION
Do not install rigid conduit into electrical knockouts. Only nylon cable glands are permitted for cable or wire fastening.
The controller has no power-on switch. An external switch or circuit breaker shall be included in the building instal­lation to interrupt power to L and N electric power lines. It shall be in close proximity to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.
2.2.2. Alarm Connection
There are two types of alarms on the market. One type activates when current is cut off at its input; the other type of alarm activates when current is supplied at its input. For an alarm of the first type, use the NC terminal as shown on the wiring diagram. For an alarm of the second type, use the NO terminal.

3. USER INTERFACE

3.1. Location of the Controls

Graphic LCD display — The large graphic
LCD screen is used to display the parameters and menus.
Menu selectors — The menu selectors allow selecting a tab on screen.
Home key — This short-cut key provides ac­cess to the main menu.
Back — The “Back” key is used to go back to the previous menu.
Arrow keys — The arrow keys allow select­ing a parameter on screen. The right and left arrow keys can also be used to move through the display by pages (left=page-up, right=page-down).
Enter — The “Enter” key is used to change the value of non-numerical parameters. Pressing this key makes a drop-down choice menu appear.
Adjustment buttons — The adjustment but­tons allow increasing or decreasing the value of a parameter.
2.2.3. Sensor Inputs
Sensors operate at low voltage and are isolated from the supply. Make sure that sensor cables remain isolated from all high voltage sources. In particular, do not route the sensor cables through the same electri­cal knockout as other cables. Do not connect the shield from the sensor cable to a terminal or a ground.
Extending a sensor: Each sensor can be ex­tended up to 500 feet (150 meters).
To extend a sensor: Use a shielded cable of outside diameter between 0.245 and 0.260 in (6.22 and 6.60 mm) (the cable dimensions should not be under 18 AWG) to ensure the cable entry is liquid tight. Do not ground the
shielding.
It is preferable to solder the cable joint to ensure a proper contact between the two cables.
Delete — The delete key allows clearing the last digit that has been posted while editing a
Graphic
LCD
Display
numerical value.
+/- & AM/PM but ton — This push-button allows entering a negative value and allows changing the AM/PM time in­dicator.
Digital keypad — The digital keypad is used to modify the value of numerical parameters.
Alarm Status LED — The alarm LED turns red when an alarm
Menu
Selectors
Home
Key
Back
button
Arrow keys
(Right = Page-Down
Left = Page-Up)
situation is active or turns green when there is no alarm.

3.2. Adjusting a Parameter

When a parameter is selected, the control­ler gives indications about the way it can be modified at the bottom of the screen. A parameter can either be modified with the adjustment buttons, with the digital keypad or by pressing the “Enter” key and then selecting an item from a drop-down menu. Follow the instructions on screen to modify the value of a parameter.
Do not run sensor cables next to other power cables. When crossing over other cables, cross at 90°.
Defective sensors: An alarm is generated when a defective sensor is detected. Defec­tive sensors are identified in the “Alarm” menu. Refer to chapter 13 fo r f ur the r information on the alarms.
2.2.4. 0-10V Output Connection
It is recommended to use a 18 to 22 AWG wire to connect the devices to the 0-10V outputs. This type of output can be used to connect various devices such as lights.
Alarm
AM/PM
Status LED
3
6
9
+/-
+/-
AM/PM Button
Delete
Main Menu
Current conditions
Set Point
Minimu m ventilation
On/Off Settings
Inlets/Vents
MAIN MENU
BACK
ENTER
Start flock / Egg
Light Programs
Alarms
History
Set-up
Adjustment
Buttons
Digital Keypad
1
2
4
5
7
8
DEL
0
8
PRO-VISION rev.07
PRO-VISION

4. INSTALLATION SETUP

4.1. Setting the Time & Date

1. Select:
Main menu
* Set-up
Time & Date
* A complete- access password may be required to access this menu (see sec. 4.2.1).
Time & Date
Tue Jan 1 20XX
11:59:59 am
To modify use
Each of the following parameters must be set in turn.
2. Press “En ter” to start editing the month.
3. Use the navigation buttons to select the current month from the scrolling list.
4. Press “En ter” to continue.
5. The day is now selected. Use the adjust­ment buttons or the numerical keypad to change the current day.
6. Press “En ter” to continue.
7. The year is now selected. Use the +/­push-buttons or the numerical keypad to change the current year.
8. Press “En ter” to continue.
9. The time is now selected. Use the nu­merical keypad to set the time of day and use the AM/PM key to change the time indicator (if required).

4.2. Password

The controller can identify 6 users that are having different privilege levels. Below is a list of possible privileges:
History — This privilege provides access to all read-only menus such as the “Current Condi- tion s”, “A la rm ” & “His tory” menus.
Settings — This privilege provides access to all menus except for the “Se t- up” menu.
All — This password provides complete ac­cess to all menus of the controller.
Using password security is optional. Re­fer to the Set-up menu to enable/disable this protection (see section 4.4).
4.2.1. Entering a Password
If the password protection is used, the control­ler will prompt for a password each time a user that does not have the proper privileges tries ac­cessing a protected menu. Refer to section 4.4 to enable or disable the password protection.
Please enter password
****
1. Type in your 4-digit password.
The message “Wrong Password” is dis­played either if the posted password is incorrect or if the privileges associated with it are not sufficient to access the protected menu.
4.2.2. Changing / Retrieving a Password
A user that has complete access to the con­troller can view and modify the passwords and privileges of all users.
1. Select:
Main menu
* Set-up
* * Password
* A complete-access password may be required to access this menu (see sec. 4.2.1).
* * This menu is accessible if the password protec­tion is enabled in the Set-up menu (see sec. 4.4).
Passwor ds
Sec urity
User 1
User 2
User 3
User 4
User 5
Maste r
To modify use
2. Set the following parameters:
Security — Select the level of privileges that must be selected after 5 minutes of inactivity (history, settings or all).
Cur. user — This is user currently logged in (for information only).
User 1-5 — Set the password of each user.
Choose easy-to-remember passwords and write them down in a safe place!
Master — Set the master password. This user automatically has complete access to all menus of the controller.
Histor y
1111
2222
3333
4444
5555
0610
Cur. user User 1
Level
Level
Level
Level
Level
Settings
Histor y
Histor y
Histor y
All
10. Press “E nte r” to validate the time and date.
Level — Assign the desired level of privileges to each user. *NB. T he Master user automatically
has complete access to all menus.
PRO-VISION rev.07
9
PRO-VISION

