Integra PRO-VISION User Manual

O
X
TION IS POWER
PRO-VISION
Temperature controller
User’s Manual
Current conditions
Set Point
Minim um ventilation
On/Off Settings
Inlets/Vents
Main Menu
Start flock / Egg
Light Programs
Alarms
History
Set-u p
M 890-00515 rev.07
MAIN MENU
BACK
B
BOX
INFORMATION IS POWER
1
2
3
4
5
6
ENTER
360
DEL
7
8
9
+/-
0
AM/PM
REV.09
PRO-VISION
WARNINGS
The warranty can be void if this product is used in a manner not specified by the manufacturer.
Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information con­tained in it is however subject to change without notice due to further developments.
2
PRO-VISION rev.07
PRO-VISION

TABLE OF CONTENTS

1. INTRODUCTION .................................................................................. 6
1.1. Precautions ................................................................................................. 6
1.2. Symbols of the Manual ................................................................................. 6
1.3. Controller’s Overview ................................................................................... 6
1.4. Main Features .............................................................................................. 7
2. MOUNTING INSTRUCTIONS ................................................................. 7
2.1. Installing the Controller on the Wall ................................................................ 7
2.2. Connections ................................................................................................ 7
2.2.1. Main Wiring ...........................................................................................7
2.2.2. Alarm Connection ...................................................................................8
2.2.3. Sensor Inputs .........................................................................................8
2.2.4. 0-10V Output Connection ........................................................................8
3. USER INTERFACE ................................................................................ 8
3.1. Location of the Controls ................................................................................ 8
3.2. Adjusting a Parameter ................................................................................... 8
4. INSTALLATION SETUP ......................................................................... 9
4.1. Setting the Time & Date ................................................................................ 9
4.2. Password ................................................................................................... 9
4.2.1. Entering a Password ...............................................................................9
4.2.2. Changing / Retrieving a Password .............................................................9
4.3. Controller Programs ................................................................................... 10
4.4. Set-up Menu .............................................................................................. 10
4.5. Sensor Assignment ..................................................................................... 14
4.5.1. Assigning the Sensors ...........................................................................14
4.5.2. Assigning the Digital Inputs ...................................................................14
4.5.3. Selecting the Attic Sensor .....................................................................15
4.5.4. Egg Room Sensors ................................................................................15
4.5.5. Main Breaker Sensor .............................................................................15
4.6. Calibrating the Inputs .................................................................................. 15
4.7. Relays ....................................................................................................... 16
4.7.1. Relay Assignment .................................................................................16
4.7.2. Relays with Current Sensors ..................................................................16
4.8. Non-Brood Zones & Clean Mode ................................................................... 17
4.9. Test Mode ................................................................................................. 18
4.10. Version ..................................................................................................... 18
5. SET POINTS .......................................................................................19
5.1. Temperature & RH Set Points ...................................................................... 19
5.2. Set Point Ramp .......................................................................................... 19
6. VENTILATION & COOLING ..................................................................20
6.1. Overview of the Ventilation Concepts ........................................................... 20
6.2. Minimum Ventilation .................................................................................. 21
6.2.1. Minimum Ventilation Timer ....................................................................21
6.2.2. Min Ventilation Timer Ramp ...................................................................22
PRO-VISION rev.07
3
PRO-VISION
6.2.3. Minimum Ventilation Fans ......................................................................22
6.2.3.1. Fan Selection ...............................................................................22
6.2.3.2. Stir Fans in Minimum Ventilation .....................................................22
6.2.3.3. Fan Cycling ..................................................................................23
6.2.4. Air Intake in Min Ventilation ...................................................................23
6.3. Lateral Ventilation ...................................................................................... 25
6.3.1. Lateral Ventilation Fans ........................................................................25
6.3.2. Attic & Sidewall Vents based on Temperature ..........................................26
6.3.3. Attic & Sidewall Vents based on Static Pressure ......................................27
6.3.3.1. Compensation on Pressure Set Points ..............................................27
6.3.3.2. Settings .......................................................................................28
6.4. Natural Ventilation ...................................................................................... 29
6.5. Tunnel Ventilation ...................................................................................... 30
6.5.1. Principle of Operation ............................................................................30
6.5.2. Tunnel Ventilation in Standby .................................................................30
6.5.3. Tunnel Fans .........................................................................................31
6.5.4. Tunnel Inlets ........................................................................................32
6.5.4.1. Temperature-based Tunnel Inlet .....................................................32
6.5.4.2. Pressure-based Tunnel Inlets .........................................................33
6.6. Stir Fans ................................................................................................... 34
6.7. Cooling Output .......................................................................................... 35
6.8. Fogger Output ........................................................................................... 36
7. HEATING ...........................................................................................37
8. LIGHTS .............................................................................................38
8.1. Principle of Operation .................................................................................. 38
8.2. Settings .................................................................................................... 39
8.2.1. Light Program Settings ..........................................................................39
8.2.2. Light Peak Settings ...............................................................................39
9. TIME CLOCKS ..................................................................................40
9.1. Regular Time Clocks ................................................................................... 40
9.2. Time Clocks in a Breeder Facility .................................................................. 41
10. WATER LINE FLUSH ...........................................................................42
11. EGG ROOM OUTPUTS ........................................................................43
12. RELATIVE HUMIDITY (RH) COMPENSATION ..........................................44
12.1. High RH Comp.on the Min Vent. Timer ......................................................... 44
12.2. High RH Comp. with Heaters in Min Vent. ..................................................... 44
12.3. RH Comp. with Cooling & Foggers ............................................................... 45
4
PRO-VISION rev.07
PRO-VISION
13. ALARMS ...........................................................................................46
13.1. Alarm Log ................................................................................................. 46
13.2. Temperature Alarms ................................................................................... 46
13.2.1. High/Low Temperature Alarms ...............................................................46
13.2.2. Temperature Alarms in Clean Mode ........................................................46
13.2.3. Outdoor Temperature Compensation .......................................................47
13.2.4. Temperature Alarm Settings ...................................................................47
13.2.5. Critical Temperature Ramp .....................................................................48
13.2.6. Static Pressure Alarms ..........................................................................48
13.2.7. Water Spill Alarms ................................................................................49
13.2.8. Feeder Alarms ......................................................................................49
13.2.9. Amperage Draw Alarms .......................................................................50
14. MONITORING FUNCTIONS ..................................................................51
14.1. Current Conditions ..................................................................................... 51
14.1.1. Current Condition Screen Saver ..............................................................51
14.1.2. Current Input/Output Status ...................................................................51
14.2. History Menus ........................................................................................... 52
14.3. Animal Age & Count ................................................................................... 52
14.4. Egg Count ................................................................................................. 53
14.5. Operation Costs & Current Consumption ....................................................... 53
15. UPDATE & BACKUP ............................................................................53
16. DIAGNOSTIC .....................................................................................54
17. TECHNICAL SPECIFICATIONS ..............................................................55
18. INDEX ...............................................................................................56
PRO-VISION rev.07
5
PRO-VISION

1. INTRODUCTION

1.1. Precautions

WARNING: Read and save these in­structions!
Safety may be jeopardized if the equipment is used in a manner not specified by the manu­facturer. Carefully read and keep the following instructions for future reference.
We strongly recommend installing supplemen­tary natural ventilation as well as a backup thermostat on at least one cooling stage.
Although fuses at the input and outputs of the controller protect its circuits in case of an overload or over-voltage, we recommend installing an additional protection device on the controller’s supply circuit.
The room temperature where the controller is located must always remain between 32°F and 104°F (0°C to 40°C). Indoor use only!
To avoid exposing the controller to harmful gases or excessive humidity, it is preferable to install it in a corridor.
If the equipment is used in a manner not specified by the manufacturer, the protec­tion provided by the equipment may be impaired.

1.2. Symbols of the Manual

Warning. Read the following text carefully; it contains important information which, if ignored, may cause the controller to operate improperly.
High Voltage. Hazard of electrical shock. Read the message and follow the instructions carefully.
Pay attention. The following text contains very useful information.
Press on the proper menu selector.
Press the “Main Menu” push-button.
Both direct and alternating current (AC/DC).
Direct current (DC).
Alternating current (AC).
Earth Ground Terminal Primarily used for functional earth terminals which are generally asso­ciated with test and measurement circuits. These terminals are not for safety earthing purposes but provide an earth reference point.

1.3. Controller’s Overview

The PRO-VISION is an electronic device used for environmental control in livestock build­ings. It combines sidewall, natural and tunnel ventilation into one powerful system.
OUTPUTS — The PRO-VISION can control up to 128 relays located in external relay panels. These relays can be used to control the following outputs:
32 heaters; 16 hi-fire heaters; 5 lateral fans; 20 tunnel fans; 1 stir fan; 6 cooling outputs; 6 foggers 2 tunnel inlets; 8 natural ventilation curtains; 1 sidewall vent; 1 attic vent; 12 time clocks; 2 light outputs (0-10V); 8 water line flushing outputs; 1 egg room heater; 1 egg room cooling output; 1 egg room humidity output; 1 alarm output; 1 backup relay; 4 feeder cut-off relays.
Do not spray water on the controller! In order to clean the control, wipe it with a damp cloth.
Before servicing or cleaning unit, switch power off at service panel and lock the switch disconnecting means to prevent power from being switched accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
6
PRO-VISION rev.07
For Customer Use: Enter below the serial number located on the side of the alarm system and keep this information for future reference.
Model: PRO-VISION
Serial number:
Date installed:
BUILT-IN INPUTS:
32 inside temperature sensors (8 basic
temperature inputs & up to 24 additional
inputs with the expansion cards); 1 outside temperature sensor; 1 relative humidity sensor; 1 static pressure sensor; 1 NH3 sensor; 1 wind speed sensor; 6 digital inputs (water meters and/or feeder
monitoring inputs).
Refer to the end of this manual to con­nect the sensors and loads.
PRO-VISION

1.4. Main Features

Easy-to-Use Controller — With its conve-
nient menu selectors and its large graphic LCD screen, the PRO-VISION is certainly the most easy-to-use temperature controller on the market.
10 Controller Programs — The controller al­lows using 10 different programs to control the room temperature. It is thus possible to activate a specific program that uses par­ticular temperature settings according to the animal age for instance.
32 Indoor Temperature Sensors — Up to 32 temperature sensors can be connected to the controller to obtain an accurate read­ing of the average room temperature and a faster reaction time. The controller comes with 8 basic temperature inputs and 24 ad­ditional inputs can be added with the optional extension cards.
Minimum Ventilation Cycle — When ven­tilation is not required to reduce the room temperature, fan outputs can run either con­tinuously or intermittently to reduce humidity levels and supply oxygen to the room.
Recuperation of the Warm Attic Air — In order to make energy savings, the controller can extract the warm air from the attic and send it back into the room.
Natural Ventilation — This is a ventilation mode that uses existing air currents and natural convection to move and distribute air through the building.
Humidity Control — The control offers many ways to compensate for high or low humid­ity levels.
Control of the Air Inlet Movement — The movement of the air inlets (sidewall vents or tunnel inlets) can be coordinated with the operation of the fans or according to the pressure level. This allows the inlets to be adjusted correctly, without the influence of uncontrollable factors such as wind or air from adjoining rooms.
Egg Room — In addition to controlling the ambient temperature in the house, the PRO­VISION can control the temperature and humidity conditions in an egg room. It can also keeps a tally of the number of eggs produced each day.
Operation Cost Monitoring — The control­ler can monitor the amperage draw of the outputs and give you daily reports of the operation costs.
History Menus — The history menus allow monitoring the sensor readings and verify the run time of some outputs. Below is a list of all available histories menus:
Static pressure sensor ...............400 days
Heater run time ..........................400 days
Feeder run time .......................... 400 days
Water consumption .....................400 days
Mortality ................................... 400 days
Alarm Management — The controller provides alarms for high-low temperatures, defective sensors and other system failures. It keeps in memory the 75 latest alarm conditions.
Password Protection — Different passwords levels can be enabled to restrict access to some menus of the controller.
Backup Battery — A backup battery allows the unit to keep time in case of a power failure.
USB Connector — Controller backups and updates can be made easily with a standard USB memory card.
Overload and Over-voltage Protection — Re­settable fuses are provided at low-voltage inputs of the controller to protect its circuitry in the case of an overload or over-voltage.
Computer Control — The controller can be connected to a computer, thus making it possible to centralize the management of information and diversify control strategies.
Tunnel Ventilation — When the room tem­perature rises, tunnel ventilation reduces the actual temperature perceived by the animals.
2. MOUNTING INSTRUC­TIONS
2.1. Installing the Controller
on the Wall
Fasten the two metal brackets on the mount­ing holes located behind the controller using four screws. Then, mount the enclosure on the wall using four other screws. Leave a clearance of at least 16” to the left of the enclosure to allow the cover to be removed for maintenance.
Minimum and maximum sensor readings:
Ambient temperature ................400 days
Inside temperature sensors ............7 days
Outside temperature sensor .......400 days
Relative humidity sensor ...........400 days
Test Mode — A test mode allows simulat­ing temperature changes and verifying the controller‘s performances.

2.2. Connections

2.2.1. Main Wiring
Refer to the wiring diagram enclosed with this user’s manual to connect the controller. Drill holes at the bottom of the enclosure to pass the wires and install watertight connectors to prevent water from entering in the enclosure. Do not make any holes at the side and top of the enclosure.
All wiring must be done by an autho­rized electrician and must comply with applicable codes, laws and regulations. Make sure power is off before doing any wiring to avoid electrical shocks and equipment damage.
PRO-VISION rev.07
7
PRO-VISION
Do not install rigid conduit into electrical knockouts. Only nylon cable glands are permitted for cable or wire fastening.
The controller has no power-on switch. An external switch or circuit breaker shall be included in the building instal­lation to interrupt power to L and N electric power lines. It shall be in close proximity to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.
2.2.2. Alarm Connection
There are two types of alarms on the market. One type activates when current is cut off at its input; the other type of alarm activates when current is supplied at its input. For an alarm of the first type, use the NC terminal as shown on the wiring diagram. For an alarm of the second type, use the NO terminal.

3. USER INTERFACE

3.1. Location of the Controls

Graphic LCD display — The large graphic
LCD screen is used to display the parameters and menus.
Menu selectors — The menu selectors allow selecting a tab on screen.
Home key — This short-cut key provides ac­cess to the main menu.
Back — The “Back” key is used to go back to the previous menu.
Arrow keys — The arrow keys allow select­ing a parameter on screen. The right and left arrow keys can also be used to move through the display by pages (left=page-up, right=page-down).
Enter — The “Enter” key is used to change the value of non-numerical parameters. Pressing this key makes a drop-down choice menu appear.
Adjustment buttons — The adjustment but­tons allow increasing or decreasing the value of a parameter.
2.2.3. Sensor Inputs
Sensors operate at low voltage and are isolated from the supply. Make sure that sensor cables remain isolated from all high voltage sources. In particular, do not route the sensor cables through the same electri­cal knockout as other cables. Do not connect the shield from the sensor cable to a terminal or a ground.
Extending a sensor: Each sensor can be ex­tended up to 500 feet (150 meters).
To extend a sensor: Use a shielded cable of outside diameter between 0.245 and 0.260 in (6.22 and 6.60 mm) (the cable dimensions should not be under 18 AWG) to ensure the cable entry is liquid tight. Do not ground the
shielding.
It is preferable to solder the cable joint to ensure a proper contact between the two cables.
Delete — The delete key allows clearing the last digit that has been posted while editing a
Graphic
LCD
Display
numerical value.
+/- & AM/PM but ton — This push-button allows entering a negative value and allows changing the AM/PM time in­dicator.
Digital keypad — The digital keypad is used to modify the value of numerical parameters.
Alarm Status LED — The alarm LED turns red when an alarm
Menu
Selectors
Home
Key
Back
button
Arrow keys
(Right = Page-Down
Left = Page-Up)
situation is active or turns green when there is no alarm.

3.2. Adjusting a Parameter

When a parameter is selected, the control­ler gives indications about the way it can be modified at the bottom of the screen. A parameter can either be modified with the adjustment buttons, with the digital keypad or by pressing the “Enter” key and then selecting an item from a drop-down menu. Follow the instructions on screen to modify the value of a parameter.
Do not run sensor cables next to other power cables. When crossing over other cables, cross at 90°.
Defective sensors: An alarm is generated when a defective sensor is detected. Defec­tive sensors are identified in the “Alarm” menu. Refer to chapter 13 fo r f ur the r information on the alarms.
2.2.4. 0-10V Output Connection
It is recommended to use a 18 to 22 AWG wire to connect the devices to the 0-10V outputs. This type of output can be used to connect various devices such as lights.
Alarm
AM/PM
Status LED
3
6
9
+/-
+/-
AM/PM Button
Delete
Main Menu
Current conditions
Set Point
Minimu m ventilation
On/Off Settings
Inlets/Vents
MAIN MENU
BACK
ENTER
Start flock / Egg
Light Programs
Alarms
History
Set-up
Adjustment
Buttons
Digital Keypad
1
2
4
5
7
8
DEL
0
8
PRO-VISION rev.07
PRO-VISION

4. INSTALLATION SETUP

4.1. Setting the Time & Date

1. Select:
Main menu
* Set-up
Time & Date
* A complete- access password may be required to access this menu (see sec. 4.2.1).
Time & Date
Tue Jan 1 20XX
11:59:59 am
To modify use
Each of the following parameters must be set in turn.
2. Press “En ter” to start editing the month.
3. Use the navigation buttons to select the current month from the scrolling list.
4. Press “En ter” to continue.
5. The day is now selected. Use the adjust­ment buttons or the numerical keypad to change the current day.
6. Press “En ter” to continue.
7. The year is now selected. Use the +/­push-buttons or the numerical keypad to change the current year.
8. Press “En ter” to continue.
9. The time is now selected. Use the nu­merical keypad to set the time of day and use the AM/PM key to change the time indicator (if required).

4.2. Password

The controller can identify 6 users that are having different privilege levels. Below is a list of possible privileges:
History — This privilege provides access to all read-only menus such as the “Current Condi- tion s”, “A la rm ” & “His tory” menus.
Settings — This privilege provides access to all menus except for the “Se t- up” menu.
All — This password provides complete ac­cess to all menus of the controller.
Using password security is optional. Re­fer to the Set-up menu to enable/disable this protection (see section 4.4).
4.2.1. Entering a Password
If the password protection is used, the control­ler will prompt for a password each time a user that does not have the proper privileges tries ac­cessing a protected menu. Refer to section 4.4 to enable or disable the password protection.
Please enter password
****
1. Type in your 4-digit password.
The message “Wrong Password” is dis­played either if the posted password is incorrect or if the privileges associated with it are not sufficient to access the protected menu.
4.2.2. Changing / Retrieving a Password
A user that has complete access to the con­troller can view and modify the passwords and privileges of all users.
1. Select:
Main menu
* Set-up
* * Password
* A complete-access password may be required to access this menu (see sec. 4.2.1).
* * This menu is accessible if the password protec­tion is enabled in the Set-up menu (see sec. 4.4).
Passwor ds
Sec urity
User 1
User 2
User 3
User 4
User 5
Maste r
To modify use
2. Set the following parameters:
Security — Select the level of privileges that must be selected after 5 minutes of inactivity (history, settings or all).
Cur. user — This is user currently logged in (for information only).
User 1-5 — Set the password of each user.
Choose easy-to-remember passwords and write them down in a safe place!
Master — Set the master password. This user automatically has complete access to all menus of the controller.
Histor y
1111
2222
3333
4444
5555
0610
Cur. user User 1
Level
Level
Level
Level
Level
Settings
Histor y
Histor y
Histor y
All
10. Press “E nte r” to validate the time and date.
Level — Assign the desired level of privileges to each user. *NB. T he Master user automatically
has complete access to all menus.
PRO-VISION rev.07
9
PRO-VISION

4.3. Controller Programs

Program definition: A programs is an assem-
bly of settings (temperature settings, relay assignment, sensor assignment, etc.) that can be enabled at different moment of the breeding process. In all, the controller can use 10 different programs.
Refer to the Set-up menu to enable the de­sired number of programs (section 4.4).
Make sure the right program is selected before adjusting any parameter.
1. Select:
Main menu
* Start Flock
* A password may be required to access this menu (see section 4.2.1).
Start flock
Mortality
Loss (%)
Stat Flo ck
Age
Clean M ode
To modify use
2. Set the following parameters:
Program — Activate the desired controller program. *Only the programs that are enabled in
the Set-up menu can be used (see section. 4.4).
0
0.00
No
10000
On
Remaining
Birds placed
Age
Program
New Mortality
Alarm low T°
-
10000
10000
Progra m 1
0
No

4.4. Set-up Menu

The following section shows how to custom­ize the controller for your particular applica­tion. It shows how to enable and set the inputs & outputs of your controller. Normally, this setup needs to be done only once.
Hint: Use the right and left arrow keys to scroll the display by pages (right = page-down, left = page-up).
1. Select:
Main menu
* Set-up
* A complete-access password may be required to access this menu (see sec. 4.2.1).
2. Set the following parameters:
Contrast — Adjust the contrast of the LCD screen. Default = 50%.
Backlight intensity — Set the intensity of the LCD screen backlight as required. This param­eter ranges from 1 (darker) to 5 (brighter). Default = 3.
Key beeper tone — Adjust the volume of the keypad beeper.
Language — Select the desired language (English or Spanish).
Hint! Press and hold the main menu button for 5 seconds to switch from a language to the other.
Controller used for — The controller can either be used in a breeder, broiler, layer or turkey production facility. The breeder facility gives you access to additional parameters to monitor an egg room; the breeder and turkey options give you access to the natural ventila­tion mode (natural curtain).
Time mode— Select the desired time format (AM/PM or 24 hours).
Pressure unit — Select the desired pressure units (inches of water (“WC) or Pascal (Pa)). * This parameter is accessible if the static pressure
sensor is enabled above.
Use min. vent ramping ? — Select “Yes” to enable the ramping function on the Time ON portion of the minimum ventilation timer. Refer to section 6.2.2 for further information on this feature.
Use relative humidity (RH) sensor ? — Select “Ye s” if a humidity sensor is connected to the controller. Note that if the controller operates in a breeder facility, the RH sensor is used to control the humidity level in the egg room; if the controller is located in a broiler, layer or in a turkey facility, the RH sensor is used to control the humidity level in the house.
Use RH min vent compensation? — Select “Ye s” for the controller to adjust On Time portion of minimum ventilation cycles as a function of the relative humidity level. Re­fer to section 12.1 for further information about this RH compensation method. * This
parameter is accessible if the controller is used in a broiler, layer or turkey facility and if the RH sensor is enabled above.
Use outside T° sensor ? — Select “Yes” if an outside temperature sensor is connected to the controller.
Use critical alarm? — Select “Yes” to enable the critical temperature alarm condition. * This parameter is common to all programs of the
controller.
Number of programs — The controller can use several programs to control the temperature. Enable the desired number of programs (1 to 10 programs) * This parameter is common to all
programs of the controller.
Save current program to — This function allows copying all parameter settings of a program onto another program (it thus avoids repeating the same programming sequence several times). Select the program on which the current program must be pasted. * This
parameter is accessible if more than 1 program is enabled above.
10
PRO-VISION rev.07
Temperature unit — Select the desired tem­perature units (Celsius or Fahrenheit)
Use static pressure sensor ?— Select “Yes” if a static pressure sensor is connected to the controller.
The controller automatically selects the newly pasted program after the saving process.
Confirm — Select “Ye s” to start the copying process. The message “Copy successful” will be displayed after data transfer. *This parameter is
PRO-VISION
accessible if the program selected above is different from the program currently in use.
Number of water meters — Enable the desired number of water meters and then refer to sec­tion 4.5.2 to assign them to the digital inputs of the PRO-VISION. In all, the controller can monitor 6 digital inputs (water meters and feeder-monitoring inputs). *This parameter is
common to all programs of the controller.
Water meter unit — If a water meter is en­abled above, select the desired unit of water volume (gallons or liters). * This parameter is
common to all programs.
Number of temperature sensors — Select the number of inside temperature sensors that are connected to the controller. The control­ler initially comes with 8 temperature inputs and 24 additional inputs can be used with the expansion cards (total of 32 sensors). * This parameter is common to all programs of the
controller.
Use wind speed? — Select “Ye s” if an an­emometer is connected to the controller.
Use ammonia sensor? — Select “Yes” if an am- monia sensor is connected to the controller.
Use water flush? — Select “Ye s” to use the water line flush. Refer to chapter 10 for fur­ther information on this feature.
Number of water lines — Select the number of water line outputs in used (1 to 8 out­puts). Note that up to 2 water lines can be connected to each output. * This parameter is
ac cessible if th e wa te r ush opti on i s enabled a bo ve .
Number of natural curtains — Enable the desired number of natural ventilation curtains (0 to 8 curtains). *This parameter is accessible if
the controller is used in a turkey or breeder facility
Use cur tain inlet? — It is possible to use one natural curtain output in lateral and minimum ventilation. When a curtain is used in one of these ventilation mode, it follows the same movements as the vent inlet. When the con­troller enters in natural ventilation, the curtain output becomes a regular natural curtain again Select the natural curtain output that acts as a curtain inlet in lateral and minimum ventilation or select “Non e” to disable this function *This parameter is accessible if natural
ventilation curtains are enabled above.
Number of heaters — Enable the proper number of heating outputs. If the controller is used in a breeder, broiler or layer production facility, the number of heaters ranges from 1 to 16 and can be doubled with the “Hi Fire” option; if the controller is used in a turkey production facility, the number of heaters ranges from 1 to 32.
Use heater RH compensation ? — Select “Ye s” for the controller to activate the heaters in timer mode when the relative humidity level is too high. Refer to section 12.2 for further information about this RH compensation method. * This parameter is accessible if the con-
troller is used in a broiler, layer or turkey facility and if at least 1 heater and relative humidity sensor are enabled above. It is also common to all programs of the controller.
Use hi fire heaters ? — Select “Ye s” to enable the hi fire option for the heating outputs. This function allows doubling the number of heating stages (refer to chapter 7 for further information on this function). * This parameter
is common to all programs and is only accessible if the controller is used in a breeder, broiler or layer production.
Number of fans — Enable the proper number of lateral fans: up to 5 fans can be used in a breeder, broiler or turkey production and up to 20 fans can be used in a layer production. *If
tunnel fans are used in a layer facility, a maximum of 5 lateral fans can be enabled; if tunnel fans are not used, up to 20 lateral fans can then be enabled.
Number of tunnel fans — Enable the proper number of tunnel fans (1 to 20 tunnel fans). *If tunnel fans are used in a la yer facility, a maximum
of 5 lateral fans can be enabled; if tunnel fans are not used, up to 20 lateral fans can then be enabled.
Number of coolings — Enable the proper number of cooling outputs (0 to 6 outputs).
RH shutoff cooling ? — Select “Yes” for the controller to disable the cooling outputs when the humidity level gets too high. Refer to sec­tion 12. 3 for further information about this RH compensation method. * This parameter is
accessible if the controller is used in a broiler, layer, or turkey facility and if at least 1 cooling output and relative humidity sensor are enabled above. It is also common to all programs of the controller.
Activate cooling low RH ? — Select “Yes” for the controller to activate the cooling outputs when the humidity level gets too low. Refer to
List of parameters Value
Contrast 50% Backlight intensity 3 Key beeper t one 100% Language English Controller used for Breeder Time mo de AM/PM Tempe rature Unit °F Use static pressure sensor? Yes/No Pressure Unit “WC Use min. vent ram ping? Yes/No Use relative humidity sensor? Yes/No Use RH min ve nt. compe nsation? Yes/No Use outside T° sensor? Yes/No Use critical alarm? Yes/No Num ber of program s 10 Save curre nt program to Progra m x Co nfir m Yes/N o Num ber of water meters 2 Water meter unit gal Num ber of T° sensors 8 Use wind speed ? Yes/No Use am monia sensor? Yes/No Use water flush? Yes/No Num ber of water lines 8 Num ber of natural curtains 8 Use curtain inlet? Yes/No Num ber of heaters 32 Use heater RH com pensation? Yes/No Use hi fire heaters Yes/No Num ber of fans 5 Num ber of tunnel fans 20 Num ber of coolings 6 RH shutoff cooling ? Yes/No Activate cooling on low RH? Yes/No Use Weedon fog gers ? Yes/No Num ber of fogger zones 2 Activate Foggers on low R H? Yes/No Num ber of feeders 3 Num ber of time clocks 12 Cloc k mode Start /Stop Feeder 1 Assigne d to clock Clk1 Feeder 2 Assigne d to clock Clk2 Feeder 3 Assigne d to clock None Use stir fan? Yes/No Stir fan base on T° Use light? Yes/No Num ber of light programs 9 Use sidewall vent? Yes/No Use tunnel i nlet? Yes/No Num ber of tunnel inlets 2 Tun nel inlet mode SP Vent inlet mode T° Vent inlet SP adjustment? Yes/No Use attic vent? Yes/No Use attic T° sensor Yes/No Use attic min vent. compen s? Yes/No Pre-opening m ode Auto Use night set point? Yes/No Use min vent. night on tim e? Yes/No Day starts at 8:00A Night starts at 6:00P Monitor breaker te mperature? Yes/No Breaker sensor Sensor 1 Use password s? Yes/No Num ber of relays 3 RP32 Use current se nsors? Yes/No Ap pr o x.o pe rat io n c ost 0.0 0$ /KW /H Fan voltage 120 V Tun fan v oltage 120 V Com munication s peed High Curre nt condition display All
(example only)
PRO-VISION rev.07
11
PRO-VISION
section 12 .3 for further information about this RH compensation method. * This parameter is
accessible if the controller is used in a broiler, layer or turkey facility and if at least 1 cooling output and relative humidity sensor are enabled above. It is also common to all programs of the controller.
Use Weedon foggers ? — Select “Ye s” to use the Weedon foggers.
Number of fogger zones — Enable the desired number of fogger zones (1 to 6 zones). *This
parameter is accessible if the foggers are enabled above.
Activate Foggers on low RH ? — Select “Ye s” for the controller to activate the foggers when the humidity level gets too low. Refer to sec­tion 12. 3 for further information about this RH compensation method. * This parameter is
accessible if the foggers an d relative humidity sensor are enabled above. It is also common to all programs of the controller.
Number of feeders — Enable the desired num­ber of feeder run time monitoring inputs and then refer to section 4.5.2 to assign them to the digital inputs of the PRO-VISION. In all, the controller can monitor 6 digital inputs (water meters and feeder-monitoring inputs). *This parameter is common to all programs of the
controller.
Number of time clocks — Enable the proper number of time clocks (0 to 12 outputs).
Use clock loop feeding? — This option al­lows defining a number of on/off cycles to be performed within a given clock cycle (see graph in section 9 .1). Select “Ye s” to enable this operating mode or select “No” to use the regular start/ stop mode. *This parameter is not
available in a breeder production.
Clock mode (Breeder mode only) — The clock mode allows stopping a time clock at a spe­cific time of the day (Start/Stop mode) or after a certain run time (Start/Run mode). Select the desired operating mode of the time clocks. Note that the “S ta rt/Ru n” option allows stop­ping the outputs with a little more precision since it allows stopping them by the seconds (contrarily to the “Start/Stop” mode which al­lows stopping them by the minutes). * This
parameter is accessible in breeder mode if at least 1 time clock is enabled above.
Feeder #x Assigned to Clock — When a feeder run time alarm occurs, the controller can open the relay associated with the feeder (see section 4.7.1) or stop a particular clock output. Select the clock output that needs to be stopped when a feeder run time alarm occurs or select “None” if no clock output needs to be stopped. *Refer to section “13.2.8.
Feeder Alarms” on page 49 to set the maximum run time of the feeders or to restart a feeder after it has been stopped.
Use stir fan? — Select “Yes” to enable the stir fan output.
Stir fan base on — If the stir fan output is enabled above, specify its operating mode: select “ Tem p” if it operates within a certain temperature range or select “MinV” if it only operates in minimum ventilation (refer to section 6.6 for further information on this function).
Use light? — Select “ Yes” to enable the 0-10V light output.
Number of light programs — If the light output is enabled above, select the desired number of light programs (1 to 9 programs).
Use sidewall vent ? — Select “Yes” to enable the sidewall vent output. * This parameter is
accessible if the static pressure sensor is enabled above.
Use tunnel inlet ? — Select “Yes” to use a tunnel inlet.
Number of tunnel inlets — If the tunnel inlet option is enabled above, select the number of tunnel outputs in use (1 or 2 tunnel inlets).
Tunnel inlet mode — Tunnel inlets can either move according to the level of static pressure (S.P.) or according to the room temperature. Select the desired operating mode. * This
parameter is accessible if at least 1 tunnel inlet is enabled above.
Vent inlet mode — The position of vent in­lets can either be defined according to the static pressure level or in timer mode as a function of temperature. Select “S .P.” if they are regulated by the static pressure level or “T°” if their opening is based on temperature variations.
Vent inlet SP adjustment ? — The controller can automatically adjust the static pressure set points as a function of inside or outside temperature. Select “Insi de T°” to define a second group of static pressure set point (this group starts being used when the room temperature reaches a certain point); select “Oustide T°” to define different pressure set points for winter and summer or select “No” to disable these functions. *This parameter
is accessible if the Vent Inlet Mode is set to “S.P.” above.
Use attic vent? — Select “Ye s” to enable the attic vent output.
Use attic T° sensor? — Select “Ye s” if a temperature sensor is present in the attic. * This parameter is accessible if the attic vent is
enabled above.
Use attic min vent. compens? — In order to extract air from the attic, the controller can increase the operating time of the fans, in minimum ventilation, when temperature is suitable in the attic. Select “Ye s” to enable this compensation function (refer to section
6.5 for further information on this function). * This parameter is accessible if the attic sensor is
enabled above. It is also common to all programs of the controller.
Vents pre-opening mode — The pre-opening delay is used to pre-open the vents (sidewall & attic vents) before activating the fans at the startup of each minimum ventilation cycle. The controller can use a steady pre-opening delay or can set this delay automatically. Se­lect “Au to” to use an automatic pre-opening delay or select “Ma n .” to set the delay your­self. * This parameter is accessible if the attic vent
or sidewall vent is enabled above.
Use Night Set Point? — Select “Ye s” to use a different target temperature at night; select “N o” to disable this function.
Use min. vent. night on time ? — The con­troller can use different minimum ventilation timer at night. Select “Ye s” to use particular night settings.
Day starts at — Set the time at which the day timer starts being used in minimum ventila­tion. * This parameter is accessible if the “Night
min. vent. on time” option is enabled above.
12
PRO-VISION rev.07
PRO-VISION
Night starts at — Set the time at which the night timer starts being used in minimum ventilation. * This parameter is accessible if the
“Night min. vent. on time” option is enabled above.
Monitor breaker temperature ? — Select “Yes” if a temperature sensors is used to monitor the temperature of the main breaker. The controller will set off an alarm if the reading of this input gets higher than acceptable temperature limit. * This parameter is common
to all programs of the controller.
Breaker sensor — If the breaker monitoring function is enabled above, specify which of the temperature sensors is used for this pur­pose (sensor 1-8). * This parameter is common
to all programs of the controller.
Use password? — Select “Yes” to enable the password protection or “N o” to disable it. * This parameter is common to all programs of
the controller.
Number of relays — Select the proper relay panel or combination of relay panels in use:
1 RP-32 / 1 RP-40 / 1 RP-40 & RP-16 2 RP-32 / 1 RP-32 & RP-40 2 RP-40 / 3 RP-32 / 3 RP-40 / 4 RP-32
* This parameter is common to all programs of the controller.
your application only uses relay panels with the “CS” technology or select “Low” if your application contains 1 or more relay panels that do not use this technology. *Refer to
chapter 16 to see the communication rate currently being used by your controller.
Current condition display — Select what information needs to be displayed on current condition menu: select “Al l” for the controller to display all possible pieces of information or select “W/O heat” or “W/O Prb,Heat” to re­move the heater run time and/or the reading of individual temperature sensors from the current condition display. * This parameter is
common to all programs of the controller.
Use current sensors ? —Select “Yes” if at least 1 output uses a current sensor.
Approximative operation cost — The control­ler can calculate the approximate operating cost of the outputs that are using a current sensor. Select the going rate per kilowatt­hour.* This parameter is accessible the current
sensor is enabled above. It is also common to all programs of the controller.
Output voltage — Specify what voltage each output uses: 120, 208 or 240 Volts.
Communication speed — The communication speed provided by the controller depends on the type of relay panels you are using. Using the high-speed communication mode allows connecting more relay panels and current sensors without lowering the communica­tion speed of the controller. Note that the high-speed mode can only be used if your application exclusively contains relay panels with the “CS” technology (the letters “CS” are written on the faceplate of a relay panel that uses this technology). Select “High” if
PRO-VISION rev.07
13
PRO-VISION

4.5. Sensor Assignment

The selection of sensors must be made separately for each controller program in use.
4.5.1. Assigning the Sensors
The controller outputs either run according to the average reading of their own selection of sensors or according to a pre-defined group of sensors (such as the average temperature). The table below gives a list of all outputs and tells according to which selection of sensors each one of them operates.
Outputs Selection of sensors
Heater 1-32
Heat 1-16 Hi Fire
Cooling 1-6
Fogger Zones 1-6
Natural curtains 1-2
Egg room heater
Egg room cooling
Fans 1-5
Stir Fan
Tunnel Fans 1-20
Non-brood zones: A non-brood zone is an unused part of the house. This type of zone is automatically created when a heater is only being controlled by a selection of sensors that are not used to measure the average room temperature. Refer to section 4.8 for further information about non-brood zones.
The selection of sensors must be made separately for each of these output.
In lateral ventilation, these outputs operate
according to the “Aver- age T°” sensor group. In
tunnel ventilation, they operate according to the sensors that are associ­ated with the tunnel fan output in use.
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
2. A table showing all outputs in use is dis­played. Select the desired output with the arrow keys.
On/Off Settings
Ite ms
Tun 1 Tun 2 Tun 3 Tun 4 Tun 5 Cool 1 Fan 1 Fan 2 Fan 3 Fan 4 Heat 1 Heat 2 Heat 3
Set Point : 75.0
On Off Mode
60.0 63.5 Non brood
60.0 63.5
60.0 63.5
60.0 63.5
60.0 63.5 Ti me r
60.0 63.5 Sta rt si dew all 6 0.0 63. 5 Close attic
60.0 63.5 Start tunnel 6 0.0 63. 5 Close sidewall
60.0 63.5
60.0 63.5
60.0 63.5
60.0 63.5
To modify use
-
Htr /fan shut
Time
clock
Water
flush
Average
Sensor
When an output is selected, the controller displays a sensor assignment tab at the right hand side of the screen (the tab is associ­ated with the chosen output). If the output operates according to a group of sensors, the tab leads to the sensor assignment menu of the group; if it operates according to its own selection of sensors, the tab leads to the sen­sor assignment menu of the chosen output.
3. Select the sensor assignment tab with the menu selectors.
Average Sensor
1 2 3 4 5 6 7 8
--- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
--- --- --- --- --- --- --- ---
25 26 27 28 29 30 31 32
--- --- --- --- --- --- --- ---
To modify use
4. Use the +/- buttons to put a check mark in the box of the temperature sensors that are used to control the selected output (or that forms the selected group of sensor).
4.5.2. Assigning the Digital Inputs
The controller has 6 digital inputs that can be used to monitor a water meter or the run time of a feeder. Enable these inputs in the Set-up menu (section 4.4) and assign them to digital inputs #1-6 of the controller.
1. Select:
Main menu
* Set-up
* * Digital Inputs
* A password may be required to access this menu (see sec. 4.2.1).
* * This tab is accessible if at least 1 water meter or feeder-monitoring input is enabled in the Set-up menu (see sec. 4.4).
Digital Input Assig nment
1 2 3 4 5 6
Wtr1 Wtr2 Feed1 Feed2 Feed3 -
To modify use
2. Select the desired digital input and press Enter to assign a function to this input.
14
PRO-VISION rev.07
PRO-VISION
4.5.3. Selecting the Attic Sensor
If a temperature sensor is present in the attic, please select which input number the attic sensor uses.
1. Select:
Main menu
* Inlets / Vents
* * Attic Sensors
* This menu is accessible if at least 1 inlet is enabled in the Set- up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
* * This tab is accessible if the attic sensor input is enabled in the Set-up menu (see section 4.4).
Attic Sensor
1 2 3 4 5 6 7 8
--- --- --- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
--- --- --- --- --- --- --- ---
25 26 27 28 29 30 31 32
--- --- --- --- --- --- --- ---
To modify use
---
2. Use the +/- buttons to put a check mark
in the box of the temperature sensor located in the attic.
4.5.4. Egg Room Sensors