4.3. Controller Programs

Program definition: A programs is an assem-
bly of settings (temperature settings, relay assignment, sensor assignment, etc.) that can be enabled at different moment of the breeding process. In all, the controller can use 10 different programs.
Refer to the Set-up menu to enable the de­sired number of programs (section 4.4).
Make sure the right program is selected before adjusting any parameter.
1. Select:
Main menu
* Start Flock
* A password may be required to access this menu (see section 4.2.1).
Start flock
Mortality
Loss (%)
Stat Flo ck
Age
Clean M ode
To modify use
2. Set the following parameters:
Program — Activate the desired controller program. *Only the programs that are enabled in
the Set-up menu can be used (see section. 4.4).
0
0.00
No
10000
On
Remaining
Birds placed
Age
Program
New Mortality
Alarm low T°
-
10000
10000
Progra m 1
0
No

4.4. Set-up Menu

The following section shows how to custom­ize the controller for your particular applica­tion. It shows how to enable and set the inputs & outputs of your controller. Normally, this setup needs to be done only once.
Hint: Use the right and left arrow keys to scroll the display by pages (right = page-down, left = page-up).
1. Select:
Main menu
* Set-up
* A complete-access password may be required to access this menu (see sec. 4.2.1).
2. Set the following parameters:
Contrast — Adjust the contrast of the LCD screen. Default = 50%.
Backlight intensity — Set the intensity of the LCD screen backlight as required. This param­eter ranges from 1 (darker) to 5 (brighter). Default = 3.
Key beeper tone — Adjust the volume of the keypad beeper.
Language — Select the desired language (English or Spanish).
Hint! Press and hold the main menu button for 5 seconds to switch from a language to the other.
Controller used for — The controller can either be used in a breeder, broiler, layer or turkey production facility. The breeder facility gives you access to additional parameters to monitor an egg room; the breeder and turkey options give you access to the natural ventila­tion mode (natural curtain).
Time mode— Select the desired time format (AM/PM or 24 hours).
Pressure unit — Select the desired pressure units (inches of water (“WC) or Pascal (Pa)). * This parameter is accessible if the static pressure
sensor is enabled above.
Use min. vent ramping ? — Select “Yes” to enable the ramping function on the Time ON portion of the minimum ventilation timer. Refer to section 6.2.2 for further information on this feature.
Use relative humidity (RH) sensor ? — Select “Ye s” if a humidity sensor is connected to the controller. Note that if the controller operates in a breeder facility, the RH sensor is used to control the humidity level in the egg room; if the controller is located in a broiler, layer or in a turkey facility, the RH sensor is used to control the humidity level in the house.
Use RH min vent compensation? — Select “Ye s” for the controller to adjust On Time portion of minimum ventilation cycles as a function of the relative humidity level. Re­fer to section 12.1 for further information about this RH compensation method. * This
parameter is accessible if the controller is used in a broiler, layer or turkey facility and if the RH sensor is enabled above.
Use outside T° sensor ? — Select “Yes” if an outside temperature sensor is connected to the controller.
Use critical alarm? — Select “Yes” to enable the critical temperature alarm condition. * This parameter is common to all programs of the
controller.
Number of programs — The controller can use several programs to control the temperature. Enable the desired number of programs (1 to 10 programs) * This parameter is common to all
programs of the controller.
Save current program to — This function allows copying all parameter settings of a program onto another program (it thus avoids repeating the same programming sequence several times). Select the program on which the current program must be pasted. * This
parameter is accessible if more than 1 program is enabled above.
10
PRO-VISION rev.07
Temperature unit — Select the desired tem­perature units (Celsius or Fahrenheit)
Use static pressure sensor ?— Select “Yes” if a static pressure sensor is connected to the controller.
The controller automatically selects the newly pasted program after the saving process.
Confirm — Select “Ye s” to start the copying process. The message “Copy successful” will be displayed after data transfer. *This parameter is
PRO-VISION
accessible if the program selected above is different from the program currently in use.
Number of water meters — Enable the desired number of water meters and then refer to sec­tion 4.5.2 to assign them to the digital inputs of the PRO-VISION. In all, the controller can monitor 6 digital inputs (water meters and feeder-monitoring inputs). *This parameter is
common to all programs of the controller.
Water meter unit — If a water meter is en­abled above, select the desired unit of water volume (gallons or liters). * This parameter is
common to all programs.
Number of temperature sensors — Select the number of inside temperature sensors that are connected to the controller. The control­ler initially comes with 8 temperature inputs and 24 additional inputs can be used with the expansion cards (total of 32 sensors). * This parameter is common to all programs of the
controller.
Use wind speed? — Select “Ye s” if an an­emometer is connected to the controller.
Use ammonia sensor? — Select “Yes” if an am- monia sensor is connected to the controller.
Use water flush? — Select “Ye s” to use the water line flush. Refer to chapter 10 for fur­ther information on this feature.
Number of water lines — Select the number of water line outputs in used (1 to 8 out­puts). Note that up to 2 water lines can be connected to each output. * This parameter is
ac cessible if th e wa te r ush opti on i s enabled a bo ve .
Number of natural curtains — Enable the desired number of natural ventilation curtains (0 to 8 curtains). *This parameter is accessible if
the controller is used in a turkey or breeder facility
Use cur tain inlet? — It is possible to use one natural curtain output in lateral and minimum ventilation. When a curtain is used in one of these ventilation mode, it follows the same movements as the vent inlet. When the con­troller enters in natural ventilation, the curtain output becomes a regular natural curtain again Select the natural curtain output that acts as a curtain inlet in lateral and minimum ventilation or select “Non e” to disable this function *This parameter is accessible if natural