4.6. Calibrating the Inputs

This section shows how to calibrate the reading of the sensor inputs in order to obtain accurate and uniform readings from all sensors. It also shows how to calibrate the flow rate of the water meters.
1. Select:
Main menu
* Set-up
Sensor Calib.
* A complete-access password may be required to access this menu (see sec. 4.2.1).
A table showing the calibration values of each sensor input is displayed:
Sensor calibration
Temperatur e sensor 1 Temperatur e sensor 2 Temperatur e sensor 3 Outside tempe rature sensor Static pressure sensor Relative humidity sensor Water meter 1 Water meter 2 Min am monia value Max am monia value
To modify use
-
0.00
1.0g al /p
1.0g al /p 0 ppm
1000 ppm
0.0
0.0
0.0
0.0
0.0
2. If required, calibrate the reading of the sensors. Note that the calibration settings are common to all programs of the controller.
Use the +/- key to enter a negative offset.
Temperature (indoor & outdoor) — The reading of the inside and outside temperature sensors can be adjusted of ±10 °F (±5.6 °C).
Static pressure sensor — The reading of the static pressure sensor can be adjusted of ±0.10 ” WC (±25 Pa). *This parameter is acces-
sible if the static pressure sensor is enabled in the Set-up menu (see section 4.4).
Relative humidity sensor — The reading of humidity sensor can be adjusted of ±10%. *This parameter is accessible if the RH sensor is
enabled in the Set-up menu (see section 4.4).
Water meter calibration — Specify the flow rate of each water meter. It ranges from 0.1 to 100.0 gallons (or liters) per pulse. *This
parameter is accessible if a water meter is enabled in the Set-up menu (see section 4.4).
Min/max ammonia values— In order to use the ammonia sensor, you must specify the minimum and maximum ammonia levels that can be detected by the sensor (in ppm). *This
parameter is accessible if the ammonia sensor is enabled in the Set-up menu (see section 4.4).
If it is used in a breeder facility, the control­ler automatically enables an egg room and controls up to 3 outputs in this room (heater, cooling & humidity outputs). Each of these outputs operates according to a specific tem­perature sensor. Please refer to chapter 11 of this manual to specify which sensor is used in the egg room.
4.5.5. Main Breaker Sensor
A temperature sensor can be used to moni­tor the temperature of the main breaker. The controller will set off an alarm whenever the reading of this temperature input gets too high. Refer to the Set-up menu in section
4.4 to select the temperature sensors used for this purpose (if applicable).
PRO-VISION rev.07
15
PRO-VISION

4.7. Relays

4.7.1. Relay Assignment
The controller activates the loads by means of external relay panels. In all, it can control up to 128 relays. This section shows how to specify the function of each relay. Please refer to the wiring diagram enclosed with your relay panel to connect the loads and to assign the ID numbers of the panels.
A worksheet is available at the end of this manual to write down the function of each relay.
Relay Functions
Display Meaning
Htr Heater
Hi
#x; #xx Hi Fire heater #x or Heater #x
Fan Fan
Tun Tunnel fan
Feed Feeder
Cool Cooling output
Clk Time clock
Flu Water flush output
Stir Stir fan
Light On/Off light output
Bckup Backup device
2
SW-O
/SW-C2Sidewall vent open/close relay
2
AV-O
/ AV-C2Attic vent open/close relay
2
TN-O
/ TN-C2Tunnel inlet open/close relay
Eg.Htr Egg room heater
Eg.Cool Egg room cooling output
Eg.RH Egg room humidity output
Fogg Fogger zone
(depending if your controller uses the
hi-re option or if it uses 32 relays).
1
1. Select:
Main menu
* Set-up
Relay Assign
* A complete-access password may be required to access this menu (see sec. 4.2.1).
The function of each relay is displayed.
Relay Assignm ent
1 2 3 4 5 6 7 8
Fan 1 Fan 2 Fan 2 Fan 3 Fan 4 Tun 1 Tun 2 T un 3
9 10 11 12 13 14 15 16
Heat HiFi1 Heat2 HiFi2 Heat3 HiFi3 Cool 1 Cool 2
17 18 19 20 21 22 23 24
Cool 3 Cool 4 Stir S V-O SV-C AV-O AV-C TN-O
25 26 27 28 29 30 31 32
TN-C Clk 1 Clk 2 Clk 3 - - - -
Select an item and press
2. Use the arrow keys to select the desired relay number and then press “Enter” to change its function. A table showing all possible functions prompts on screen.
Relay 1 Assignm ent
Htr HiFi Fan Tun Fee d Cool Clk Flu Stir Light Bcku p SW-O SW-C TN-O TN-C AV-O AV-C Eg.Cool Eg.Htr Eg.RH Fogg Off
Use the arrow keys to select the type of output being controlled by the relay and then press “Ent er”.
4.7.2. Relays with Current Sensors
The controller can monitor the current flow on each of its outputs. The following procedure shows how to identify the outputs that are using a current sensor.
1. Select:
Main menu
* Set-up
* *Current sensors
* A complete-access password may be required to access this menu (see sec. 4.2.1).
** This menu is accessible if a current sensor is enabled in the Set-up menu (see section 4.4).
Relay current se nsor assignment
1 2 3 4 5 6 7 8
--- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
--- --- --- --- --- --- --- ---
25 26 27 28 29 30 31 32
--- --- --- --- --- --- --- ---
To modify use
2. Use the +/- buttons to put a check mark in the box of the relays that are using a cur­rent sensor.
3. If the controller uses many outputs of the same type, choose the output number from the drop-down menu.
4. Proceed the same way to assign a relay to each output in use.
Htr
Htr 2
Htr 3
Htr 4
1. Feeder relays are used to stop the feeders when a feeder run time alarm occurs. These relays are normally closed (NC) relays which open when their
respective feeder exceeds a user-dened run time.
2. Some relays on the relay panels have specially been designed to connect actuators (an actuator relay has an “Open/Off/Close” marking instead of an “On/Off” marking on the faceplate of the panel). When actuators are connected to these relays, their open and close relays can never be activated at the same time.
16
PRO-VISION rev.07
PRO-VISION

4.8. Non-Brood Zones & Clean Mode

Definition of a Non-Brood Zone: A non-brood
zone is an unused part of the house. This type of zone is automatically created when a heater exclusively uses temperature sen­sors that are not used to measure the aver­age room temperature. Non-brood zones are generally not ventilated and only have some heaters to ensure minimum heat.
Heaters in Non- Brood Zones: The operating temperatures of the heaters in non-brood zones are related to the “Non-Brood temperature set point” rather than on the regular temperature set point. This means that if the non-brood temperature set point changes, the operating temperatures of non-brood heaters will be ad­justed consequently. Refer to section 5.1 to set the “Non-Brood temperature set point”.
Definition of the Clean Mode: The clean mode is used to interrupt regular operations of the controller when the whole house is empty. When this mode is enabled, the controller provides a minimum level of heat and venti­lation (optional). In clean mode, the heaters operate according to their non-brood settings.
Low Temperature Alarms in Clean Mode: The controller can sound an alarm if the temperature gets too low while it operates in clean mode (or when the temperature gets too low in an empty zone). Once it is enabled, refer to section 13. 2 to adjust the low temperature limit.
Figure: Heaters in Non-Brood Zones
Fans
Heaters
Temp.
Sensors
Heaters
Figure: Heaters in Clean Mode
Heaters
Temp.
Sensors
Heaters
Clean Mode
Unused Fans
Heater
Temp.
Sensors
Temp.
Heater
Temp.
Sensor
Sensor
Heater
Non-Brood ZoneBrood Zone
Unused Fans
Unused FansUnused Fans
Temp.
Sensors
Heater
Unused Fans
Unused Fans
1. Select:
Main menu
* Start Flock
* A password may be required to access this menu (see section 4.2.1).
2. Set the following parameters:
Clean Mode — Select “On” to enable the clean mode or select “Of f” to disable it.
Alarm low T° — Select “Yes” for the con­troller to set off an alarm when the average temperature gets lower than the Non Brood Set Point while the controller is in clean mode. *This parameter is accessible if the clean mode is
enabled above or if an empty zone is used.
Use minimum ventilation? — Select “Yes” to activate minimum ventilation cycles while the clean mode is on.
Unused Fans
Mortality
Loss (%)
Stat Flo ck
Age
Clean M ode
Use min.vent?
To modify use -
PRO-VISION rev.07
Start flock
Remaining
0
Program
0.00
Age
Nb Birds
No
New Mortality
1
Alarm low T°?
Yes
Yes
10000
Progra m 1
10000
0
No
17
PRO-VISION

4.9. Test Mode

The test mode is used to simulate changes in the ambient temperature and relative humid­ity and verify the controller’s performance. When the test is enabled, all outputs of the controller operate according to the simulated temperature. The test automatically ends after 15 minutes of inactivity or if the user deacti­vates it manually.
1. Select:
Main menu
* Set-up
Test Mode
* A complete-access password may be required to access this menu (see sec. 4.2.1).
Test Mo de
Program
Progra m 1
Status
Hu mid ity
2. Set the following parameters:
Program # — This is the program that is cur­rently used by the controller. It is displayed for information only. *Refer to section 4.3 to change
the program in use.
S. P.
Tem peratur e
On
0
---
77. 8

4.10. Version

The version menu gives the version number of the program used by the controller. This piece of information is useful to get techni­cal support.
1. Select:
Main menu
* Set-up
Version
* A complete-access password may be required to access this menu (see sec. 4.2.1).
Pro -visio n
V X.X
Build no. XXXX
Released: Jan 1 200X
Stat. Pressure — This is the current level of static pressure. It is displayed for information only and cannot be modified manually. * This
parameter is accessible if the test mode is enabled above and if a static pressure sensor is enabled in the Set-up menu (see section 4.4).
Status — Select “On” to enable the test mode or select “Off ” to disable it.
Temperature — Set the simulated room tem­perature to the desired value. * This parameter
is accessible if the test mode is enabled above.
Humidity — Set the simulated humidity level to the desired value. * This parameter is acces-
sible if the test mode is enabled above and if the RH sensor i s enabled in the Set-up menu (see section 4.4).
18
PRO-VISION rev.07
PRO-VISION

5. SET POINTS

5.1. Temperature & RH Set Points

1. Select:
Main menu
* Set Point
* A password may be required to access this menu (see section 4.2.1).
The current temperature & relative humid­ity (RH) set points are displayed along with a graph of the temperature set point ramp. Refer to section 5.2 for further information about this ramp.
2. Set the following parameters:
Day set point — Set the temperature set point that is used during the day (this set point is used all day long if the night set point is not enabled). The controller can also change the day set point automatically over time by us­ing a curve(see section 5.2). * This parameter
is common to all programs.
Night set point — A different temperature set point can be used at night. The night set point can be used to lower the target room temperature for instance. The night set point is relative to the day set point, which means that it is automatically adjusted when the day set point changes. Set the night set point to the desired value. *Accessible if the night set point
is enabled (see section 4.4).
Non brood — Set the target temperature used in the non-brood zones. *Refer to section 4.8 for
further information about non brood zones.
RH Set Point — The relative humidity (RH) set point is the target level of relative humidity in the room. It is only used if the controller is used in a broiler, layer or turkey facility. If the humidity level in the room gets higher than this set point, the controller can enable differ­ent compensation functions to lower it down (see chapter 12). Set the relative humidity set point to the desired value. * This parameter is
accessible if the controller is used in a broiler, layer or turkey facility and if a RH Compensation func­tion is enabled in the Set-up menu (see section 4.4) .
Set Point
Day
Non brood
Temp erature
90.0
84.4
81.6
78.8
76.0
73.2
70.4
67.6
64.8
62.0
75.0
Night
RH Set Point
35.0
Ram ping
1 5 10 14 19 24 28 33 38 42 47 Age
To modify u se
-
77. 0
65
Ram ping

5.2. Set Point Ramp

The controller can automatically adjust the temperature set point over time with a ramp. The set point ramp is composed of 12 steps and each step associates a temperature set point with an animal age. Once the ramp is enabled, the controller changes the tempera­ture set point every hour in a linear fashion between consecutive steps of the ramp. When it reaches the last step, the controller keeps using the last temperature set point until the end of the flock.
Temperature
Tem peratu re
90.0 8 7.2
84.4
81.6
78.8
76.0
73.2
70.4 6 7.6
64.8
62.0 1 5 10 14 19 24 28 33 38 42 47 Age
Set Point Ramp
1. Select:
Main menu
* Set Point
Ramping
* A password may be required to access this menu (see section 4.2.1).
2. Set the following parameters. * The param­eters below are common to all programs.
Ramping Status — This is the status of the set point ramp. Select “O n” to enable it or select “Off” to disable it.
Age — Set the age at which each step starts. This parameter ranges from -5 to 450 days (negative values are used to prepare the house before letting the animals in).
Temperature — Assign a temperature set point with each step of the ramp. If you don’t need 12 different steps, repeat the last tem­perature for each unnecessary step.
Rampin g Status: OFF
Age Set Point
1 90.0° F 7 85.0° F 10 8 0.0°F 15 78.0°F 21 7 2.0°F 25 70.0°F 28 6 8.0°F 32 6 6.0°F 36 64 .0°F 40 6 2.0°F 46 62 .0°F 47 62.0 °F
To modify u se
-
PRO-VISION rev.07
19
PRO-VISION

6. VENTILATION & COOLING

6.1. Overview of the Ventilation Concepts

Ventilation Concept in a Broiler or Layer Facility Ventilation Concept in a Turkey or Breeder Facility
In tunnel mode, ventilation is provided by chosen tunnel fans and the air intake is exclusively provided by the tunnel inlet (the sidewall vents are closed). The controller starts measuring the average temperature according to the tunnel sensors and starts using the tunnel inlet static pressure limits and alarm limits.
In tunnel mode, ventilation is provided by chosen tunnel fans and the air intake is exclusively provided by the tunnel inlet (the sidewall vents & natural curtains are closed). The controller starts measuring the average temperature according to the tunnel sensors and starts using the tunnel inlet static pres-
sure limits and alarm limits. This ventilation
mode is optional in a turkey facility.
Startup of the
tunnel fan labeled
“Close sidewall”
(see sec. 6.5.3).
Startup of the
tunnel fan labeled
“S tar t Tunne l”
(see sec. 6.5.3).
“ON T°”
of the first
lateral fan
As the room temperature rises, the control­ler can start opening the tunnel inlet before closing the sidewall vents in order to create a smooth transition between lateral & tunnel ventilation. This transition is optional.
In lateral mode, ventilation is provided by chosen sidewall fans and the air intake is provided by the sidewall and/or attic vents.
In minimum ventilation, the fans that are used to ensure a minimum ventilation run in timer mode and the vents (sidewall and/or attic) slightly open prior to each activation of the fans.
Minimum Vent. Lateral Mode Tunnel ModeTransition (opt.)
Startup of the
tunnel fan labeled
“S tar t Tunne l” (see
sec. 6.5.3).
Startup of the first
natural ventilation
curtain (see sec.
6.5.3).
“ON T°”
of the first
lateral fan
In natural ventilation, no fan is running and the air intake is provided by the natural ven­tilation curtain and by the tunnel inlet (if a tunnel inlet is used).
In lateral mode, ventilation is provided by chosen sidewall fans and the air intake is pro-
vided by the sidewall and/or attic vents. This
ventilation mode is optional in a turkey facility.
In minimum ventilation, the fans that are used to ensure a minimum ventilation run in timer mode and the vents (sidewall and/or attic) slightly open prior to each activation
of the fans. This ventilation mode is optional
in a turkey facility.
Minimum Vent. (opt.) Lateral Mode (opt.) Tunnel Mode (opt.)Natural Mode
20
PRO-VISION rev.07
PRO-VISION

6.2. Minimum Ventilation

Minimum ventilation cycles are activated when the room temperature is lower than the start temperature of the first fan stage. Run­ning the fans even though ventilation is not required for reducing the room temperature is useful to reduce humidity levels and supply oxygen to the room. It also prevents the fans from freezing in winter.
Minimum ventilation can only be used
if at least 1 fan output is enabled in
the Set-up menu (see section 4.4).
6.2.1. Minimum Ventilation Timer
The minimum ventilation timer is composed of an “O n Ti me” and of a “C ycle Time” . The fans run during the “On T ime” and then stop until the end of the “C yc le T ime”. This timer is common to all programs of the controller.
Min.Vent
Fan Status
ON
OFF
Minimum
Ventilation Timer
ON Time
Cycle Time
Time
Automatic adjustment of the minimum venti­lation timer as a function of relative humidity: The controller can automatically increase the “On Time” portion of the minimum ventilation timer as the humidity level increases. Refer to section 12.1 for further information about this RH compensation function.
The controller can automatically extend the cycle time in order to pre-open the vents.
Settings
1. Select:
Main menu
* Minimum Ventilation
** Day Settings or Night Settings
* A password may be required to access this menu (see section 4.2.1).
**If different minimum ventilation settings are used at night, select the parame ters you want to adjust (day or night settings). These tabs are accessible if the “Use min. vent. night on time” parameter is enabled in the Set-up menu (see section 4.4).
2. Set the following parameters:
Mini mum ve ntilation
On Time(or) Night On
Cycle
ON TIME
3:05
2:48
2:31
2:14
1:57
1:40
1:23
1:06
0:49
0:32
0:15
1 2 3 4 5 6 7 8 9 10 11 12 AGE
0:1 5 M:S
5:0 0 M:S
Cor rect.
Enhanced
Ram ping
0sec
No
Graph is accessible if the minimum ventilation ramping is enabled in Set-up menu.
On Time — Set the “O n Ti me” of the minimum ventilation timer. If the minimum ventilation ramping is enabled, the controller automati­cally defines this value as a function of the animal age (see section 6.2.2). *If different day/
night minimum ventilation timers are used, press the “Day Settings” tab to access this parameter.
Night On — Set the “On Time” of the mini- mum ventilation night timer. If the minimum ventilation ramping is enabled, the controller automatically defines this value as a func­tion of the animal age (see section 6.2.2).*If
different day/night minimum ventilation timers are used, select the “Night Settings” tab to access this parameter.
Correct. — Select the correction that needs to be applied to all steps of the minimum ventilation ramp. The correction value is expressed in seconds and can either be a positive or negative value. *This parameter is
accessible if the minimum ventilation ramping curve is currently running.
Cycle — Set the cycle time of the minimum ventilation timer. Note that the cycle time must be longer than the “On Time”.
Enhanced — Select “Ye s” if you want the On Time portion of the minimum ventilation timer to increase as the room temperature gets closer to stage 1 start temperature or select “N o” to disable this function. With this function, the On Time reaches the Cycle Time (fans are fully on) at the beginning of the highest minimum ventilation timer fan.
PRO-VISION rev.07
21
PRO-VISION
6.2.2. Min Ventilation Timer Ramp
The controller can automatically adjust the “On Ti me” portion of the minimum ventilation timer
with time. The minimum ventilation ramp is composed of 12 steps and each step associates an On Time with an animal age. Once the ramp is enabled, the controller changes “O n Ti me” portion of the minimum ventilation cycles every hour in a linear fashion between consecutive steps of the ramp. When it reaches the last step, the controller keeps using the last “On Ti me” until the end of the flock.
ON TIME
3:05
2:48
2:31
2:14
1:57
1:40
1:23
1:06
0:49
0:32
0:15
1 2 3 4 5 6 7 8 9 10 11 12 AGE
Night Ramp: The minimum ventilation ramp can be configured differently for nighttime. Refer to the Set-up menu to enable or disable the night settings (see section 4.4).
Ram ping
1. Select:
Main menu
* Minimum Ventilation
**Ramping
* A password may be required to access this menu (see section 4.2.1).
** This tab is accessible if the minimum ventilation ramp is enabled in the Set-up menu (see section 4.4).
Rampin g Status: Off
Age On Night On
1 0:15 M:S 0:00 M:S 2 0:33 M:S 0:15 M:S 3 0:49 M:S 0:30 M:S 4 1:06 M:S 0:45 M:S 5 1:23 M:S 1:00 M:S
2. Set the following parameters. *The param­eters below are common to all programs.
Ramping Status — This is the status of the minimum ventilation ramp. Select “O n” to enable it or select “Off ” to disable it.
Age — Set the age at which each step starts. This parameter ranges from -5 to 450 days (negative values are used to prepare the house before letting the animals in).
On — Assign a minimum ventilation “On Tim e” with each step of the ramp. If you don’t need 12 different steps, repeat the last “On T ime” for each unnecessary step.
Night On — If a different night ramp is used, assign a night “On Tim e” for each step of the curve. If you don’t need 12 different steps, repeat the last “O n Time” for each unneces­sary step. * This parameter is accessible if the
“Night Min. Vent.” option is enabled in the Set-up menu (see section 4.4).
6.2.3. Minimum Ventilation Fans
6.2.3.1. Fan Selection
Minimum ventilation cycles are ensured by a user-defined selection of fans and/or tunnel fans. To identify the fans/tunnel fans that are used in minimum ventilation, set their operating mode to “Timer” or “Tmr, clo attic” in the “On/Off Settings” menu. Refer to the lateral or tunnel fan sections of this manual to assign these fan operating modes (sections
6.3.1 & 6.5.3).
6.2.3.2. Stir Fans in Minimum Ventilation
If the controller uses a stir fan output, it can activate this output according to a particular timer when the fans stand idle in minimum ventilation.
1. Select:
Main menu
* Minimum Ventilation
**Stir Timer
* A password may be required to access this menu (see section 4.2.1).
** This tab is only accessible if the stir fan mode is set to “Min.V” in the Set-up menu (see section 4.4).
2. Set the following parameters:
Stir fan timer settings
On Time C ycle.
0:30 M:S 5:00 M:S
22
PRO-VISION rev.07
3. Press “Back” to see the Ramp graph.
It is possible to adjust all steps of the minimum ventilation ramp while the ramp is active. See “Correct” parameter in section 6.2.1.
On Time — Set the “O n Ti me” of the minimum ventilation stir fan timer.
Cycle — Set the cycle time of the minimum ventilation stir fan timer. Note that the cycle time must be longer than the “O n Time”.
This stir fan timer is only used when the fans stand idle in minimum ventila­tion (Off Time portion of the minimum ventilation timer).
PRO-VISION
6.2.3.3. Fan Cycling
In minimum ventilation, the controller can make a rotation of the fans selection between consecutive cycles. This rotation allows run­ning the fan motors evenly and regularly. In order to use fan cycling, you must specify how many fans must be activated simultane­ously and specify after how many cycles they must switch.
Here is an example of fan cycling with 4 fans. In this example 2 fans are used simultane­ously and a switch is made every 3 cycles:
Fan 1 Fan 2 Fan 3 Fan 4
st
1
step:
Cycles 1-3
nd
2
step:
Cycles 4-6
rd
3
step:
Cycles 7-9
th
step:
4
Cycles 10-12
ON ON
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
1. Select:
Main menu
* Minimum Ventilation
Fan Cycling
* A password may be required to access this menu (see section 4.2.1).
Min Vent Fan Cyclin g
Fans per cycle Chang e fan cycle Fan 1 Fan 2 Fan 3 Tun 1 Tun 2
1
1 On On
Cycle
---
---
2. Set the following parameters:
Fans per cycle — Select how many cycling fans must be activated simultaneously in a minimum ventilation cycle. Only the fans that are labeled “C ycle” will make a rotation from one minimum ventilation cycle to the other. The fans that are labeled “O n” are the regular minimum ventilation fans used in all minimum ventilation cycles.
Only the fans that are not used in timer mode in minimum ventilation can do the fan rotation. Giving a fan the “Cycle” label will thus automatically disable the “Timer” mode for that fan in the On/Off Settings menu and vice-versa.
Change fan cycle — Select after how many minimum ventilation cycles the selection of cycling fans must switch. This parameter ranges from 1 to 1,000 cycles.
Fan#x / Tun#x— To use a fan/tunnel fan ac­cording to the above fan cycling parameters, set its status to “C yc le”.
6.2.4. Air Intake in Min Ventilation
The air intake in minimum ventilation can be provided by the attic vent or by sidewall vents. During the Time ON portion of the minimum ventilation cycle, the vent opens during the “Vent Pre-opening” and then starts moving according to its respective static pressure limits. During the Time OFF portion of the minimum ventilation cycle, the vent stays closed.
Pre-Opening of the Vents: The pre-opening delay is used to pre-open the vents (sidewall & attic vents) before activating the fans at the startup of each minimum ventilation cycle. The controller can use a steady pre-opening delay or can set this delay automatically. Refer to the Set-up menu in section 4.4 to enable/ disable the automatic pre-opening function and refer to section 6.3.2 to set this delay if the automatic function is not used.
Automatic Pre- Opening Delays: If the au­tomatic pre-opening function is used, the controller refers to the time it actually took for the vents to reach the desired pressure range the last time they had to open and then sets the next pre-opening delay accordingly.
Refer to section 6.3.2 to set the pre­opening delay & the static pressure limits.
Opening of the Vents in
Minimum Ventilation
Pre-opening of the vents.
S.P Mode: The vents move according to the pressure level. Timer mode: the vents stay still
The vents close and stay closed
ON
Min.V
Fan
Status
OFF
ON Time
PRO-VISION rev.07
Cycle Time
Time
23
PRO-VISION
Attic Compensation on the Min Ventila­tion Air Intake
When the PRO-VISION operates in minimum ventilation and the attic temperature is warm enough, the controller can extract the warm air from the attic by increasing the operating time of the fans. When this compensation is on, the controller automatically adjusts the “O n Time“ portion of the minimum ventilation timer as a function of the room temperature.
Attic Compensation on
On Time of
the Min
Vent. Timer
Compen-
sated
On Time
(On Time=
Cycle Time)
Regular
On Time
the Minimum
Ventilation Timer*
If the room temperature is higher than the cut­off point of the attic compensation and then starts decreasing, the “On T ime” becomes fully compensated when the room tempera­ture falls to the attic compensation’s cut-off point (“Attic stop comp. at”). The “O n Ti me” then starts decreasing gradually, in a linear fash­ion, as the room temperature falls. The “On Ti me” finally stops being compensated when the room temperature reaches the “Attic start comp at” value.
1. Select:
Main menu
* Inlets / Vents
* * Attic Compens
*A password may be required to access this menu (see section 4.2.1).
* * This menu is accessible if the attic compensa­tion function is enabled in the Set-up menu (see section 4.4).
Attic Compensation
Attic start comp. at Attic stop comp. at
74.0
77. 0
T°. in the attic T°. in the room
Room T° =
Compens.
start T°
Room T° <
Compens.
start T°
*This compensation only takes place when the attic temperature is warmer than the “Attic start comp. at” temperature value.
Room T° =
Compens.
stop T°
Room T°
If the room temperature is cooler than the “Attic start comp at” value and the attic tem­perature is equal or higher than this start-up point, the “On Time” of the minimum ventila­tion cycle is fully compensated in order to extract a maximum level of heat from the attic (the fans are always on). As the room temperature rises and reaches the compen­sation’s start-up point, the “On Time” starts decreasing gradually, in a linear fashion, as the room temperature increases. The “On Ti me” finally stops being compensated when the room temperature is warm enough and reaches the “Room Stop T°” value. At the end of the compensation, the minimum ventilation “On Ti me” goes back to its regular value, and the sidewall vent starts being used jointly with the attic vent.
To modify use
-
2. Set the following parameters:
Attic start comp. at — Select the attic tem­perature over which the attic compensation can be used. This parameter also represents the room temperature over which the “On Ti me” portion of the minimum ventilation timer starts decreasing in a linear fashion as the temperature rises (see graph).
Attic stop comp. at — Select the room tem­perature at which the attic compensation ends. Note that this temperature must be higher than the compensation’s start tem­perature and lower than the room temperature at which the 1st fan stage starts.
24
PRO-VISION rev.07
PRO-VISION

6.3. Lateral Ventilation

Lateral ventilation can only be used if at least 1 fan output is enabled in the Set-up menu (see section 4.4).
6.3.1. Lateral Ventilation Fans
Lateral ventilation begins at the startup of the first fan stage and ends at the startup of the ventilation mode that follows (i.e natural or tunnel ventilation).
A fan output starts running when the room temperature reaches its “On Temperature”; likewise, it stops when the room temperature falls to its “Off Temperature”.
The temperatures at which a fan starts and stops are related to the temperature set point. This mean they are automatically adjusted when the temperature set point changes.
Operating Diagram of
Fan Status
On
Off
Fans Following Time Clocks: In the breeder mode, it is possible for a fan output to start running each time a particular time clock is on. Refer to the “Follow clock” parameter below to use this function.
a Fan Output
On T°
Room T°Off T°
Settings
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select the desired fan output. * These outputs are avail-
able if they have previously been enabled in the Set-up menu (see section 4.4).
On/Off Settings
Ite ms
...
Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 ...
3. Set the following parameters:
On & Off Columns:
Temperatures — Set the room temperature
at which each fan starts and below which it stops. Note that the first fan to start signals the end of minimum ventilation and the begin­ning of lateral ventilation. * Note that the “On
Temperature” of a fan must be greater than its “Off Tem pe ra tu re”.
Mode Column:
This column tells the controller to execute a particular function at the startup of a fan output or allows giving the output a special attribute. Set the mode of each fan output as follows (set the mode to “—” if nothing applies to an output).
Set Point : 75.0
On Off Mode
...
77. 0 76.0
79.0 7 7.0 T im er
80.0 78.0
81.0 79.0
82.0 80.0 Close attic ...
To modify u se
-
Htr /fan shut
Follow
Clock
Close Attic — The controller can close the at­tic vent at the startup of a certain fan output. Assign the “Close attic” label to the fan output at which the attic must close (if applicable). * This option is available if the attic vent is enabled
in the Set-up menu (see section 4.4).
Timer, Close At tic — Use this label to identify a fan that is used in minimum ventilation and whose startup asks for the attic vent to close. * This option is available if the attic vent is enabled
in the Set-up menu (see section 4.4).
4. If you want the selected fan to run when a particular time clock output is on, select the “Follow Clock” tab with the menu selec- tors and then set parameters below. *This
tab is only accessible if the controller is used in a breeder facility.
Fan 1 follow clock
Follow clock Low stop T°
2
Stat.Pressure
73.0
Follow clock — Select during the operation of which time clock output you want the selected fan to run.
Low stop T° — If the room temperature gets too low, the fan stops following the time clock output. Set this security limit to the desired value.
Timer — The “Ti mer” label identifies a fan output that is used in minimum ventilation. A fan output that is labeled “T ime r” runs according to a timer in minimum ventila­tion and runs continuously when the room temperature reaches its “On Temperature”.
The Timer label automatically dissapears if the fan uses the cycling feature (see section 6.2.3.3.
PRO-VISION rev.07
25
PRO-VISION
6.3.2. Attic & Sidewall Vents based on Temperature
The controller can control the opening of two vent outputs in lateral ventilation: a sidewall vent and an attic vent. These vent outputs can either move as a function of temperature (timer mode) or as a function of static pres­sure. Set the operating mode of the vents in the Set-up menu (see section 4.4).
This section shows how the vents move when they are controlled by temperature:
Principle of Operation:
When timer-based vents are used, you must first specify the total time required to open each actuator and then associate an opening with the start-up of each fan stage (openings are defined as a percentage of the total open­ing time). As the room temperature increases and new stages are activated, the vents will open or close accordingly.
Additional Curtain Inlet
It is possible to use one natural curtain out­put in lateral and minimum ventilation. When a curtain is used in one of these ventilation mode, it follows the same movements as the vent inlet. Enable the “Curtain Inlet” option in section 4.4 to use this supplementary inlet in lateral ventilation.
Actuator Reset for Timer Vents
The controller must reset the position of the actuator for each timer-based vent to make sure the vent position is always accurate. This reset is performed automatically according to one of these two methods:
1. Reset the minimum position only (Close mode): Each time a reset is performed,
the vent totally closes. Once the actuator’s position is reset, the vent returns to its previ­ous position.
2. Reset toward the nearest position: If the current vent position is higher than 50% at the reset time, the controller fully opens the vent to reset the actuator’s position; if the current vent position is lower than 50%, the controller closes the actuator to perform the reset. This way, the vent never closes when the room temperature already asks for a wide opening.
Make sure limit switches are located at both ends of the actuators when using this resetting method.
Opening of Sidewall/Attic
Vents as a Function of
Temperature
Vent Opening
(% of the Total Opening Time)
45%
30%
The vent reaches the position associated with fan X.
0%
Fan X
Fan X
ON T°
OFF T°
Fan Y
OFF T°
The vent reaches the position associated with fan Y.
Room T°
Fan Y
ON T°
Settings
1. Select:
Main menu
* Inlets / Vents
* This menu is accessible if at least 1 inlet is enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
Inlets / Vents
Sidew all
Attic
To Modify Pre ss
Pre-op ening Vents
-
15sec
2. Set the following parameters:
Pre-opening Vents — Specify how much time is required to pre-open the sidewall & attic vents before activating the fans in minimum ventilation. Refer to section 6.2.4 for further information on this delay.
3. Press the tab corresponding to the vent you want to adjust (Attic or Sidewall).*These tabs
are only available if the “Vent inlet mode” is set to “Temperature” in the Set-up menu (see section 4.4.).
Fan 1 Fan 2 Fan 3 Fan 4 Tun 1 Tun 2 ... Total open tim e Auto reset period Reset position
To modify use
Sidew all
5% 5% 5% 5% 5% 5%
... 5:00 M:S 6:00 H: M
Near est
-
4. Set the following parameters:
Fan #x or Tun #x — Assign a vent opening (in %) with the startup of each fan/tunnel fan.
Set the vent position to 0% if you do not want it to open during a tunnel fan stage for instance.
Total opening time — Specify the exact time that is required to reach the actuator’s maxi­mum limit switch. The controller will limit the opening of the inlet according to this value. * This parameter is common to all programs.
Auto reset period — The controller must reset the position of the actuator for each timer­based vent to make sure the vent position is always accurate. Set the frequency at which actuator resets must be made (once every 0-24 hour).
Reset position — Select the desired reset mode: “Nearest” to reset the actuator toward its nearest position; select “Close” to reset the actuator at its closed position or select “Open” to reset it at its fully opened position.
26
PRO-VISION rev.07
PRO-VISION
6.3.3. Attic & Sidewall Vents based on Static Pressure
The controller can control the opening of two vent outputs in lateral ventilation: a sidewall vent and an attic vent. These vent outputs can either move as a function of temperature (timer mode) or as a function of static pres­sure. Set the operating mode of the vents in the Set-up menu (see section 4.4).
This section shows how sidewall & attic vents move when they are controlled according to the static pressure level:
Additional Curtain Inlet
It is possible to use one natural curtain output in lateral and minimum ventilation. When a curtain is used in one of these ventilation mode, it follows the same movements as the vent inlet. Enable the “Curtain Inlet” option in section 4.4 to use this supplementary inlet in lateral ventilation.
Principle of Operation
Static-pressure-based vent doors (inlets) open or close as a function of the static pressure level in the room. They open when the static pressure level exceeds the high pressure set point or close when the static pressure level is lower than the low pressure set point. The graph below illustrates this process.
6.3.3.1. Compensation on Pres­sure Set Points
The controller can automatically adjust the static pressure set points being used by the sidewall vents according to the inside or out­side temperature as shown below.
Refer to the Set-up menu in section 4.4 to enable the vent inlet adjustment option.
1) According to Outside Temperature
If an outside temperature sensor is used, the controller can automatically adjust the static pressure limits used by sidewall vents according to the outside temperature. Using higher pressure limits in cold weather allows reducing the cold air intake since the pressure level has to be higher before the vents start opening. Likewise, using lower pressure limits in warm weather allows the vents to move with fewer restrictions.
2) According to Inside Temperature
The controller can use a different set of high and low pressure set points when the room temperature reaches a certain point.
Pressure
S.P.
Limits
in cold
conditions
S.P. Limits in hot
conditions
Static
Limits
Static Pressure
Limits as a Function
of Outside T°
Cold T° Hot T°
Outside
Temperature
Sidewall
Hi pressure
limits*
Sidewall
Lo pressure
limits*
Opening of the Sidewall & Attic Vents
Static
Pressure
The vents
starts closing
after the Wind
The
open
vents
The
vents
move
do not
The
close
vents
*The Hi and Lo pressure limits can automatically be adjusted according to the outside temperature
Delay has
elapsed.
in Lateral Ventilation
The vents stop
closing
Wind Delay
start opening
after the Wind
The vents
Delay has
elapsed.
The vents stop
opening
Wind
Delay
Time
PRO-VISION rev.07
27
PRO-VISION
6.3.3.2. Settings
1. Select:
Main menu
* Inlets / Vents
* This menu is accessible if at least 1 inlet is enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
2. Set the following parameters:
Inlets / Vents
Attic Min. vent. SP Tra nsitional SP Vents Lo 0.05 H i 0.08 Lo 0.05 Hi 0.0 8
Sidewall Min. vent. SP Transitional SP Vents Lo 0.05 H i 0.08 Lo 0.05 Hi 0.0 8
80.0° F
Inlets / Vents
Pre-op ening Vents
-
Pre-op ening Vents
Outside T° Hot
-
15sec
15sec
Wind delay 0:30M: S
Tra nsiti onal
To Modify Pre ss
Sidewall Vents, S.P. set points based on inside T°
Attic Hot SP Cold SP Vents Lo 0.05 H i 0.08 Lo 0.05 Hi 0.0 8
Sidewall Hot SP Cold SP Vents Lo 0.05 H i 0.08 Lo 0.05 Hi 0.0 8
Wind delay 0:30M: S
Outside T° Cold
To Modify Pre ss
5.0°F 45.0° F
Sidewall Vents, S.P. set points based on outside T°
The parameters presented below are only accessible if the sidewall vents operate according to static pressure. Refer to the Set-up menu in section 4.4 to select the operating mode of these vents.
Sidewall Vents Lo/Hi Pressure Limits — Set the static pressure level below/above which the vents must close/open. * This parameter
is accessible if a pressure-based sidewall vent is enabled in the Set-up menu (see section 4.4).
• (Min vent / Transi tional SP) If an inside temperature compensation is applied on the pressure set points, set both groups of pressure set points separately.
• (Hot / Cold SP) If an outside temperature compensation is applied on the pressure set points, set these limits separately for hot and cold weather conditions.
Attic Vents Lo/Hi Pressure Limits — Set the static pressure level below/above which the attic vent must close/open. * This parameter is
accessible if a pressure-based attic vent is enabled in the Set-up menu (see section 4.4).
• (Min vent / Transi tional SP) If an inside temperature compensation is applied on the pressure set points, set both groups of pressure set points separately.
• (Hot / Cold SP) If an outside temperature compensation is applied on the pressure set points, set these limits separately for hot and cold weather conditions.
Wind Delay — When the pressure level gets out of range, the vents wait for the end of the “Wi nd D ela y” before moving; they only move if the high or low pressure condition is valid all along this delay. This way, the vents do not move if a wind draft causes fleeting changes in the pressure level. Set the “Wind Dela y” to the desired value. *Note that this parameter is
common to all air inlets (sidewall vent, attic vent and tunnel inlets).
Pre- opening Vents — Specify how much time is required to pre-open the sidewall & attic vents before activating the fans in minimum ventilation. Refer to section 6.2.4 for further information on this delay. *This
parameter is accessible if the pre-opening is not set automatically by the controller. Refer to the Set-up menu in section 4.4 to enable/disable the automatic pre-opening function.
Outside T° Hot & Cold — If an outside temperature compensation is applied on the pressure set points, specify the outdoor tem­perature at which hot & cold static pressure set points start being used. *These parameters
are accessible if the “Vent inlet SP adjustment” parameter is set to “Outside” in the Set-up menu (see section 4.4).
Transitional T° — If an inside temperature compensation is applied on the pressure set points, specify the inside temperature at which the second group of pressure set points starts being used. *This parameter is
accessible if the “Vent inlet SP adju stment” option is set to “Inside” in the Set-up menu (see section 4.4). This parameter is also related to the temperature set point, which means it is automatically adjusted when the temperature set point changes.
28
PRO-VISION rev.07
PRO-VISION