ventilation curtains are enabled above.
Number of heaters — Enable the proper number of heating outputs. If the controller is used in a breeder, broiler or layer production facility, the number of heaters ranges from 1 to 16 and can be doubled with the “Hi Fire” option; if the controller is used in a turkey production facility, the number of heaters ranges from 1 to 32.
Use heater RH compensation ? — Select “Ye s” for the controller to activate the heaters in timer mode when the relative humidity level is too high. Refer to section 12.2 for further information about this RH compensation method. * This parameter is accessible if the con-
troller is used in a broiler, layer or turkey facility and if at least 1 heater and relative humidity sensor are enabled above. It is also common to all programs of the controller.
Use hi fire heaters ? — Select “Ye s” to enable the hi fire option for the heating outputs. This function allows doubling the number of heating stages (refer to chapter 7 for further information on this function). * This parameter
is common to all programs and is only accessible if the controller is used in a breeder, broiler or layer production.
Number of fans — Enable the proper number of lateral fans: up to 5 fans can be used in a breeder, broiler or turkey production and up to 20 fans can be used in a layer production. *If
tunnel fans are used in a layer facility, a maximum of 5 lateral fans can be enabled; if tunnel fans are not used, up to 20 lateral fans can then be enabled.
Number of tunnel fans — Enable the proper number of tunnel fans (1 to 20 tunnel fans). *If tunnel fans are used in a la yer facility, a maximum
of 5 lateral fans can be enabled; if tunnel fans are not used, up to 20 lateral fans can then be enabled.
Number of coolings — Enable the proper number of cooling outputs (0 to 6 outputs).
RH shutoff cooling ? — Select “Yes” for the controller to disable the cooling outputs when the humidity level gets too high. Refer to sec­tion 12. 3 for further information about this RH compensation method. * This parameter is
accessible if the controller is used in a broiler, layer, or turkey facility and if at least 1 cooling output and relative humidity sensor are enabled above. It is also common to all programs of the controller.
Activate cooling low RH ? — Select “Yes” for the controller to activate the cooling outputs when the humidity level gets too low. Refer to
List of parameters Value
Contrast 50% Backlight intensity 3 Key beeper t one 100% Language English Controller used for Breeder Time mo de AM/PM Tempe rature Unit °F Use static pressure sensor? Yes/No Pressure Unit “WC Use min. vent ram ping? Yes/No Use relative humidity sensor? Yes/No Use RH min ve nt. compe nsation? Yes/No Use outside T° sensor? Yes/No Use critical alarm? Yes/No Num ber of program s 10 Save curre nt program to Progra m x Co nfir m Yes/N o Num ber of water meters 2 Water meter unit gal Num ber of T° sensors 8 Use wind speed ? Yes/No Use am monia sensor? Yes/No Use water flush? Yes/No Num ber of water lines 8 Num ber of natural curtains 8 Use curtain inlet? Yes/No Num ber of heaters 32 Use heater RH com pensation? Yes/No Use hi fire heaters Yes/No Num ber of fans 5 Num ber of tunnel fans 20 Num ber of coolings 6 RH shutoff cooling ? Yes/No Activate cooling on low RH? Yes/No Use Weedon fog gers ? Yes/No Num ber of fogger zones 2 Activate Foggers on low R H? Yes/No Num ber of feeders 3 Num ber of time clocks 12 Cloc k mode Start /Stop Feeder 1 Assigne d to clock Clk1 Feeder 2 Assigne d to clock Clk2 Feeder 3 Assigne d to clock None Use stir fan? Yes/No Stir fan base on T° Use light? Yes/No Num ber of light programs 9 Use sidewall vent? Yes/No Use tunnel i nlet? Yes/No Num ber of tunnel inlets 2 Tun nel inlet mode SP Vent inlet mode T° Vent inlet SP adjustment? Yes/No Use attic vent? Yes/No Use attic T° sensor Yes/No Use attic min vent. compen s? Yes/No Pre-opening m ode Auto Use night set point? Yes/No Use min vent. night on tim e? Yes/No Day starts at 8:00A Night starts at 6:00P Monitor breaker te mperature? Yes/No Breaker sensor Sensor 1 Use password s? Yes/No Num ber of relays 3 RP32 Use current se nsors? Yes/No Ap pr o x.o pe rat io n c ost 0.0 0$ /KW /H Fan voltage 120 V Tun fan v oltage 120 V Com munication s peed High Curre nt condition display All
(example only)
PRO-VISION rev.07
11
PRO-VISION
section 12 .3 for further information about this RH compensation method. * This parameter is
accessible if the controller is used in a broiler, layer or turkey facility and if at least 1 cooling output and relative humidity sensor are enabled above. It is also common to all programs of the controller.
Use Weedon foggers ? — Select “Ye s” to use the Weedon foggers.
Number of fogger zones — Enable the desired number of fogger zones (1 to 6 zones). *This
parameter is accessible if the foggers are enabled above.
Activate Foggers on low RH ? — Select “Ye s” for the controller to activate the foggers when the humidity level gets too low. Refer to sec­tion 12. 3 for further information about this RH compensation method. * This parameter is
accessible if the foggers an d relative humidity sensor are enabled above. It is also common to all programs of the controller.
Number of feeders — Enable the desired num­ber of feeder run time monitoring inputs and then refer to section 4.5.2 to assign them to the digital inputs of the PRO-VISION. In all, the controller can monitor 6 digital inputs (water meters and feeder-monitoring inputs). *This parameter is common to all programs of the
controller.
Number of time clocks — Enable the proper number of time clocks (0 to 12 outputs).
Use clock loop feeding? — This option al­lows defining a number of on/off cycles to be performed within a given clock cycle (see graph in section 9 .1). Select “Ye s” to enable this operating mode or select “No” to use the regular start/ stop mode. *This parameter is not
available in a breeder production.
Clock mode (Breeder mode only) — The clock mode allows stopping a time clock at a spe­cific time of the day (Start/Stop mode) or after a certain run time (Start/Run mode). Select the desired operating mode of the time clocks. Note that the “S ta rt/Ru n” option allows stop­ping the outputs with a little more precision since it allows stopping them by the seconds (contrarily to the “Start/Stop” mode which al­lows stopping them by the minutes). * This
parameter is accessible in breeder mode if at least 1 time clock is enabled above.