6.4. Natural Ventilation

The controller can control the opening of 8 natural ventilation curtains. In the natural ventilation mode, all the fans are off and the air intake is provided by the natural curtains and by the tunnel inlet (if applicable). This ventilation mode is only accessible in breeder or turkey facilities. Refer to section 4.4 to select the type of facility in use.
The natural ventilation is only acces­sible in a turkey or breeder facility (see section 4.4).
Note that the static pressure alarm conditions are not monitored while the controller is in natural ventilation.
Beginning of Natural Ventilation: The con­troller enters in natural ventilation when temperature reaches the start temperature of a natural ventilation curtain. At that moment, the controller makes the natural curtain open to its initial position and closes the lateral & attic vents.
Stopping the Fans in Natural Ventilation: The controller switches off all the fan outputs (lateral & tunnel fans) when the temperature reaches the fans shutoff point (“Shutoff fans at”).
Movement of the curtains in natural ventila­tion: A natural ventilation curtain opens to its
initial position when temperature reaches its respective start temperature. The curtain then opens gradually towards its maximum opening as temperature increases; it finally reaches its maximum opening when temperature reaches the “Max Open T°” temperature value.
Operating Diagram of
Natural Curtain 1 Opening
100%
First
Opening
Natural Ventilation
Curtain
0.3°F
Start T°
Natural 1
Max
Open T°
T° of the curtain’s probes
When a curtain reaches a particular position and stops, a temperature variation of at least
0.5°F must occur for the curtain’s position to be readjusted. An “Off Ti me” is also defined to leave a sufficient amount of time between 2 movements of the curtain.
Note that if the tunnel inlet is enabled, this inlet will follow the same movements as natural curtain 1.
Transition from Natural to Tunnel: At the start-up of tunnel ventilation, the natural ventilation curtains close completely and the tunnel inlet opens in the meanwhile. When the natural ventilation curtains are totally closed, the tunnel inlet reaches its required position and the controller activates the proper fans and tunnel fans.
Transition from Tunnel to Natural: Tunnel ventilation ends when the temperature gets lower than the stop temperature of the first tunnel fan stage. At that moment the natural ventilation curtain opens completely and the tunnel inlet opens in the meanwhile. When half the opening time of the natural curtain has elapsed, the controller switches off all the tunnel fans and the tunnel inlet starts moving along with natural curtain 1.
Transition from Natural to Lateral: When the controller goes back to lateral ventilation, the sidewall vents will open during the same amount of time it takes for the natural cur­tains to reach their first opening.
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select the desired natural curtain output. * These out-
puts ar e available if they h ave previous ly been enabled in the Set-up menu (see section 4.4).
3. Set the following parameters:
On temperature — Set the temperature at which the selected natural ventilation curtain starts opening. *If more than 1 curtain is used, the
rst curtain to start moving signals the beginning of
natural ventilation.
On/Off Settings
Ite ms
...
Natur al 1 Natur al 2 ...
Set Point : 75.0
On Off Mode Htr /fan shut
79.0
79.0
...
To modify u se -
4. Select the “Nat.x Setting” tab with the menu selectors to display the curtain settings and set the following parameters:
Natural 1 Settings
Maxim um open T° Shutoff fans at Total open tim e Total opening First op ening Off Ti me
To modify u se
81.0° F
79.0° F
7:00 M:S
60”
2:00 M:S
4”
Maximum open T° — Select the temperature at which the selected curtain reaches its maximum opening.
Shutoff fans at — Select the temperature at which the fans must stop running in natural ventilation. *This parameters is common to both
natural ventilation curtains and is only available if fan outputs are enabled in the Set-up menu (see section 4.4).
Total open time — Select the total opening time of the curtain (in minutes and seconds).
Total opening — Select the total distance that separates the minimum and the maximum positions of the curtain (in inches).
First opening — Select the initial opening of the curtain (in inches). The curtain reaches this opening when temperature reaches its “On Temperature”.
Off Time — Select the amount of time that must be left between 2 consecutive move­ments of the curtain.
Nat.1
Setting
PRO-VISION rev.07
29
PRO-VISION

6.5. Tunnel Ventilation

6.5.1. Principle of Operation
The tunnel ventilation mode begins at the startup of a chosen tunnel fan output. If the lateral ventilation mode precedes the tunnel ventilation mode, the controller can make a smooth transition between both modes by opening the tunnel inlet prior to closing the sidewall vents. Refer to the following sec­tion of this manual to specify the moment at which the transition begins and the moment at which tunnel ventilation is fully enabled.
Temperature Sensors in Tunnel Ventilation:
When it is in tunnel ventilation, the controller measures the room temperature according to the temperature sensors that are associ­ated with the tunnel fan output in use. The sensors that are being used in tunnel ventila­tion are specially defined to compensate for changes in airflow patterns that can distort the room temperature. Refer to section 4.5 to select the temperature sensors used in tunnel ventilation.
Air Intake in Tunnel Ventilation: In tunnel ven­tilation, the air intake is exclusively provided by the tunnel inlets (the sidewall vent, attic vents and natural curtains are closed). Up to 2 tunnel inlets can operate as a function of the static pressure level or as a function of the room temperature. Refer to section 4.4 of this manual to enable the tunnel inlets and to choose their operating mode.
Low Static Pressure Alarm Limit: If the low pressure alarm condition is used, the pressure limit at which the alarm occurs changes when the controller enters in tunnel ventilation. Re­fer to section 13. 2.6 to set the low pressure limit used in tunnel ventilation.
Refer to the previous section to see how the transition is made between natural to tunnel ventilation.
6.5.2. Tunnel Ventilation in Standby
The controller allows putting tunnel ventila­tion on standby at any moment or to disable tunnel ventilation on specific controller programs.
The standby option is useful to prevent the tunnel inlet from opening when the animals are too young or when it is too cold outside for instance. When this ventilation is on standby and the room temperature is suitable for tun­nel ventilation, the controller will not switch to tunnel ventilation and will keep using the highest level of ventilation.
1. Select:
Main menu
* Inlets / Vents
* * Tunnel settings
* This menu is accessible if at least 1 inlet is enabled in the Set- up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
* * This menu is accessible if the tunnel inlet is en­abled in the Set-up menu (see section 4.4).
Allow T unnel
Tunn el settings
To modify u se
2. Set the following parameters:
Allow Tunnel — Select “Yes” to allow tunnel ventilation or select “N o” to put this ventila­tion mode on standby. *This parameter must be
set separately for each controller program.
No
30
PRO-VISION rev.07
PRO-VISION
6.5.3. Tunnel Fans
A tunnel fan output starts running when the room temperature reaches the output’s “On Temperature”; likewise, it stops when the room temperature falls to its “Off Temperature”.
The temperatures at which a tunnel fan starts and stops are related to the temperature set point. This mean they are automatically adjusted when the temperature set point changes.
Operating Diagram of
Tunnel
Fan Status
On
Off
Tunnel Fans Following Time Clocks: In the breeder mode, it is possible for a tunnel fan output to start running each time a particular time clock is on. Refer to the “Follow clock” parameter below to use this function.
1. Select:
* A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select the desired tunnel fan output. * These outputs
are available if they have previously been enabled in the Set-up menu (see section 4.4).
a Tunnel Fan Output
On T°
Main menu
* On / Off Settings
Room T°Off T°
On/Off Settings
Ite ms
...
Tun 1 Tun 2 Tun 3 Tun 4 Tun 5 ...
Set Point : 75.0
On Off Mode Htr /fan shut
...
82.0 80.0
80.0 79.0 Start tunnel 2 8 1.0 8 0.0 Close sidewall 3 4 5
82.0 81.0 - -
83.0 8 2.0 Start tu n n el 2 ...
To modify u se -
3. Set the following parameters:
On & Off Columns:
Temperatures — Set the room temperature
at which each tunnel fan starts and below which it stops. *The On Temperature of a tunnel
fan must be greater than its Off Temperature.
Mode Column: This column tells the control­ler to execute a particular function at the startup of a tunnel fan output or allows giving the output a special attribute. Set the mode of each tunnel fan output as follows (set the mode to “—” if nothing applies to an output).
Timer — The “Ti mer” label identifies a tunnel fan output that is used in minimum ventilation. A tunnel fan that has this label runs according to a timer in minimum venti­lation and runs continuously when the room temperature reaches its “On Temperature”.
The Timer label automatically dissapears if the fan uses the cycling feature (see section 6.2.3.3.
Start tunnel — The “Start tunnel” label indi- cates the moment at which the transition from lateral to tunnel ventilation begins: the first tunnel inlet starts being used at the start-up of that tunnel fan and the sidewall vent keeps being used.
Close sidewall — The “Close sidewall” label indicates the moment at which lateral venti­lation ends. The sidewall vent closes at the startup of the chosen tunnel fan and the tun­nel ventilation mode becomes fully effective at that moment.
Follow
Clock
mode to the other. The sidewall vents close and the tunnel inlet start being used at the startup of the chosen tunnel fan.
Start tunnel 2 — The second tunnel inlet starts being used at the startup of the se­lected tunnel fan output.
Fan Shutoff Column:
Fan Shutoff — The controller can disable
some lateral fans at the startup of chosen tunnel fan outputs. Select the moment at which each lateral fan must stop (if appli­cable). Note that when a fan is stopped, it will not restart until the controller re-enters in lateral ventilation.
If a low static pressure alarm occurs in tunnel ventilation after the fans were shutoff, the controller automatically goes back to the ventilation level that preceded the fan shutoff and displays the following message on screen: “Min Fan Restart”. Make corrective actions and then access the Alarm Log menu to acknowledge the alarm.
4. If you want the selected fan to run when a particular time clock output is on, select the “Follow Clock” tab with the menu selec- tors and then set parameters below. *This
tab is only accessible if the controller is used in a breeder facility.
Tunn el fan 1 follow clock
Follow clock Low stop T°
2
Stat.Pressure
73.0
Follow clock — Select during the operation of which time clock output you want the selected tunnel fan to run.
Low stop T° — The selected tunnel fan will stop following the time clock output if the room temperature gets too low. Set this se­curity limit to the desired value.
St.tun,clo.side — The “Start tunnel, close side- wall” label indicates the moment at which
the controller switches from lateral to tun­nel ventilation. With this option, there is no gradual transition made from one ventilation
PRO-VISION rev.07
31
PRO-VISION
6.5.4. Tunnel Inlets
The controller can control the opening of 2 tunnel inlets. These inlets either operate as a function of the static pressure level or as a function of temperature. Refer to the Set-up menu in section 4.4 to enable the tunnel inlets and to choose their operating mode.
If 2 tunnel inlets are used, they both follows the same movements. However, both tunnel inlets do not start being used at the same time. The 1st inlet starts being used at the beginning of tunnel ventilation and the 2nd inlet starts at the startup of another user-defined tunnel fan output. Refer to the previous section of this manual to set the moment at which the 2nd tunnel inlet starts being used.
6.5.4.1. Temperature-based Tunnel Inlet
When using temperature-based tunnel inlets, the user must associate an actuator position with the startup of each tunnel fan. This way, when a fan/tunnel fan starts, the inlet opens accordingly. The tunnel inlet starts opening this way at the beginning of tunnel ventilation. The graph below shows how the tunnel inlet opens. Refer to Set-up menu in section 4.4 to enable a temperature-based tunnel inlet.
Pre- opening of the Tunnel Inlet: At the begin­ning of tunnel ventilation, the controller waits for the tunnel inlet to reach half of its pro­grammed position before activating the fans (or waits 30 seconds, whichever is shorter).
1. Select:
Main menu
* Inlets / Vents
* * Tunnel settings
* This menu is accessible if at least 1 inlet is enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
** This menu is accessible if the tunnel inlet’s op­erating mode is set to “T°” in the Set-up menu (see section 4.4).
2. Set the following parameters:
Allow t unnel
Tun nel settings
Stop tun fans o n pre-open?
Yes Yes
Allow Tunnel — Select “Yes” to allow tunnel ventilation or select “N o” to put this ventila­tion mode on standby. *This parameter must be
set separately for each controller program.
Stop tun fans on pre-open? — Some tunnel fans can be used before entering in tunnel ventilation. Select “Yes” to stop these tunnel fans during the pre-opening of the tunnel inlet or select “ No” to let them run during the pre-opening.
Tunnel Inlet Opening as a Function
Tunnel Inlet Opening (%)
of Temperature
3. Press the “Tunnel Opening” tab.
Tun 1 Tun 2 Tun 3 Tun 4 Tun 5 Tun 6
...
Total open tim e
To modify use
Tunnel Opening
0%
5% 10% 15% 20% 25%
...
5:00 M:S
-
4. Set the following parameters:
Tun #x Opening — Associate a tunnel inlet opening (in %) with the startup of each tun­nel fan.
If a tunnel fan is used in lateral ventila­tion, set its tunnel inlet opening to 0% if you don’t want the tunnel inlet to open in lateral ventilation!
Total opening time — Specify the exact time that is required to reach the actuator’s maxi­mum limit switch. The controller will limit the opening of the inlet according to this value. * This parameter is common to all programs.
32
PRO-VISION rev.07
45%
30%
0%
OFF T°
Tun.Fan X,
Tun.Fan X,
The tunnel inlet reaches the position associated with tunnel fan X.
starts)
ON T°
(tunnel vent
OFF T°
Tun.Fan Y
Tun.Fan Y,
The tunnel inlet reaches the position associated with tunnel fan Y.
ON T°
Room T°
PRO-VISION
6.5.4.2. Pressure-based Tunnel Inlets
Opening of the Tunnel I nlet:
If the tunnel inlets are controlled by static pressure, the first inlet start moving accord­ing to the fluctuations in the pressure level when the controller enters in tunnel ventila­tion. It open when the pressure level exceeds the high pressure limit and closes when the pressure level gets lower than the low pres­sure limit. If the second tunnel inlet is used, it start moving the same way at the startup of a subsequent tunnel fan output.
The graph below shows how the tunnel inlet actually moves. Refer to Set-up menu in section 4.4 to enable pressure-based tunnel inlets.
Pre-Opening of the Tunnel Inlet: A pre-opening delay is used to pre-open the first tunnel inlet before activating the tunnel fans. The controller pre-opens the tunnel inlet for the 1st time when the transition from lateral to tunnel ventilation starts and makes another pre-opening at the very beginning of tunnel ventilation (i.e., at the startup of the tunnel fan that asks for sidewall vents to close). In both cases, the controller waits for the end of the pre-opening delay before starting the fans.
Opening of a Pressure-Based
1. Select:
Main menu
* Inlets / Vents
* This menu is accessible if at least 1 inlet is enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
Inlets / Vents
Tunnel Stat. Pressure Inlet Lo 0.05 H i 0.08 L
Wind delay 0:3 0M:S
To modify u se
-
2. Set the following parameters:
Lo/Hi Stat. Pressure — Set the static pressure level below/above which the tunnel inlet must close/open. * This parameter is accessible if the
tunnel inlet operates according to static pressure level (see section 4.4).
Tunnel Inlet
Tunnel
settin gs
Wind Delay — When the pressure level exceeds the high or low static pressure set limit, the tunnel inlet waits for the end of the “Wi nd Dela y” before moving. The high or low pressure condition must be maintained during the whole delay for the tunnel inlet to start moving. This way, the tunnel inlet does not move if a wind draft causes fleeting changes in the pressure level. Set the “Wind Delay” to the desired value. *Note that this parameter is
common to all pressure-based air inlets (sidewall, attic and tunnel inlet).
3. Select the “Tunnel settings” tab with the menu selectors.
Allow T unnel
Tun nel settings
Pre-op ening Pre-op ening 2 Stop tun fans o n pre-open?
Yes 45 sec 45 sec
Yes
4. Set the following parameters:
Allow Tunnel — Select “Yes” to allow tunnel ventilation or select “N o” to put this ventila­tion mode on standby. *This parameter must be
set separately for each controller program.
Pre-opening — Specify how much time is required to pre-open the tunnel inlet at the startup of tunnel ventilation (if no transition is made) or at the startup of the transition from lateral to tunnel ventilation. The controller will pre-open the tunnel inlet before activating the fans at the startup of the tunnel fan that is labeled “Start Tunnel” or “St.Tun,Clo side” (refer to section 6.5.3). * This parameter is accessible if
the tunnel inlet operates according to static pressure level (see section 4.4).
Tunnel inlet
Hi pressure
limit
Tunnel inlet Lo pressure
limit
Static
Pressure
opens
The actuator
The
move
actuator
does not
closes
The actuator
The actuator
starts closing
after the Wind
Delay has
elapsed.
The actuator stops closing
Wind Delay
The actuator starts opening after the Wind
Delay has
elapsed.
The actuator
opening
Wind Delay
stops
Time
Pre-opening 2 — Specify how much time is
required to pre-open the tunnel inlet at the startup of tunnel ventilation (when the transi­tion from sidewall to tunnel ventilation is over). The controller will pre-open the tunnel inlet before activating the fans at the startup of the tunnel fan that is labeled “Close sidewall” (refer to section 6.5.3). If no transition is made, this delay is simply added to the initial pre-opening de lay. * * This parameter is accessible if the tun-
nel inlet operates according to static pressure level (see section 4.4).
Stop tun fans on pre-open? — Some tunnel fans can be used before entering in tunnel ventilation. Select “Yes” to stop these tunnel fans during the pre-opening of the tunnel inlet or select “ No” to let them run during the pre-opening.
PRO-VISION rev.07
33
PRO-VISION

6.6. Stir Fans

The controller has 1 stir fan output that can either be used in minimum ventilation or when the room temperature gets lower than a user-defined limit. Refer to the Set-up menu to enable the desired operating mode of this output (section 4.4).
Stir Fans in Minimum Ventilation: When they are used in minimum ventilation the stir fans only run during the “Of f T ime” portion of the minimum ventilation cycles. This ensures good air circulation when the exhaust fans are not running.
Stir Fans as a Function of Temperature: When they operate as a function of temperature, the stir fans run in timer mode when the aver­age temperature is lower than the output’s “On Temperature” and stop when the room temperature rises and reaches the output’s “Off Temperature”.
Stir Fan as a
Stir Fan
On
Timer
Function of
Temperature
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select the stir fan output. * This output is available if it
has previously been enabled in the Set-up menu (see section 4.4).
3. Set the temperature at which the stir fan output starts (“On Temperature”) and the tem- perature above which the output stops (“Off Tem pe ra tu re” ). Note that the temperature at which the output starts must be lower than the temperature at which it stops.
On/Off Settings
Ite ms
...
Stir
...
Set Point : 75.0
On Off Mode
73.0 74.0 Stirring
...
Htr /fan shut
Off
Off T°
Room T°On T°
Reference Temperature: Operating tempera-
tures of the stir fan output are related to the temperature set point. This means that if the set point changes, the ON and OFF Tempera­tures are adjusted consequently.
Output
Status
ON
OFF
Stir Fan Timer
ON
Time
Cycle
Time
Time
Stir
To modify u se
-
Timer
4. Select the timer tab that is associated with the stir fan output with the menu selectors.
Stir fan timer settings
On Time 0 :30 M:S Cy cle 5:00 M:S
5. Set the “O n Time” and the “Cycle Time” of the stir fan’s timer.
34
PRO-VISION rev.07
PRO-VISION

6.7. Cooling Output

The controller has 6 cooling outputs that can be used to activate various types of cooling devices.
A cooling output starts operating in timer mode when the average temperature reaches its “ON Temperature”. The “ON Tim e” portion of the timer then increases as the tempera­ture rises and reaches its maximum value when the room temperature reaches the “Max Run T°”. The graph below sums up this situation.
of the timer
On Time
ON Time
Output
Status
ON
OFF
ON Time
portion
Max
Min
OFF
Cooling Output
Output Timer
ON
Time
Cycle
Time
ON T° Max Run T°OFF T°
Time
Operating Time Range: The user can specify
a range of time over which the cooling out­puts can run. This allows deactivating them at night for instance.
Reference Temperature: Each cooling/fogger output operates according to the average temperature reading of its respective group of sensors. Refer to section 4.5 to assign these sensors. The operating temperatures of the cooling outputs are also related to the temperature set point. This means that if the temperature set point changes the ON & OFF temperatures of these outputs are adjusted consequently.
Cooling Output in the Egg Room: The con­troller can control a supplementary cooling output in the egg room. This output operates differently from the cooling outputs that are used in the rest of the house. Refer to chap­ter 11 of this manual to get information about the egg room cooling output.
Settings
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
On/Off Settings
Ite ms
...
Cool 1 Cool 2 Cool 3 Cool 4 Cool 5 Cool 6
...
Set Point : 75.0
On Off Mode
...
85.0 84.5
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Cooling
...
Htr /fan shut
Cool 1
Settings
starts must be greater than the temperature at which it stops.
4. Select the “Settings” tab that is associated with the chosen cooling output with the menu selectors.
5. Set the following parameters separately for each cooling output in use:
Cool 1 Settings
Max Run T°
Max On
Start at
95.0
3:00 M :S
6:00 p m
Min On
Cycle
Stop at
1:00 M: S
3:00 M :S
9:00 a m
Max Run T° — Set the temperature at which the cooling output runs continuously (i.e., the “On Ti me” portion of the timer is equal to the “C ycle T ime”). Note that this parameter value must be greater than the temperature at which the output starts.
Min On — Set the “On Time” of the minimum cooling timer.
Max On — Set the “On Time” of the maximum cooling timer. *The Max On Time cannot exceed
the Cycle Time.
Cycle — Set the “C ycle T ime” of the cooling timer. Note that the “Cycle Time” must be longer than the “On Time”.
Start At / Stop At — Specify the period of time over which the cooling outputs can run.
To modify u se
-
2. Use the arrow keys to scroll down and select the desired cooling output. * These outputs are
available if they have previously been enabled in the Set-up menu (see section 4.4).
3. Set the temperature at which each cool­ing output starts running in timer mode (“O n Temperature”) and the temperature below which the output stops (“Off Temperature”). Note that the temperature at which the output
PRO-VISION rev.07
35
PRO-VISION

6.8. Fogger Output

The controller can control 6 zones of Weedon Foggers.
A fogger output starts operating in timer mode when the average temperature reaches its “ON Temperature”. The “O N Ti me” portion of the timer then increases as the temperature rises and reaches its maximum value when the room temperature reaches “Max Run T°” parameter value. The graph below sums up this situation.
of the timer
On Time
ON Time
Output
Status
ON
OFF
ON Time
portion
Max
Regular
OFF
Fogger Output
Output Timer
ON
Time
Cycle
Time
ON T° Max Run T°OFF T°
Time
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
On/Off Settings
Ite ms
...
Fogg 1 Fogg 2 Fogg 3 Fogg 4 Fogg 5 Fogg 6
...
Set Point : 75.0
On Off Mode
...
85.0 84.5
85.0 84.5 Fogger
85.0 84.5 Fogger
85.0 84.5 Fogger
85.0 84.5 Fogger
85.0 84.5 Fogger
...
To modify u se
-
Htr /fan shut
Fogg 1
Settings
2. Use the arrow keys to scroll down and select the desired fogger output. * These outputs are
available if they have previously been enabled in the Set-up menu (see section 4.4).
3. Set the temperature at which each fogger output starts running in timer mode (“On Temperature”) and the temperature below which the output stops (“Off Temperature”). Note that the temperature at which the output starts must be greater than the temperature at which it stops.
4. Select the “Settings” tab that is associated with the chosen fogger output with the menu selectors.
5. Set the following parameters separately for each fogger in use:
Start Age
Min On
Cycle
Stimulate bird
On Time
Fogg 1 Settings
Max Run T°
1
Max On
1:00 M: S
3:00 M :S
Yes
Off Ti me
0sec
65.0
3:00
4:00 H:M
Start Age — Set the animal age at which the selected fogger starts being used.
Max Run T° — Set the temperature at which the fogger output runs continuously (i.e., the
“On Ti me” portion of the timer is equal to the “Cycl e Time” ). Note that this parameter value
must be greater than the temperature at which the output starts.
Min On — Set the “On Time” of the minimum fogging timer.
Max On — Set the “On Time” of the maximum fogging timer. *The Max On Time cannot exceed
the Cycle Time.
Cycle — Set the “C yc le T ime” of the fogging timer. Note that the “Cycle Time” must be longer than the “On Time”.
Stimulate bird — Select “Yes” if you want the fogger output to spray a light fog on the birds at regular interval.
On Time / Off Time — Set the “On Ti me” and the “Off Tim e” of the stimulation timer
Bird Stimulation: To stimulate the birds, the fogger output can spray a light fog at regular intervals (fog timer).
Reference Temperature: The fogger output operates according to the average tempera­ture reading of its respective group of sen­sors. Refer to section 4.5 to assign these sensors. The operating temperatures of this output is also related to the temperature set point. This means that if the temperature set point changes the ON & OFF temperatures of the output are adjusted consequently.
36
PRO-VISION rev.07
PRO-VISION

7. HEATING

Heaters in a breeder, broiler or layer facility:
If the controller is used in a breeder, broiler or layer production, it can use up to 16 heaters. In addition, the PRO-VISION can simulate additional heating outputs with the Hi Fire option. When this option on, the controller doubles the number of heaters in use and each simulated heater (Hi Fire Step) operates as a regular heater, with its own start/stop temperatures, relay selection and selection of sensors. Refer to section 4.4 to activate the Hi fire option.
Heaters in a turkey facility: If the controller is used in a turkey facility, up to 32 indepen­dent heaters can be enabled and each one of them operates with its own start/stop temperatures, relay selection and selection of sensors.
Heater Status
ON
Operating Diagram
of a Heater
0.5°F
differently from the heating outputs that are used in the rest of the house. Refer to chap­ter 11 of this manual to get information about the egg room heating output.
1. Select:
Main menu
* On / Off Settings
* A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select the desired heating output. * These outputs are
available if they have previously been enabled in the Set-up menu (see section 4.4).
On/Off Settings
Ite ms
...
Heat 1 Heat 1 hi Heat 2 Heat 2 hi Heat 3 Heat 3 hi
...
Set Point : 75.0
On Off Mode
73.0 74.5 Heating On
72.0 74.0 Heating O n
73.0 74.5 Heating On
72.0 74.0 Heating O n
73.0 74.5 Heating On
72.0 74.0 Heating O n
...
Htr /fan shut
OFF
T° of
Start T°Stop
heater’s
sensors
Reference Temperature: Operating tempera-
tures of the heaters are defined with respect to the temperature set point and with respect to heater 1: if the set point changes, the on/ off temperatures of all heaters will be adjusted by the same amount and if the On or Off tem­perature of heater 1 changes, the operating temperatures of all heaters will be replaced by the operating temperatures of heater 1.
Heaters in Non-brood Zones: The label “Non- brood” is given to a heater that is located in
an empty zone. The On & Off temperatures of a non-brood heater are related to the non­brood temperature set point. This means that they are automatically adjusted when this set point changes. Refer to section 4.8 for further information about non-brood zones.
Heating Output in the Egg Room: The con­troller can control a supplementary heating output in the egg room. This output operates
To modify u se
-
3. Set the following parameters:
On temperature — Set the temperature below which the selected heater starts. If the Hi Fire option is used, set this temperature separately for both steps of the heating stage.
Off temperature — Set the temperature over which the heater stops. Note that the “Off Temperature” of an heating output must be greater than its “On Temperature”. If the Hi Fire option is used, set this temperature separately for both steps of the heating stage.
Htr/fan shut — This option allows disabling a heating output at any moment. The heater will not run as long as the heater status is set to “Off” in this column.
PRO-VISION rev.07
37
PRO-VISION

8. LIGHTS

8.1. Principle of Operation

The controller has two 0-10V outputs that can be used to control the light intensity. Additional lights can also be connected to the On/Off relays: the on/off lights simply turn on when the 0-10V light output is on. Refer to section 4.4 to enable light programs and refer to section 4.7 to assign the on/off light relays.
Light Programs: The controller can use 9 different light programs containing 6 daily cycles each. The same program is performed every day until another program replaces it (the program selection is made according to the animal age).
Light Cycles: Up to 6 daily light cycles can be performed in the course of a light program. These cycles are used to change the light intensity over the day (see graph below).
Light Peaks: A light peak is a marked increase in the light intensity. They are used to stimu­late the animals. When light peaks are used, they are performed right after the sunrise, at the very beginning of a light cycle and are then performed on a regular basis, according to a user-defined timer.
Intensity
Peak
Intensity
Intensity
0%
Light Cycles
Light
Start Time
Sunrise
Peak
Sunrise
Peak Cycle
Peak
Duration
LIGHT PROGRAM
CYCLE 1 CYCLE 2 CYCLE 3 CYCLE 4 CYCLE 5 CYCLE 6
CYCLE 1
Sunset
Sunset
Stop Time
Time
38
PRO-VISION rev.07
PRO-VISION

8.2. Settings

8.2.1. Light Program Settings
1. Select:
Main menu
* Light Programs
Select a Light Program
* Accessible if the light output is enabled in the Set­up menu (see section 4.4). A password may also be required to access it (see section 4.2 .1).
A graph showing the current status of the ongoing light cycle is displayed along with the light parameters.
2. Set the following parameters:
Make sure you have selected the right light program before adjusting the fol­lowing parameters.
Light Progra m 1
Age
Prog 1
Use Peaks
Sunset
Prog 2
Adjust
Start
Prog 3
CURRENT AG E: 1 PROGRAM: 1 INTENSITY: 50
Prog 4
Prog 5
1
12:00A
Lights 24hr
1
Sunris e
No
# of cycles
30m in
Int ensit y
Cycle 1
Stop
6:00 a m
6
5
4
3
2
8:00A 4:00A 11:59P
30 mi n
100%
6:00 a m
No
Prog 6
6
Prog 7
Prog 8
Prog 9
Peaks
Age — Select the animal age at which the chosen program starts. This value ranges from -5 to 450 days (negative values are used to prepare the house before letting the animals in).
Lights 24hr — Select “Ye s” for the lights to stay lit all day long; select “N o” to use the light cycles.
Use Peaks — Select “Ye s” to use light peaks at regular intervals or select “No” to disable them.
Sunrise — When a cycle starts, the light intensity increases from its minimum to its maximum intensity over this delay (see previous graph). Set the sunrise delay to the desired value (from 0 to 60 minutes). * This
parameter is accessible if the “Lights 24hr” option is disabled.
Sunset — When the stop time of a light cycle is reached, the light intensity gradually decreases from its maximum to its minimum intensity over this delay (see previous graph). Set the sunset delay to the desired value (from 0 to 60 minutes). * This parameter is
accessible if the “Lights 24hr” option is disabled.
Number of Cycles — Select how many cycles must be performed in a light program. It ranges from 1 to 6 cycles. * This parameter is
accessible if the “Lights 24hr” option is disabled.
Adjust — Select the desired light cycle. The following parameters are related to this cycle: * This parameter is accessible if the “Lights 24hr”
option is disabled.
Intensity —Select the light intensity that is reached in the chosen light cycle. * This
parameter is accessible if the “Lights 24hr” option is disabled.
Hint: Use the “AM/PM” key to change the time indicator while adjusting the start & stop time (if applicable).
Start Time — Set the time at which the se­lected cycle starts. Make sure the light cycles do not overlap each other. * This parameter is
accessible if the “Lights 24hr” option is disabled.
Stop Time— Set the time at which the light intensity starts decreasing at the end of the cycle (sunset). * This parameter is accessible if
the “Lights 24hr” option is disabled.
8.2.2. Light Peak Settings
1. Select:
Main menu
* Light Programs
** Peaks
* This menu is accessible if the light output is enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see sect. 4.2.1).
* * This tab is accessible if the “Use Peak” option is enabled in section 8.2.1.
Light peak settings
Adjust
Cycle
Sunris e
Int ensit y
To modify u se
2. Set the following parameters:
Adjust — Select the desired light cycle. All parameters below are related to the chosen cycle.
Enabled — Select “Ye s” to use light peaks during the selected light cycle.
Cycle — Select how much time is required to perform a light peak cycle (see previous graph). Note that the “C yc le T ime” must be even or longer than the “Peak time + Peak Sun- rise + Peak Sunset”.
Peak Time — Select during how much time the light peak intensity must be maintained (from 1 to 120 minutes).
Sunrise / Sunset — Select the duration of the peak sunrise and sunset (see previous graph). These parameters range from 0 to 60 minutes.
Intensity — Set the intensity of light peaks to the desired value. It ranges from the regular light intensity (as defined in previous section) to 100%.
Cycle 1
0:15 H: M
2min
100%
Ena bled
Peak tim e
Sunset
-
No
1min
2min
PRO-VISION rev.07
39
PRO-VISION

9. TIME CLOCKS

9.1. Regular Time Clocks

Time clock outputs used in a breeder production operate differently from the time clocks presented in this section. Refer to next section for more information about time clocks for breeders.
The controller can control 12 time clocks outputs using 8 cycles each. They are used to activate different kind of devices using the real-time clock and can be programmed in two different ways:
1. Clock Loop Feeding Mode — The time clock starts running for the first time when it reaches the “Start Time”. From this moment, the output runs according to a timer that is repeated at a user-defined frequency. *The
clock loop feeding mode is not available in a bree der production.
Time Clock Cycle
in the Clock Loop Feeding
Output Status
On
Off
Run Run Run
Start Time
(e.g. 8h30AM)
2. Start/Stop Mode — The time clock starts when it reaches its “Start Time” and stops at the “Stop Time”. This operating mode is auto-
matically enabled if the clock loop feeding mode is disabled in the Set-up menu.
Output Status
On
Time Clock Cycle
in the Start/Stop Mode
Mode
3 repeats illustrated
Stop Time
(e.g. 3h00PM)
Time
Refer to the Set-up menu to select the proper operating mode for the time clocks (see section 4.4).
1. Select:
Main menu
* On / Off Settings
* *Time clock
*A password may be required to access this menu (see section 4.2.1).
* * This menu is accessible if at least 1 time clock is enabled in the Set-up menu (see section 4.4).
The time clock menu will appear dif­ferently in the breeder mode (see next section).
2. Set the following parameters:
Display — Select the desired clock output. All parameters below are related to the cho­sen output.
Start — Set the time at which each cycle starts. NB. Use the “A M / PM ” key to change the time indicator (if required).
Stop — Set the time at which each cycle stops. The controller automatically adjusts this parameter if the entered value does not allow all clock cycles to be performed the same day. NB. Use the “A M/PM ” key to change the time indicator (if required).
Run — If the output is activated at regular intervals inside the clock cycle, set the run time to the desired value (in hours and minutes). The controller automatically limits the run time so that all clock cycles can be performed the same day (the number of repeats multiplied by the run time must be less than 24h).*Accessible in the clock loop feed-
ing mode only.
Cycle
Display Cycle 1 Cycle 2 Cycle 3 Cycle 4 Cycle 5 Cycle 6 Cycle 7 Cycle 8
Time Clo ck
Run Rep Start
Clk1 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am 0:00 4 6:00am 6:00am
To modify u se
-
Clock Loop Feeding Mode
Display Clock 1
Cycle Start Stop
1 6:00 am 6:00 am 2 6:00 am 6:00 am 3 6:00 am 6:00 am 4 6:00 am 6:00 am 5 6:00 am 6:00 am 6 6:00 am 6:00 am 7 6:00 am 6:00 am 8 6:00 am 6:00 am
To Modify Pre ss
Stop
-
Start/Stop Mode
Off
40
Start Time
(e.g. 8h30AM)
Stop Time
(e.g. 9h30AM)
Time
PRO-VISION rev.07
Rep — If the output is activated at regular intervals inside the clock cycle, set the num­ber repeats to be performed. *Accessible in the
clock loop feeding mode only.
PRO-VISION
9.2. Time Clocks in a Breed­er Facility
In a breeder production, the controller can control 12 time clocks outputs using 4 cycles each. These outputs are used to activate different kind of devices using the real-time clock and they can be enabled on specific days of the week.
A time clock starts when the “Start Time” of a time clock cycle is reached and it stops after a certain run time or at a certain time of day. The following diagrams show both possibilities:
Output Status
On
Off
Clock Cycle in the
Start/Stop Mode
Start Time (e.g. 8h30AM)
Stop Time (e.g. 9h00AM)
Time
1. Select:
Main menu
* On / Off Settings
* *Time clock
*A password may be required to access this menu (see section 4.2.1).
* * This menu is accessible if at least 1 time clock is enabled in the Set-up menu (see section 4.4).
Note that the time clock menu will appear as shown below only if the “Breeder” facility is enabled in the
Set-up menu (see section 4.4).
Time clo ck
Display
Sun Mon Tue Wed Thu Fri Sat
Start
Start
Clock 1
6:00 a m
6:00 a m
Skip da y
Run Ti me
Run Ti me
No
0:00:00
0:00:00
or
Time clo ck
Display
Start
Mon
Start
Start
Clock 1
6:00 a m
6:00 a m
Skip da y
Run Ti me
Run Ti me
2
0:00:00
0:00:00
Start Time — Set the time at which each cycle starts. If 3 cycles are not required, set the “Start & Stop Times” of the unused cycles to the same value or set the “Ru n Time” to 0:00:00. NB. Use the “A M/P M “ key to change the time indicator (if required).
Stop or Run Time — The cycles can either stop at a specific time of day or after a certain run time. Set the time at which each cycle ends. NB. Use the “A M/P M “ key to change the time indicator (if required). *Refer to section 4.4
to choose how the time clocks must stop.
Output Status
On
Off
Clock Cycle in the
Start/Run Mode
Run Time
(e.g. 30m:15s)
Start Time (e.g. 8h30AM)
Time
Note that the “S ta rt/Ru n” mode allows stop­ping the outputs with a little more precision since it allows stopping them by the seconds (contrarily to the “Start/Stop” mode which allows stopping them by the minutes). Refer to the Set-up menu in section 4.4 to choose the desired operating mode of the time clocks (“Start/Stop” or “S tar t/ Ru n”).
2. Set the following parameters:
Display — Select the desired time clock. All parameters displayed below are related to the chosen output.
Skip day — Time clock outputs can either run according to a weekly schedule (7 days) or they can be stopped at regular intervals without considering the day of the week. Select “No” to use the weekly schedule or select the number of days to be skipped after each operating day (1-5 days).
Day of the week — Select on what day of the week the selected time clock is used. *This
parameter is accessible if the “Skip Day” option is set to “No”.
Start Day — Select on what day of the week the time clock schedule starts. *This
parameter is displayed if the “Skip Day” option is enabled above.
PRO-VISION rev.07
41
PRO-VISION