Feeder #x Assigned to Clock — When a feeder run time alarm occurs, the controller can open the relay associated with the feeder (see section 4.7.1) or stop a particular clock output. Select the clock output that needs to be stopped when a feeder run time alarm occurs or select “None” if no clock output needs to be stopped. *Refer to section “13.2.8.
Feeder Alarms” on page 49 to set the maximum run time of the feeders or to restart a feeder after it has been stopped.
Use stir fan? — Select “Yes” to enable the stir fan output.
Stir fan base on — If the stir fan output is enabled above, specify its operating mode: select “ Tem p” if it operates within a certain temperature range or select “MinV” if it only operates in minimum ventilation (refer to section 6.6 for further information on this function).
Use light? — Select “ Yes” to enable the 0-10V light output.
Number of light programs — If the light output is enabled above, select the desired number of light programs (1 to 9 programs).
Use sidewall vent ? — Select “Yes” to enable the sidewall vent output. * This parameter is
accessible if the static pressure sensor is enabled above.
Use tunnel inlet ? — Select “Yes” to use a tunnel inlet.
Number of tunnel inlets — If the tunnel inlet option is enabled above, select the number of tunnel outputs in use (1 or 2 tunnel inlets).
Tunnel inlet mode — Tunnel inlets can either move according to the level of static pressure (S.P.) or according to the room temperature. Select the desired operating mode. * This
parameter is accessible if at least 1 tunnel inlet is enabled above.
Vent inlet mode — The position of vent in­lets can either be defined according to the static pressure level or in timer mode as a function of temperature. Select “S .P.” if they are regulated by the static pressure level or “T°” if their opening is based on temperature variations.
Vent inlet SP adjustment ? — The controller can automatically adjust the static pressure set points as a function of inside or outside temperature. Select “Insi de T°” to define a second group of static pressure set point (this group starts being used when the room temperature reaches a certain point); select “Oustide T°” to define different pressure set points for winter and summer or select “No” to disable these functions. *This parameter
is accessible if the Vent Inlet Mode is set to “S.P.” above.
Use attic vent? — Select “Ye s” to enable the attic vent output.
Use attic T° sensor? — Select “Ye s” if a temperature sensor is present in the attic. * This parameter is accessible if the attic vent is
enabled above.
Use attic min vent. compens? — In order to extract air from the attic, the controller can increase the operating time of the fans, in minimum ventilation, when temperature is suitable in the attic. Select “Ye s” to enable this compensation function (refer to section
6.5 for further information on this function). * This parameter is accessible if the attic sensor is
enabled above. It is also common to all programs of the controller.
Vents pre-opening mode — The pre-opening delay is used to pre-open the vents (sidewall & attic vents) before activating the fans at the startup of each minimum ventilation cycle. The controller can use a steady pre-opening delay or can set this delay automatically. Se­lect “Au to” to use an automatic pre-opening delay or select “Ma n .” to set the delay your­self. * This parameter is accessible if the attic vent
or sidewall vent is enabled above.
Use Night Set Point? — Select “Ye s” to use a different target temperature at night; select “N o” to disable this function.
Use min. vent. night on time ? — The con­troller can use different minimum ventilation timer at night. Select “Ye s” to use particular night settings.
Day starts at — Set the time at which the day timer starts being used in minimum ventila­tion. * This parameter is accessible if the “Night
min. vent. on time” option is enabled above.
12
PRO-VISION rev.07
PRO-VISION
Night starts at — Set the time at which the night timer starts being used in minimum ventilation. * This parameter is accessible if the
“Night min. vent. on time” option is enabled above.
Monitor breaker temperature ? — Select “Yes” if a temperature sensors is used to monitor the temperature of the main breaker. The controller will set off an alarm if the reading of this input gets higher than acceptable temperature limit. * This parameter is common
to all programs of the controller.
Breaker sensor — If the breaker monitoring function is enabled above, specify which of the temperature sensors is used for this pur­pose (sensor 1-8). * This parameter is common
to all programs of the controller.
Use password? — Select “Yes” to enable the password protection or “N o” to disable it. * This parameter is common to all programs of
the controller.
Number of relays — Select the proper relay panel or combination of relay panels in use:
1 RP-32 / 1 RP-40 / 1 RP-40 & RP-16 2 RP-32 / 1 RP-32 & RP-40 2 RP-40 / 3 RP-32 / 3 RP-40 / 4 RP-32
* This parameter is common to all programs of the controller.
your application only uses relay panels with the “CS” technology or select “Low” if your application contains 1 or more relay panels that do not use this technology. *Refer to
chapter 16 to see the communication rate currently being used by your controller.
Current condition display — Select what information needs to be displayed on current condition menu: select “Al l” for the controller to display all possible pieces of information or select “W/O heat” or “W/O Prb,Heat” to re­move the heater run time and/or the reading of individual temperature sensors from the current condition display. * This parameter is
common to all programs of the controller.
Use current sensors ? —Select “Yes” if at least 1 output uses a current sensor.
Approximative operation cost — The control­ler can calculate the approximate operating cost of the outputs that are using a current sensor. Select the going rate per kilowatt­hour.* This parameter is accessible the current
sensor is enabled above. It is also common to all programs of the controller.
Output voltage — Specify what voltage each output uses: 120, 208 or 240 Volts.
Communication speed — The communication speed provided by the controller depends on the type of relay panels you are using. Using the high-speed communication mode allows connecting more relay panels and current sensors without lowering the communica­tion speed of the controller. Note that the high-speed mode can only be used if your application exclusively contains relay panels with the “CS” technology (the letters “CS” are written on the faceplate of a relay panel that uses this technology). Select “High” if
PRO-VISION rev.07
13
PRO-VISION

4.5. Sensor Assignment

The selection of sensors must be made separately for each controller program in use.
4.5.1. Assigning the Sensors
The controller outputs either run according to the average reading of their own selection of sensors or according to a pre-defined group of sensors (such as the average temperature). The table below gives a list of all outputs and tells according to which selection of sensors each one of them operates.
Outputs Selection of sensors
Heater 1-32
Heat 1-16 Hi Fire
Cooling 1-6
Fogger Zones 1-6
Natural curtains 1-2
Egg room heater
Egg room cooling
Fans 1-5
Stir Fan
Tunnel Fans 1-20
Non-brood zones: A non-brood zone is an unused part of the house. This type of zone is automatically created when a heater is only being controlled by a selection of sensors that are not used to measure the average room temperature. Refer to section 4.8 for further information about non-brood zones.
The selection of sensors must be made separately for each of these output.
In lateral ventilation, these outputs operate
according to the “Aver- age T°” sensor group. In
tunnel ventilation, they operate according to the sensors that are associ­ated with the tunnel fan output in use.
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
2. A table showing all outputs in use is dis­played. Select the desired output with the arrow keys.
On/Off Settings
Ite ms
Tun 1 Tun 2 Tun 3 Tun 4 Tun 5 Cool 1 Fan 1 Fan 2 Fan 3 Fan 4 Heat 1 Heat 2 Heat 3
Set Point : 75.0
On Off Mode
60.0 63.5 Non brood
60.0 63.5
60.0 63.5
60.0 63.5
60.0 63.5 Ti me r
60.0 63.5 Sta rt si dew all 6 0.0 63. 5 Close attic
60.0 63.5 Start tunnel 6 0.0 63. 5 Close sidewall
60.0 63.5
60.0 63.5
60.0 63.5
60.0 63.5
To modify use
-
Htr /fan shut
Time
clock
Water
flush
Average
Sensor
When an output is selected, the controller displays a sensor assignment tab at the right hand side of the screen (the tab is associ­ated with the chosen output). If the output operates according to a group of sensors, the tab leads to the sensor assignment menu of the group; if it operates according to its own selection of sensors, the tab leads to the sen­sor assignment menu of the chosen output.
3. Select the sensor assignment tab with the menu selectors.
Average Sensor
1 2 3 4 5 6 7 8
--- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
--- --- --- --- --- --- --- ---
25 26 27 28 29 30 31 32
--- --- --- --- --- --- --- ---
To modify use
4. Use the +/- buttons to put a check mark in the box of the temperature sensors that are used to control the selected output (or that forms the selected group of sensor).
4.5.2. Assigning the Digital Inputs
The controller has 6 digital inputs that can be used to monitor a water meter or the run time of a feeder. Enable these inputs in the Set-up menu (section 4.4) and assign them to digital inputs #1-6 of the controller.
1. Select:
Main menu
* Set-up
* * Digital Inputs
* A password may be required to access this menu (see sec. 4.2.1).
* * This tab is accessible if at least 1 water meter or feeder-monitoring input is enabled in the Set-up menu (see sec. 4.4).
Digital Input Assig nment
1 2 3 4 5 6
Wtr1 Wtr2 Feed1 Feed2 Feed3 -
To modify use
2. Select the desired digital input and press Enter to assign a function to this input.
14
PRO-VISION rev.07
PRO-VISION
4.5.3. Selecting the Attic Sensor
If a temperature sensor is present in the attic, please select which input number the attic sensor uses.
1. Select:
Main menu
* Inlets / Vents
* * Attic Sensors
* This menu is accessible if at least 1 inlet is enabled in the Set- up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
* * This tab is accessible if the attic sensor input is enabled in the Set-up menu (see section 4.4).
Attic Sensor
1 2 3 4 5 6 7 8
--- --- --- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
--- --- --- --- --- --- --- ---
25 26 27 28 29 30 31 32
--- --- --- --- --- --- --- ---
To modify use
---
2. Use the +/- buttons to put a check mark
in the box of the temperature sensor located in the attic.
4.5.4. Egg Room Sensors

4.6. Calibrating the Inputs

This section shows how to calibrate the reading of the sensor inputs in order to obtain accurate and uniform readings from all sensors. It also shows how to calibrate the flow rate of the water meters.
1. Select:
Main menu
* Set-up
Sensor Calib.
* A complete-access password may be required to access this menu (see sec. 4.2.1).
A table showing the calibration values of each sensor input is displayed:
Sensor calibration
Temperatur e sensor 1 Temperatur e sensor 2 Temperatur e sensor 3 Outside tempe rature sensor Static pressure sensor Relative humidity sensor Water meter 1 Water meter 2 Min am monia value Max am monia value
To modify use
-
0.00
1.0g al /p
1.0g al /p 0 ppm
1000 ppm
0.0
0.0
0.0
0.0
0.0
2. If required, calibrate the reading of the sensors. Note that the calibration settings are common to all programs of the controller.
Use the +/- key to enter a negative offset.
Temperature (indoor & outdoor) — The reading of the inside and outside temperature sensors can be adjusted of ±10 °F (±5.6 °C).
Static pressure sensor — The reading of the static pressure sensor can be adjusted of ±0.10 ” WC (±25 Pa). *This parameter is acces-
sible if the static pressure sensor is enabled in the Set-up menu (see section 4.4).
Relative humidity sensor — The reading of humidity sensor can be adjusted of ±10%. *This parameter is accessible if the RH sensor is
enabled in the Set-up menu (see section 4.4).
Water meter calibration — Specify the flow rate of each water meter. It ranges from 0.1 to 100.0 gallons (or liters) per pulse. *This
parameter is accessible if a water meter is enabled in the Set-up menu (see section 4.4).
Min/max ammonia values— In order to use the ammonia sensor, you must specify the minimum and maximum ammonia levels that can be detected by the sensor (in ppm). *This
parameter is accessible if the ammonia sensor is enabled in the Set-up menu (see section 4.4).
If it is used in a breeder facility, the control­ler automatically enables an egg room and controls up to 3 outputs in this room (heater, cooling & humidity outputs). Each of these outputs operates according to a specific tem­perature sensor. Please refer to chapter 11 of this manual to specify which sensor is used in the egg room.
4.5.5. Main Breaker Sensor
A temperature sensor can be used to moni­tor the temperature of the main breaker. The controller will set off an alarm whenever the reading of this temperature input gets too high. Refer to the Set-up menu in section
4.4 to select the temperature sensors used for this purpose (if applicable).
PRO-VISION rev.07
15
PRO-VISION