10. WATER LINE FLUSH

The controller can flush 8 water line outputs in turn and can repeat the flushing process up to 4 times a day. Note that 2 water lines can be connected to each water line output.
Water Flush Cycle: When a water flush cycle starts, the controller flushes all water line outputs in turn : after having flushed a water line output, it waits for a certain delay before flushing the lines of the next output. In all, up to 4 cycles can be performed each day.
Make sure all water flush cycles can be performed within the same day (between 12:00am and 11:59pm).
Water Flush Program: A water flush program is the combination of all water flush cycles that are performed in a day. The water flush parameters must be associated with a par­ticular program which starts at a specific age. Using multiple programs is useful to adapt the frequency and the duration of the flushing cycles as the birds are growing. Up to 5 dif­ferent water flush programs can be defined.
Water Flush Cycles & Programs
1 Cycle
Output #1 starts flushing
Duration Interval Duration Interval Duration Interval Duration
Output #2 starts flushing
Output #3 starts flushing
1. Select:
Main menu
* On / Off Settings
* * Water Flush
*A password may be required to access this menu (see section 4.2.1).
* * This menu is accessible if at least 1 water ush
line output is enabled in the Set-up menu (see sec­tion 4.4).
2. Set the following parameters:
Display Skip day
Mon T ue Wed Thu F ri Sat Sun
Start A ge
Interval
Start 1
Start 3
To m odify use
Water Flush
Program1
0:10 H: M
12:00 a m
12:00 a m
Durat ion
1
# of cycles
Start 2
Start 4
-
No
0:10 H: M
4
12:00 a m
12:00 a m
or
Display Skip day
Start
Mon
Start A ge
Interval
Start 1
Start 3
To m odify use
Output #4 starts flushing
Water Flush
Program1
0:10 H: M
12:00 a m
12:00 a m
Durat ion
1
# of cycles
Start 2
Start 4
-
2
0:10 H: M
4
12:00 a m
12:00 a m
Display — Select the desired water flush pro­gram (program 1-5). All parameters below are related to the chosen water flush program.
Skip day — Water flush can either be per­formed according to a weekly schedule (7 days) or they can be stopped at regular intervals without considering the day of the week. Select “N o” to use the weekly schedule or select the number of days to be skipped after each operating day (1-5 days).
Start Day — Select on what day of the week the water flush schedule starts. *This
parameter is displayed if the “Skip Day” option is enabled above.
Start Age — Select the age at which the selected water flush program starts.
Day of the Week — Select on which days of the week the water flush program must be performed. *This parameter is accessible if the
“Skip Day” option is set to “No”.
Duration — Specify the amount of time re­quired to flush one (1) water line output. The duration of water flushes is the same for all water line outputs.
Inter val — After having flushed a water line output, the controller waits for this time delay before flushing the water lines of the next output. Note that this delay is common to all water line outputs.
Number of cycles — Select the number of daily flush cycles that must be performed in the course of the selected program (1 to 4 cycles per day).
Start 1-4 — Select the start time of each water flush cycle. NB. Use the “A M /PM “ key to change the time indicator (if required).
Make sure all water flush cycles can be performed within the same day (between 12:00am and 11:59pm).
42
Cycle #1 Cycle #2 Cycle #3 Cycle #4
1 Program
PRO-VISION rev.07
PRO-VISION

11. EGG ROOM OUTPUTS

If it is used in a breeder facility the controller automatically enables an egg room and con­trols the ambient temperature and humidity level of in it with its 3 egg room outputs (egg room cooling, heating and humidity outputs). Refer to the Set-up menu in section 4.4 to select in what type of facility the controller is located (breeder, broiler, layer or turkey).
When the egg room is used, the PRO-VISION also keeps a tally of the number of eggs pro­duced each day (the egg tally includes the daily count of produced, cracked and floor eggs as well as the daily average egg weight) and finally allows setting the time clocks with a weekly schedule. Refer to section 14.4 to access the egg count menu and refer to sec­tion 9.1 to set the egg room time clocks.
Reference Temperature: All egg room outputs operate according to the egg room tempera­ture. Refer to section 4.5 to select which temperature sensors are located in this room.
Relative Humidity in the Egg Room: If the egg room is enabled and the controller uses a relative humidity (RH) sensor, the RH sensor must be located inside the egg room.
Egg Room Heating Output: The controller can control 1 heating output in the egg room. This output starts when the egg room temperature gets lower than its “On Temperature” and stops when the egg room temperature reaches its “Off Temperature”.
Output
Status
On
Off
Heater in the
Egg Room
On T°
Off T°
Egg
room T°
Egg Room Cooling Output: The controller can
control 1 cooling output in the egg room. This output starts when the egg room temperature reaches its “On Temperature” and stops when the egg room temperature gets lower than the its “Off Temperature”.
Output Status
On
Off
Cooling Output in the
Egg Room
Off T°
On T°
Egg
room T°
Egg Room Humidity Output: The controller
can control 1 relative humidity (RH) output in the egg room. This output starts when the RH level in the egg room gets lower than its “On RH level” and stops when the RH level reaches its “Off RH level”.
Output
Humidity Output in the
Status
On
Off
On Level
Egg Room
Off Level
Egg
room RH
Level
1. Select:
Main menu
* On / Off Settings
**Egg room
* A password may be required to access this menu (see section 4.2.1).
* * This menu is accessible if the breeder mode is enabled in the Set-up menu (see section 4.4).
Egg roo m
Ite ms Start Stop Se nsor
Heat 74.0°F 75.0°F Sensor 1
Cool 74.0°F 75.0°F Sensor 1 RH 74.0°F 75.0° F
To modify u se
2. Set the following parameters:
Heat On/Off temperatures — Set the tem­perature below which the egg room heating output starts and above which it stops. Note that the “Off Temperature” must be greater than the “On Temperature”.
Cool On/Off temperatures — Set the tempera­ture at which the egg room cooling output starts and below which it stops. Note that the “Off Temperature” must be lower than the “On Temperature”.
On/Off humidity levels — Set the relative humidity level at which the egg room humid­ity output starts and below which it stops. Note that the “Off RH level” must be lower that the “On RH level”. * This output is acces-
sible if the RH Sensor is enabled in the Set-up menu (see section 4.4.).
Sensor — Select which temperature sensor is used to control the egg room heating & cooling outputs. Note that the same sensor can be used to control both outputs.
PRO-VISION rev.07
43
PRO-VISION

12. RELATIVE HUMIDITY (RH) COMPENSATION

The controller can automatically adjust the value of certain parameters as a function of the relative humidity (RH) level. This section explains how each RH compensation function works and how to program them.

12.1. High RH Comp.on the Min Vent. Timer

The controller can compensate for a high humidity levels by increasing the level of mini­mum ventilation. As the RH level rises, the controller increases the “On Time” portion of the minimum ventilation timer to compensate for the change. The maximum compensated “On Ti me” is reached when the RH level is 10% above the RH set point.
Refer to section 5.1 to adjust the RH set point and refer to the Set-up menu in section 4.4 to enable this RH compensation method (“Use RH min vent. compensation”).
On Time of
the Min
Vent. timer
Compen-
sated
On Time
Regular
On
Time
Off
RH Compensation on
Minimum Ventilation
Time
Added
10%
RH Set Point
RH Level
(%)
The relative humidity compensation func­tions are only available if the controller is used in a broiler, layer or turkey facility (in a breeder facility, the RH sensor is used to control a humidity output in the egg room).
1. Select:
Main menu
* Minimum Ventilation
**Compens
*A password may be required to access this menu (see section 4.2.1).
* * This menu is accessible if the “Use RH min vent. compensation” option is enabled in the Set-up menu (see section 4.4).
RH add min v entilation 0 :15
To modify use
Compensation
-
2. Set the following parameters:
RH add min ventilation — Select the maxi­mum amount of time that can be added to the “On Time” portion of the minimum ven­tilation timer.

12.2. High RH Comp. with Heaters in Min Vent.

The controller can compensate for high hu­midity levels, during minimum ventilation, by activating the heaters in timer mode. As the RH level increases, the controller increases the “O n Ti me” portion of the heating timer to compensate for the change. The maximum compensated heating “On T ime” is reached when the RH level is 10% above the RH Set Point.
On Time of the heat timer
Maximum
On Time
Minimum
On Time
Off
The RH heat timer is composed of an “On Tim e” and of a “Cyc le Tim e”. The heaters run during the “On Tim e” and then stop until the end of the “Cycle Time”. The “On Tim e” portion of this cycle increases as the RH level increases.
Output
Status
RH Comp. with
Heating Outputs
10%
RH Set Point
RH Heat Timer
RH
Level (%)
44
PRO-VISION rev.07
ON
OFF
ON Time
Cycle
Time
Time
Refer to section 5 .1 to adjust the RH set
PRO-VISION
point and refer to the Set-up menu to enable this RH compensation method (“Use heater RH compensation” parameter in section 4.4).
1. Select:
Main menu
* On / Off Settings
*A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select any heating output.
On/Off Settings
Ite ms
...
Heat 1 Heat 1 hi Heat 2 Heat 2 hi Heat 3 Heat 3 hi
...
Set Point : 75.0
On Off Mode
73.0 74.5
72.0 74.0 Heating
73.0 74.5 He ati ng
72.0 7 4.0 H eat in g
73.0 74.5 He ati ng
72.0 7 4.0 H eat in g
...
To modify u se
-
Htr /fan shut
Heat
Compens
3. Select the “Heat Compens” tab with the menu selectors. * T his tab is accessible if the Use heat er RH
compensation” option is enabled in the Set-up menu (see section 4.4).
Heater RH Compensation
Min On
Cycle
0:15 M:S
5:00 M:S
Max On
0:45 M:S

12.3. RH Comp. with Cooling & Foggers

Low RH Compensation: The controller can
compensate for low humidity levels by acti­vating the cooling outputs and/or foggers in timer mode. The cooling output/fogger start being used for this purpose when the RH level falls below a user-defined level.
High RH Compensation: The controller can compensate for high humidity levels by stop­ping all cooling outputs. When this RH com­pensation mode is used, all cooling outputs stop when the RH level reaches the RH set point. Refer to section 5.1 to adjust the RH set point. *T his compensation does not apply to foggers.
1. Select:
Main menu
* On / Off Settings
*A password may be required to access this menu (see section 4.2.1).
2. Use the arrow keys to scroll down and select
any cooling output or fogger. * These outputs are
available if they have previously been enabled in the Set-up menu (see section 4.4).
Ite ms
...
Cool 1 Cool 2 Cool 3 Fogg 1 Fogg 2 Fogg 3
...
On/Off Settings
Set Point : 75.0
On Off Mode
...
85.0 84.5
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Foggin g
85.0 84.5 Foggin g
85.0 84.5 Foggin g
...
Htr /fan shut
Cool 1
Settings
Cool 1 / Fogg 1 Settings
Coo l shuto ff
On Time
To modify use
0:30 M: S
85
Low RH
Off Ti me
-
40
2:00 M: S
4. Set the following parameters. Note that the RH compensation settings are common to all cooling outputs (same for foggers):
Cool Shutoff — Set the humidity level above which the cooling outputs must stop being used. * This parameter is accessible if the “RH
shutoff cooling” option is enabled in the Set-up menu (see section 4.4) and doe s not apply to foggers.
Lo RH— Set the humidity level below which the cooling outputs/foggers must start run­ning in timer mode. * T his parameter i s accessible
if the “Activate cooling on low RH” or “Activate foggers on low RH” option is enabled in the Set-up menu (see section 4.4).
On & Off Times — Set the “On & Off Times” of the Lo RH timer. *T hese paramete rs are accessible
if the “Activate cooling on low RH” or “Activate foggers on low RH” option is enabled in the Set-up menu (see section 4.4).
To modify u se
-
4. Set the following parameters:
Heat Min/Max On — Set the minimum and maximum “On Ti me s” of the RH heat timer.
Cycle Time — Set the “Cycle Time” of the RH heat timer.
To modify u se
-
3. Select the “Cool /Fogg #x Settings” tab with the
menu selectors.
PRO-VISION rev.07
45
PRO-VISION

13. ALARMS

When an alarm occurs, the Alarm pilot light turns red and the alarm condition is posted to the alarm log menu. The table on the right gives a list of all possible alarm conditions.
Another alarm situation occurs when power to the controller fails. In this case, the alarm relay is activated. When the alarm relay is activated, the normally open contact ( ) closes.
Backup Thermostat Warning: Each time the Set Point changes of
4.0°F (2.2°C), the controller displays a reminder asking to adjust the backup thermostats. Press any key to make this warning disappear.
Alarm Conditions
Low temperature alarm
High temperature alarm
Critical temperature alarm
Low static pressure (P.E.) alarm
High static pressure (P.E.) alarm
Sensor #x defective
Outside sensor defective
Static pressure (P.E.) sensor defective
Relative humidity (RH) sensor defective
Breaker Hi temperature alarm
Feeder #x run time exceeded
Water Meter #x Spill
Amp draw alarm
Min fan restart (see section 13.2.6)
Empty zone alarm

13.1. Alarm Log

The alarm log displays a list of the 75 most recent alarm events.
1. Select:
Main menu
Alarms
Alarms
Alarm Log
Alarms Value Time Date Hi T° 0.0 10:00P Jan 1 08
T ° / S.P.