4.7. Relays

4.7.1. Relay Assignment
The controller activates the loads by means of external relay panels. In all, it can control up to 128 relays. This section shows how to specify the function of each relay. Please refer to the wiring diagram enclosed with your relay panel to connect the loads and to assign the ID numbers of the panels.
A worksheet is available at the end of this manual to write down the function of each relay.
Relay Functions
Display Meaning
Htr Heater
Hi
#x; #xx Hi Fire heater #x or Heater #x
Fan Fan
Tun Tunnel fan
Feed Feeder
Cool Cooling output
Clk Time clock
Flu Water flush output
Stir Stir fan
Light On/Off light output
Bckup Backup device
2
SW-O
/SW-C2Sidewall vent open/close relay
2
AV-O
/ AV-C2Attic vent open/close relay
2
TN-O
/ TN-C2Tunnel inlet open/close relay
Eg.Htr Egg room heater
Eg.Cool Egg room cooling output
Eg.RH Egg room humidity output
Fogg Fogger zone
(depending if your controller uses the
hi-re option or if it uses 32 relays).
1
1. Select:
Main menu
* Set-up
Relay Assign
* A complete-access password may be required to access this menu (see sec. 4.2.1).
The function of each relay is displayed.
Relay Assignm ent
1 2 3 4 5 6 7 8
Fan 1 Fan 2 Fan 2 Fan 3 Fan 4 Tun 1 Tun 2 T un 3
9 10 11 12 13 14 15 16
Heat HiFi1 Heat2 HiFi2 Heat3 HiFi3 Cool 1 Cool 2
17 18 19 20 21 22 23 24
Cool 3 Cool 4 Stir S V-O SV-C AV-O AV-C TN-O
25 26 27 28 29 30 31 32
TN-C Clk 1 Clk 2 Clk 3 - - - -
Select an item and press
2. Use the arrow keys to select the desired relay number and then press “Enter” to change its function. A table showing all possible functions prompts on screen.
Relay 1 Assignm ent
Htr HiFi Fan Tun Fee d Cool Clk Flu Stir Light Bcku p SW-O SW-C TN-O TN-C AV-O AV-C Eg.Cool Eg.Htr Eg.RH Fogg Off
Use the arrow keys to select the type of output being controlled by the relay and then press “Ent er”.
4.7.2. Relays with Current Sensors
The controller can monitor the current flow on each of its outputs. The following procedure shows how to identify the outputs that are using a current sensor.
1. Select:
Main menu
* Set-up
* *Current sensors
* A complete-access password may be required to access this menu (see sec. 4.2.1).
** This menu is accessible if a current sensor is enabled in the Set-up menu (see section 4.4).
Relay current se nsor assignment
1 2 3 4 5 6 7 8
--- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
--- --- --- --- --- --- --- ---
25 26 27 28 29 30 31 32
--- --- --- --- --- --- --- ---
To modify use
2. Use the +/- buttons to put a check mark in the box of the relays that are using a cur­rent sensor.
3. If the controller uses many outputs of the same type, choose the output number from the drop-down menu.
4. Proceed the same way to assign a relay to each output in use.
Htr
Htr 2
Htr 3
Htr 4
1. Feeder relays are used to stop the feeders when a feeder run time alarm occurs. These relays are normally closed (NC) relays which open when their
respective feeder exceeds a user-dened run time.
2. Some relays on the relay panels have specially been designed to connect actuators (an actuator relay has an “Open/Off/Close” marking instead of an “On/Off” marking on the faceplate of the panel). When actuators are connected to these relays, their open and close relays can never be activated at the same time.
16
PRO-VISION rev.07
PRO-VISION

4.8. Non-Brood Zones & Clean Mode

Definition of a Non-Brood Zone: A non-brood
zone is an unused part of the house. This type of zone is automatically created when a heater exclusively uses temperature sen­sors that are not used to measure the aver­age room temperature. Non-brood zones are generally not ventilated and only have some heaters to ensure minimum heat.
Heaters in Non- Brood Zones: The operating temperatures of the heaters in non-brood zones are related to the “Non-Brood temperature set point” rather than on the regular temperature set point. This means that if the non-brood temperature set point changes, the operating temperatures of non-brood heaters will be ad­justed consequently. Refer to section 5.1 to set the “Non-Brood temperature set point”.
Definition of the Clean Mode: The clean mode is used to interrupt regular operations of the controller when the whole house is empty. When this mode is enabled, the controller provides a minimum level of heat and venti­lation (optional). In clean mode, the heaters operate according to their non-brood settings.
Low Temperature Alarms in Clean Mode: The controller can sound an alarm if the temperature gets too low while it operates in clean mode (or when the temperature gets too low in an empty zone). Once it is enabled, refer to section 13. 2 to adjust the low temperature limit.
Figure: Heaters in Non-Brood Zones
Fans
Heaters
Temp.
Sensors
Heaters
Figure: Heaters in Clean Mode
Heaters
Temp.
Sensors
Heaters
Clean Mode
Unused Fans
Heater
Temp.
Sensors
Temp.
Heater
Temp.
Sensor
Sensor
Heater
Non-Brood ZoneBrood Zone
Unused Fans
Unused FansUnused Fans
Temp.
Sensors
Heater
Unused Fans
Unused Fans
1. Select:
Main menu
* Start Flock
* A password may be required to access this menu (see section 4.2.1).
2. Set the following parameters:
Clean Mode — Select “On” to enable the clean mode or select “Of f” to disable it.
Alarm low T° — Select “Yes” for the con­troller to set off an alarm when the average temperature gets lower than the Non Brood Set Point while the controller is in clean mode. *This parameter is accessible if the clean mode is
enabled above or if an empty zone is used.
Use minimum ventilation? — Select “Yes” to activate minimum ventilation cycles while the clean mode is on.
Unused Fans
Mortality
Loss (%)
Stat Flo ck
Age
Clean M ode
Use min.vent?
To modify use -
PRO-VISION rev.07
Start flock
Remaining
0
Program
0.00
Age
Nb Birds
No
New Mortality
1
Alarm low T°?
Yes
Yes
10000
Progra m 1
10000
0
No
17
PRO-VISION

4.9. Test Mode

The test mode is used to simulate changes in the ambient temperature and relative humid­ity and verify the controller’s performance. When the test is enabled, all outputs of the controller operate according to the simulated temperature. The test automatically ends after 15 minutes of inactivity or if the user deacti­vates it manually.
1. Select:
Main menu
* Set-up
Test Mode
* A complete-access password may be required to access this menu (see sec. 4.2.1).
Test Mo de
Program
Progra m 1
Status
Hu mid ity
2. Set the following parameters:
Program # — This is the program that is cur­rently used by the controller. It is displayed for information only. *Refer to section 4.3 to change
the program in use.
S. P.
Tem peratur e
On
0
---
77. 8

4.10. Version

The version menu gives the version number of the program used by the controller. This piece of information is useful to get techni­cal support.
1. Select:
Main menu
* Set-up
Version
* A complete-access password may be required to access this menu (see sec. 4.2.1).
Pro -visio n
V X.X
Build no. XXXX
Released: Jan 1 200X
Stat. Pressure — This is the current level of static pressure. It is displayed for information only and cannot be modified manually. * This
parameter is accessible if the test mode is enabled above and if a static pressure sensor is enabled in the Set-up menu (see section 4.4).
Status — Select “On” to enable the test mode or select “Off ” to disable it.
Temperature — Set the simulated room tem­perature to the desired value. * This parameter
is accessible if the test mode is enabled above.
Humidity — Set the simulated humidity level to the desired value. * This parameter is acces-
sible if the test mode is enabled above and if the RH sensor i s enabled in the Set-up menu (see section 4.4).
18
PRO-VISION rev.07
PRO-VISION

5. SET POINTS

5.1. Temperature & RH Set Points

1. Select:
Main menu
* Set Point
* A password may be required to access this menu (see section 4.2.1).
The current temperature & relative humid­ity (RH) set points are displayed along with a graph of the temperature set point ramp. Refer to section 5.2 for further information about this ramp.
2. Set the following parameters:
Day set point — Set the temperature set point that is used during the day (this set point is used all day long if the night set point is not enabled). The controller can also change the day set point automatically over time by us­ing a curve(see section 5.2). * This parameter
is common to all programs.
Night set point — A different temperature set point can be used at night. The night set point can be used to lower the target room temperature for instance. The night set point is relative to the day set point, which means that it is automatically adjusted when the day set point changes. Set the night set point to the desired value. *Accessible if the night set point
is enabled (see section 4.4).
Non brood — Set the target temperature used in the non-brood zones. *Refer to section 4.8 for
further information about non brood zones.
RH Set Point — The relative humidity (RH) set point is the target level of relative humidity in the room. It is only used if the controller is used in a broiler, layer or turkey facility. If the humidity level in the room gets higher than this set point, the controller can enable differ­ent compensation functions to lower it down (see chapter 12). Set the relative humidity set point to the desired value. * This parameter is
accessible if the controller is used in a broiler, layer or turkey facility and if a RH Compensation func­tion is enabled in the Set-up menu (see section 4.4) .
Set Point
Day
Non brood
Temp erature
90.0
84.4
81.6
78.8
76.0
73.2
70.4
67.6
64.8
62.0
75.0
Night
RH Set Point
35.0
Ram ping
1 5 10 14 19 24 28 33 38 42 47 Age
To modify u se
-
77. 0
65
Ram ping

5.2. Set Point Ramp

The controller can automatically adjust the temperature set point over time with a ramp. The set point ramp is composed of 12 steps and each step associates a temperature set point with an animal age. Once the ramp is enabled, the controller changes the tempera­ture set point every hour in a linear fashion between consecutive steps of the ramp. When it reaches the last step, the controller keeps using the last temperature set point until the end of the flock.
Temperature
Tem peratu re
90.0 8 7.2
84.4
81.6
78.8
76.0
73.2
70.4 6 7.6
64.8
62.0 1 5 10 14 19 24 28 33 38 42 47 Age
Set Point Ramp
1. Select:
Main menu
* Set Point
Ramping
* A password may be required to access this menu (see section 4.2.1).
2. Set the following parameters. * The param­eters below are common to all programs.
Ramping Status — This is the status of the set point ramp. Select “O n” to enable it or select “Off” to disable it.
Age — Set the age at which each step starts. This parameter ranges from -5 to 450 days (negative values are used to prepare the house before letting the animals in).
Temperature — Assign a temperature set point with each step of the ramp. If you don’t need 12 different steps, repeat the last tem­perature for each unnecessary step.
Rampin g Status: OFF
Age Set Point
1 90.0° F 7 85.0° F 10 8 0.0°F 15 78.0°F 21 7 2.0°F 25 70.0°F 28 6 8.0°F 32 6 6.0°F 36 64 .0°F 40 6 2.0°F 46 62 .0°F 47 62.0 °F
To modify u se
-
PRO-VISION rev.07
19
PRO-VISION

6. VENTILATION & COOLING

6.1. Overview of the Ventilation Concepts

Ventilation Concept in a Broiler or Layer Facility Ventilation Concept in a Turkey or Breeder Facility
In tunnel mode, ventilation is provided by chosen tunnel fans and the air intake is exclusively provided by the tunnel inlet (the sidewall vents are closed). The controller starts measuring the average temperature according to the tunnel sensors and starts using the tunnel inlet static pressure limits and alarm limits.
In tunnel mode, ventilation is provided by chosen tunnel fans and the air intake is exclusively provided by the tunnel inlet (the sidewall vents & natural curtains are closed). The controller starts measuring the average temperature according to the tunnel sensors and starts using the tunnel inlet static pres-
sure limits and alarm limits. This ventilation
mode is optional in a turkey facility.
Startup of the
tunnel fan labeled
“Close sidewall”
(see sec. 6.5.3).
Startup of the
tunnel fan labeled
“S tar t Tunne l”
(see sec. 6.5.3).
“ON T°”
of the first
lateral fan
As the room temperature rises, the control­ler can start opening the tunnel inlet before closing the sidewall vents in order to create a smooth transition between lateral & tunnel ventilation. This transition is optional.
In lateral mode, ventilation is provided by chosen sidewall fans and the air intake is provided by the sidewall and/or attic vents.
In minimum ventilation, the fans that are used to ensure a minimum ventilation run in timer mode and the vents (sidewall and/or attic) slightly open prior to each activation of the fans.
Minimum Vent. Lateral Mode Tunnel ModeTransition (opt.)
Startup of the
tunnel fan labeled
“S tar t Tunne l” (see
sec. 6.5.3).
Startup of the first
natural ventilation
curtain (see sec.
6.5.3).
“ON T°”
of the first
lateral fan
In natural ventilation, no fan is running and the air intake is provided by the natural ven­tilation curtain and by the tunnel inlet (if a tunnel inlet is used).
In lateral mode, ventilation is provided by chosen sidewall fans and the air intake is pro-
vided by the sidewall and/or attic vents. This
ventilation mode is optional in a turkey facility.
In minimum ventilation, the fans that are used to ensure a minimum ventilation run in timer mode and the vents (sidewall and/or attic) slightly open prior to each activation
of the fans. This ventilation mode is optional
in a turkey facility.
Minimum Vent. (opt.) Lateral Mode (opt.) Tunnel Mode (opt.)Natural Mode
20
PRO-VISION rev.07
PRO-VISION

6.2. Minimum Ventilation

Minimum ventilation cycles are activated when the room temperature is lower than the start temperature of the first fan stage. Run­ning the fans even though ventilation is not required for reducing the room temperature is useful to reduce humidity levels and supply oxygen to the room. It also prevents the fans from freezing in winter.
Minimum ventilation can only be used
if at least 1 fan output is enabled in
the Set-up menu (see section 4.4).
6.2.1. Minimum Ventilation Timer
The minimum ventilation timer is composed of an “O n Ti me” and of a “C ycle Time” . The fans run during the “On T ime” and then stop until the end of the “C yc le T ime”. This timer is common to all programs of the controller.
Min.Vent
Fan Status
ON
OFF
Minimum
Ventilation Timer
ON Time
Cycle Time
Time
Automatic adjustment of the minimum venti­lation timer as a function of relative humidity: The controller can automatically increase the “On Time” portion of the minimum ventilation timer as the humidity level increases. Refer to section 12.1 for further information about this RH compensation function.
The controller can automatically extend the cycle time in order to pre-open the vents.
Settings
1. Select:
Main menu
* Minimum Ventilation
** Day Settings or Night Settings
* A password may be required to access this menu (see section 4.2.1).
**If different minimum ventilation settings are used at night, select the parame ters you want to adjust (day or night settings). These tabs are accessible if the “Use min. vent. night on time” parameter is enabled in the Set-up menu (see section 4.4).
2. Set the following parameters:
Mini mum ve ntilation
On Time(or) Night On
Cycle
ON TIME
3:05
2:48
2:31
2:14
1:57
1:40
1:23
1:06
0:49
0:32
0:15
1 2 3 4 5 6 7 8 9 10 11 12 AGE
0:1 5 M:S
5:0 0 M:S
Cor rect.
Enhanced
Ram ping
0sec
No
Graph is accessible if the minimum ventilation ramping is enabled in Set-up menu.
On Time — Set the “O n Ti me” of the minimum ventilation timer. If the minimum ventilation ramping is enabled, the controller automati­cally defines this value as a function of the animal age (see section 6.2.2). *If different day/
night minimum ventilation timers are used, press the “Day Settings” tab to access this parameter.
Night On — Set the “On Time” of the mini- mum ventilation night timer. If the minimum ventilation ramping is enabled, the controller automatically defines this value as a func­tion of the animal age (see section 6.2.2).*If
different day/night minimum ventilation timers are used, select the “Night Settings” tab to access this parameter.
Correct. — Select the correction that needs to be applied to all steps of the minimum ventilation ramp. The correction value is expressed in seconds and can either be a positive or negative value. *This parameter is
accessible if the minimum ventilation ramping curve is currently running.
Cycle — Set the cycle time of the minimum ventilation timer. Note that the cycle time must be longer than the “On Time”.
Enhanced — Select “Ye s” if you want the On Time portion of the minimum ventilation timer to increase as the room temperature gets closer to stage 1 start temperature or select “N o” to disable this function. With this function, the On Time reaches the Cycle Time (fans are fully on) at the beginning of the highest minimum ventilation timer fan.
PRO-VISION rev.07
21
Loading...
+ 46 hidden pages