13.2. Temperature Alarms

13.2.1. High/Low Temperature Alarms
When the average room temperature exceeds the high temperature alarm setting, a high temperature alarm is declared; likewise, a low temperature alarm is declared when the average room temperature falls below the low temperature alarm settings. Although these settings are entered by the user as ab­solute values, they are defined based on the temperature set point which mean they are adjust automatically if the set point changes.
Detection of
Alarm Limits
Hi T° limit
Set
Point
Lo T° limit
13.2.2. Temperature Alarms in Clean Mode
The controller can monitor low temperature alarms when it operates in clean mode. If this low temperature alarm condition is used, the controller sets off an alarm when the ambient temperature falls below the clean mode’s low temperature alarm limit. *Note that this alarm
limit is related to the non-brood set point, which means it automatically adjusted if the non-brood set point changes.
Temperature Alarms
Hi T° alarm
Room T°
46
PRO-VISION rev.07
PRO-VISION
13.2.3. Outdoor Temperature Com­pensation
The outside temperature probe can be used to prevent false temperature alarms that are due to warm weather conditions. When the out­side temperature is already warmer than the high alarm limit, the controller automatically changes the high temperature alarm limit. The high limit becomes the Outside Temperature + T° Comp Offset. In other words, when the outside temperature is too high, the high temperature alarm is only set off if the zone temperature exceeds the outside temperature by more than X degrees (X being the offset value). The graph below illustrates this situation.
Room temperature
Critical T°
High T°
alarm
limit
Outdoor T° Compensation on Temp. Alarms
Legend
Critical alarm limit
High T° alarm
Offset
High Alarm = Inside T° > Outside T° + Offset
limit
Alarm limits
Outside temperature
Temperature alarm
No alarm
Outside temperature offset (no alarm)
Critical Temperature:
The critical temperature is the absolute maximum temperature allowed in a zone. No matter what the outside temperature is, the zone temperature must never exceed the critical temperature.
13.2.4. Temperature Alarm Settings
1. Select:
Main menu
Alarms
* T°/S.P.
*A password may be required to access this menu (see section 4.2.1).
Tempe rature / S.P. alar m settings
Low T°
Tun high T°
T°C om p.Off set
Based on
Sensor bad T°
70.0
90.0
5.0
AvgT°
20.0
High T°
Crit ical T°
Non brood
Breaker T°
8 7.0
95.0
32.0
12 0.0
Low T°
alarm
limit
from 0.5°F to 60°F (0.3°C to 33.3°C) above the set point.
Critical T° — Set the absolute temperature at which a critical temperature alarm must set off. Note that this alarm limit can also be adjusted automatically with time. Refer to the following section to get further information about the critical temperature ramp. * This parameter is
accessible if the critical alarm condition is enabled in the Set-up menu (see section 4.4).
T°Comp. Offset — The offset is the number of degrees the ambient temperature can rise above the outdoor temperature without setting off an alarm.
Non brood — Set the temperature below which a temperature alarm is set off in an empty zone and during the clean mode.
Low T° alarm limit
Time
Breaker T° — If the controller monitors the
temperature of the main breaker, select the temperature at which it must set off an alarm. * This parameter is accessible if the breaker’s tem-
perature monitoring function is enabled in the Set-up menu (see section 4.4).
Sensor Bad T° — The controller can trigger an alarm if a temperature sensor gets defec­tive (i.e. if the sensor reading becomes out of range). Select the number of degrees above and below the average temperature that signals the presence of a bad sensor.
2. Set the following parameters:
Low /High T° — Select the room temperature below and above which a temperature alarm must set off.
Tun high T° — Set the room temperature at which a high temperature alarm sets off in tunnel ventilation. This alarm limit ranges
Based on — Select “Av g” if you want tempera­ture alarms to be triggered when the average temperature gets out of range or select “Ind. sensor” if you want them to be triggered when the reading of a single probe that takes part in the average temperature reading gets out of range.
PRO-VISION rev.07
47
PRO-VISION
13.2.5. Critical Temperature Ramp
The controller can automatically change the critical temperature alarm limit over time with a three-step ramp. Each step specifies associates a critical temperature alarm limit with an animal age. Once the steps are defined and the ramp is activated, the controller changes the critical alarm limit in a linear fashion between consecu­tive steps of the ramp. When the last step is reached, the controller keeps using the alarm limit associated with it until a new flock starts.
Critical Alarm Limit (°F)
Critical
Temperature Ramp
105
85
78
d1
1. Select:
Main menu
Alarms
* Ramping
* This menu is accessible if the outside temperature sensor is enabled in the Set-up menu (see section
4.4). A password may also be required to access it (see section 4.2.1).
Ram ping Status: Off
Age Critical T°
1 1 00.0° F
20 9 0.0°F
40 8 0.0°F
2. Set the following parameters. *The param­eters below are common to all programs.
Critical Alarm Ramp — This is the status of the alarm ramp. Prior to activating the ramp, make sure the parameters below are set properly.
Age — Set the age at which each step starts. The age ranges from -5 to 450 days (negative values are used to prepare the house before letting the animals in).
Critical T° — Assign a critical temperature alarm limit with each step of the ramp.
d25 d50 Days
13.2.6. Static Pressure Alarms
The controller can set off an alarm when the static pressure (S.P.) level exceeds the high or low pressure alarm limit for a certain period of time.
• Low Static Pressure Alarm: When a low pressure alarm occurs, the controller switches on the alarm relay and the low SP fan.
The Low Pressure alarm is not moni­tored while the controller is in natural ventilation.
Low Static Pressure Alarm in Minimum Ventilation: In minimum ventilation, the con-
troller only monitors the low pressure alarm condition while the fans are running (i.e., during the “On Tim e” portion of the minimum ventilation cycle).
High Static Pressure Alarm:
When a high static pressure alarm occurs the controller switches on the alarm relay and brings proper corrective actions (see below). This type of alarm ends when the pressure level gets back in the normal pressure range and after being acknowledged by the user.
- If the high pressure alarm occurs during lateral ventilation, the controller opens all air inlets (sidewall vent, attic vent and tunnel inlets) and lets them open continuously until the pressure level gets back in the acceptable pressure range.
- If the high pressure alarm occurs while be­ing in natural ventilation, the controller stops all the fans for 1 minute, makes the natural curtains open for 1 minute and makes them go back to their normal opening afterwards.
• Min Fan Restart:
If a low static pressure alarm occurs in tun­nel ventilation after the fans were shutoff, the controller automatically goes back to the ventilation level that preceded the fan shutoff and displays the following message on screen : “Min Fan Restart”. Make corrective actions and then access the Alarm Log menu to acknowledge the alarm.
1. Select:
Main menu
Alarms
* T°/S.P.
*A password may be required to access this menu (see section 4.2.1). In addition, this menu is only accessible if the controller uses the sidewall and/ or tunnel ventilation modes (i.e., if at least 1 fan or tunnel fan is enabled in the Set-up menu).
Tempe rature / S.P. alar m settings
L ow S. P.
Low Tu n
Low SP Fan
To Modify Press
0.00 ”W C
0.01” WC
None
H ig h S.P.
S.P D e la y
-
0.20 ”W C
1:00M :S
2. Set the following parameters:
High / Low S.P. — Set the pressure levels below and above which an alarm is declared. * These parameters are accessible if a static pres-
sure sensor is enabled in the Set-up menu (see section 4.4).
S.P. Delay — The high or low pressure condi­tion must be maintained all along this period of time for the controller to set off the alarm. Set the static pressure alarm delay to the desired value. The S.P. Delay ranges from 0 to 15 minutes * This parameter is accessible if a
static pressure sensor is enabled in the Set-up menu (see section 4.4).
Low Tun — Set the pressure level below which a low pressure alarm must set off when the controller is in tunnel ventilation. * This
parameter is accessible if a pressure-based tunnel inlet is enabled in the Set-up menu (see section 4.4).
Low SP Fan — Select which fan must be ac­tivated in case of a low pressure alarm (or se­lect “None” to disable this security function).
48
PRO-VISION rev.07
PRO-VISION
13.2.7. Water Spill Alarms
A water spill alarm is declared when the water consumption exceeds the acceptable limit. This limit ranges from 0.0 to 10 000.0 gallons or liters per 15 minutes.
The controller can also adjust the water spill limit of each water meter automatically as the animals are growing. The water spill alarm limit changes in a linear fashion between 2 user-defined steps: the first step being the maximum water consumption allowed at day 0 and the second step being the maxi­mum consumption at the “End Age”.
Water Spill
(gal/15 min)
End
meter x
Start
meter x
Limits
Water Spill
Alarm Limit
Day 0
End Age
Age
(days)
1. Select:
Main menu
Alarms
* Water
*This menu is accessible if at least 1 water meter in enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see sec­tion 4.2.1).
Water spill alarm settings
Start meter 1 Start meter 2 End meter 1 End meter 2 End Age
5.0g /15 m
5.0g /15 m
25.0 g/1 5m
25.0 g/1 5m 5
2. Set the following parameters. *The param-
eters below are common to all programs.
Start meter 1-2 — Set the maximum amount of water that can be consumed per 15 min­utes for the birds at the beginning of the flock. Set this parameter separately for each water meter in use. It ranges from 0.0 to 10 000.0 gallons (or liters).
End meter 1-2 — Set the maximum amount of water that can be consumed per 15 minutes for the birds at the end of the flock. Set this parameter separately for each water meter in use. It ranges from 0.0 to 10 000.0 gallons (or liters).
End Age — Select the age at which the flock ends. When it is reached, the controller keeps using the water spill alarm limit defined for that day until a new flock begins. * This pa-
rameter is common to both water meters.
13.2.8. Feeder Alarms
The controller can declare an alarm if a feeder runs continuously for a too long period of time. When this type of alarm occurs, the relay associated with the problematic feeder opens in order to stop the feeder motor.
1. Select:
Main menu
Alarms
* Feeders
* This menu is accessible if a feeder is enabled in the Set-up menu (see section 4.4). A password may also be required to access it (see section 4.2.1).
Feed monitoring: No
Fe ed Ma x time Send alarm Restart
Feed 1 0:10 H:M Yes No
Feed 2 0:10 H:M Yes No
Feed 3 0:10 H:M Yes No Feed 4 0:10 H:M Yes No
Feed monitoring — Select “Yes” to enable the feeder monitoring function.
Max Run Time — Set the maximum run time of each feeder separately.
Send alarm — Select “Ye s” for an alarm to set off when the run time of a feeder exceeds its respective maximum time.
Restart — When a run time alarm occurs, the controller opens the relay associated with the feeder input or stops a specific clock output to make the feeder motor stop. Select “Yes” to restart the feeder motor after a run time alarm has occurred.
PRO-VISION rev.07
49
PRO-VISION
13.2.9. Amperage Draw Alarms
If current sensors are used, the controller can set off an alarm if the amperage draw of an output gets out of range.
1. Select:
Main menu
Alarms
* Amp draw
* This menu is accessible if at least 1 relay uses a current sensor. A password may also be required to access it (see section 4. 2.1).
A table containing all outputs that are using a current sensor is displayed. Refer to section
4.7.2 to specify what relays are using this type of sensor.
Amp d raw alarm
Ite m Minimum Maximum
Heaters 1.0A 5.0A Fan 1.0 A 5.0 A Tun Fan 1.0 A 5.0A Cooling 1.0A 5.0A Stir 1.0A 5.0A Time clo ck 1.0A 5.0 A Light 1.0 A 5.0 A Wtr line 1.0A 5.0 A Backup 1.0 A 5.0 A Side wall 1.0 A 5.0 A Tu n inlet 1.0 A 5.0 A Att ic 1.0A 5.0 A Eg.C oo l 1.0 A 5.0 A E g.Ht r 1.0A 5.0A
Eg. RH 1.0 A 5.0A
To modify use
-
Minimum / Maximum — Select the acceptable amperage draw range for each output that uses a current sensor.1
50
PRO-VISION rev.07
PRO-VISION
14. MONITORING FUNC­TIONS

14.1. Current Conditions

14.1.1. Current Condition Screen
Saver
The current condition screen saver gives a quick overview of the actual conditions in the barn. This screen is automatically displayed after 5 minutes of inactivity and shows the basic conditions in the room: temperature, static pressure level, humidity level and light intensity.
7 7. 5
75 %
Main men u, press any key
0.06
100 %
14.1.2. Current Input/Output Status
1. Select:
Main menu
Current conditions
The controller displays the current reading of each input along with other useful information such as temperature and heater run times.
It is also possible to refine this screen display by removing some pieces of information from it, such as the individual reading of the temperature sensors and the run time of the heaters. Refer to the Set-up menu in section
4.4 to modify the information displayed on the current condition screen.
Current Conditions
Set Point Avr temp. Out Tem p. Attic T°
75.2°F 77.5°F 80.0°F 57.7°F
75.3 75.1 74.7 74.9 75.0 75.6
74.4 75.0
Age Hum idit y S .P. Water Tot 5 75% 0.06"WC 7.3 gal
0:00 0:00 0:0 0 0:00 0:00 0:00
0:00 0:00 0:00 0:00 0:00 0:00
Am monia Wind spd 0pp m 0ft/mi n
Temperature Sensors
Today's heater run time
Hi Hi
Hi Hi
Hi Hi
Output Status
2. Select the “Output Status” tab with the menu selectors. A table containing the status of each output is displayed.
Output St atus
Heat
HiFi
Fan
Tun
Stir
Cool
Clk
Feed
Wtr
SV
Tun
Below is a table showing the meaning of all possible output status.
Display Meaning
Heat
HiFi
Fan
Tmr
Tun
Tmr
Stir
Cool
Clk
Feed
Wtr
SV
AV
Tun
Tun2
Nat
Nat2
Htr
Cool
RH
1-32 ( )
1-16 ( )
1-20 ( )
1-20 ( )
Heater #x is active.
Hi Fire Heater #x is active.
Fan #x is active.
1-5 ( )
Fan #x runs in timer mode.
1-5 ( )
Tunnel fan #x is active.
Tunnel fan #x runs in timer mode.
Stir fan is active.
( )
Cooling output #x is active.
1-6 ( )
Time clock #x is active.
1-8 ( )
Feeder #x run time monitoring re-
1-4 ( )
lay is closed (no run time alarm)
Water flush output #x is active.
1-8 ( )
The sidewall vent is closing/
/ ( )
opening
The attic vent is closing/opening.
/ ( )
Tunnel inlet 1 is closing/opening.
/ ( )
Tunnel inlet 2 is closing/opening.
/ ( )
Natural curtain 1 is closing/opening
/ ( )
Natural curtain 2 is closing/opening
/ ( )
Egg room heating output
( )
Egg room cooling output
( )
Egg room humidity output
( )
PRO-VISION rev.07
51
PRO-VISION

14.2. History Menus

The history menus provide a daily record of the house conditions. The information con­tained in these menus is logged at midnight everyday.
1. Select:
Main menu
History
2. By default, the controller displays the aver­age temperature history at first. Use the menu selector to select the desired type of history:
Average — This menu contains the daily mini­mum and maximum readings of the average temperature of the past 400 days (or since the beginning of the flock).
T° Sensors — This menu contains the daily minimum and maximum temperature readings of each inside & outside temperature sensors of the past 7 days.
RH — This menu contains the daily minimum and maximum relative humidity readings of the past 400 days (or since the beginning of the flock). * This history menu is accessible if a
humidity sensor is enabled in the Set-up menu (see section 4.4).
S.P.— This menu contains the daily minimum and maximum static pressure readings of the past 400 days (or since the beginning of the flock). * T his history menu is accessible if a static
pressure sensor is enabled in the Set-up menu (see section 4.4).
Heaters — This menu contains the daily run time of each heating output of the past 400 days (or since the beginning of the flock)
Feeders — This menu contains the daily run time of each feeder of the past 400 days (or since the beginning of the flock). * This history
menu is accessible if a feeder is enabled in the Set-up menu (see section 4.4).
Wat er— This menu contains the daily water consumption of each water meter of the past 400 days (or since the beginning of the flock). Press the “Water/15M” tab inide the Water History menu to display today’s water
Histor y
Average
Sensor
RH
S. P.
Heaters
Average Temperature
Age Minimum Maximum
10 12:00:00 am 0.0 12:00:00 am 0.0 9 1 2:00:00 am 0.0 1 2:00:00 am 0.0 8 1 2:00:00 am 0.0 1 2:00:00 am 0.0 7 1 2:00:00 am 0.0 1 2:00:00 am 0.0 6 1 2:00:00 am 0.0 1 2:00:00 am 0.0 5 1 2:00:00 am 0.0 1 2:00:00 am 0.0 4 1 2:00:00 am 0.0 1 2:00:00 am 0.0 3 1 2:00:00 am 0.0 1 2:00:00 am 0.0 2 1 2:00:00 am 0.0 1 2:00:00 am 0.0 1 1 2:00:00 am 0.0 1 2:00:00 am 0.0
Feeders
Water
Mo rtal.
consumption per 15 minutes.* These history menus are accessible if a water meter is enabled in the Set-up menu (see section 4.4).
Mortal — This menu contains the daily number of mortalities recorded in the past 400 days (or since the beginning of the flock).

14.3. Animal Age & Count

Animal Age: Some parameters of the control-
ler can automatically change over time as the animals grow up (temperature ramps, light programs, etc.).
Animal Count & Mortality: In order to keep the animal count, you must first specify the initial number of animals at the beginning of a flock. You must then update the animal count when mortality occurs.
1. Select:
Main menu
* Start Flock
* A complete-access password may be required to access this menu (see section 4.2.1).
On top of the “Start ock” menu are some information about the current breeding (total number of mortalities, # of remaining birds and loss rate). These values are displayed as a reference only and cannot be modified.
2. Set the following parameters:
Start Flock — Before starting a new flock, make sure the number of birds placed is set properly.
ALL information contained in the history menus of the controller are reset when a new flock starts.
Age — The animal age ranges from -5 days to 450 days. Negative day values are used to prepare the house before letting the animals in.
Nb Birds — Specify the initial number of birds.
New Mortality — Enter the number of mortali-
ties. Once it is validated, the value automati­cally goes back to “0” and the is added to the “Morta lit y” count and removed from the “Remaining” count. Use the +/- key to enter a negative value in case a mistake is made.
Start flock
Mortality
Loss (%)
Stat Flo ck
Age
Clean M ode
Use min.vent?
To modify u se -
0
0.00
No
1
Yes
No
Remaining
Program
Age
Nb Birds
New Mortality
Alarm low T°?
10000
Progra m 1
10000
0
No
52
PRO-VISION rev.07
PRO-VISION

14.4. Egg Count

If it is used in a breeder facility, the controller offers an egg count menu. Refer to the Set-up menu in section 4.4 to select in what type of facility the controller is located (breeder, broiler, layer or turkey).
1. Select:
Main menu
* Start Flock / Eggs
* *Egg Count
* A complete-access password may be required to access this menu (see section 4.2.1).
* This tab is accessible if the “Breeder” application is enabled in the Set-up menu (see section 4.4.).
Egg c ount
Count
Cracked
Weight
Floor
Other
To modify u se
Yesterday 0
0
Yesterday 0
0
Ye ste rd ay 0.0 oz
0.0o z
Yesterday 0
0
Yesterday 0
0
-
14.5. Operation Costs & Cur­rent Consumption
If there are current sensors on some of the controller outputs, the PRO-VISION can dis­play the operation cost and amperage draw of these outputs. Refer to section 4.7 to assign a current sensor to a relay.
1. Select:
Main menu
History
2. Select the “Actual Current” tab with the
menu selectors to display the amperage draw of all the outputs that are using a current sen­sor. * This tab is accessible if at least 1 relay uses a
current sensor and if this relay is actually assigned to an output (see section 4.7).
Actual curre nt draw
He at 1 0.0A
Fa n 1 0.0A
T un 1 0.0A
...
3. Select the “Operation Cost” tab with the
menu selectors to see operation cost calculat­ed for each output that uses a current sensor.

15. UPDATE & BACKUP

The PRO-VISION can read and write on standard USB memory cards which makes it easy to create a backup of you controller or to upload a new configuration in it. Note that once your system’s configuration is saved on a memory card, it can then be transferred on a home computer, palm pilot or it can be up­loaded in another controller of the same type.
NO USB memory card is provided with the system. You can purchase one in any good electronic store.
Connecting the Memory Card: Open the latches and lift the cover. Now, insert the USB card in the USB connector located on the electronic board inside the enclosure.
On the left hand side of the screen are today’s egg count values. Update these values as required. On the right hand side are yester­day’s values. These values are displayed for comparison purposes only, they cannot be modified.
Ope ration co st
Ite ms Today Total
H eat 1 0.00 $ 0.0 0$ Fan 1 0.0 0$ 0.00$ Tun 1 0.00 $ 0.00 $
...
The total cost recorded since the beginning of the flock is also displayed. Note that the operation cost is determined as a function of the run time of the output and as a function of the electricity rates. Please refer to the Set-up menu in section 4.4 to specify the current electricity rates. * This tab is acce ssible if
at least 1 relay uses a current sensor and if the relay is assigned to an output (see section 4.7).
USB connector
Configuration Files (*.pkg): The controller only recognizes the configuration files with the *.pkg extension. In addition, the files must be located at the root of the USB mem­ory card otherwise, the controller will not see them (it cannot access any sub-directory). In order to erase or rename a configuration file, you must access your USB memory card via a computer (or palm pilot).
Furthermore, when uploading one of these files in the control, it is possible to upload only 1 of its 2 components: the software or the parameters settings. It is thus possible to upgrade your controller without loosing your parameter settings for instance.
PRO-VISION rev.07
53
PRO-VISION
1. Select:
Main menu
* Set-up
Update
* A complete-access password may be required to access this menu (see section 4.2.1).
Upd ate
PRO-VISION~1.pkg
PRO-VISION~2.pkg PRO-VISION~3.pkg
Select file t o install
Upd ate
Soft
Upd ate
all
Upd ate
Settings
Save all

16. DIAGNOSTIC

The diagnostic menu allows testing the con­troller’s hardware.
1. Select:
Main menu
* Set-up
Diagnostic.
* A complete-access password may be required to access this menu (see section 4.2.1).
Activate LED Activate LCD Test Activate Alarm relay Activate output relay Activate 0-10V test 0-10V 1 output value 0-10V 1 output reading 0-10V 2 output value 0-10V 2 output reading Com munication in use x%
To modify use
Diag nostic
-
2. Activate the desired hardware test:
No No No No No No No No No
80%
2. Making a backup:
Press the “Save All” tab in order to save your PRO-VISION software and parameter set­tings on the USB card. Each time you make a backup of your control, the controller creates a new PRO-VISION~X.pkg file at the root of the memory card. If this file name already exists, it will be saved under a different name (“PRO-VISION~1.pkg” for instance). This way, the controller will never erase a file on the card.
3. Loading new settings and/or software:
In order to load a new software and/or param­eter settings, select the desired configuration file from the scrolling list and then select the proper “Update” tab with the menu selector. Here are the different possibilities:
The PRO-VISION can only read the files located at the root of the USB memory card. It cannot access any sub-directory!
Activate LED — Use this function to test both colors of the alarm LED.
Activate LCD Test — Use this function to test the LCD screen.
Activate Alarm relay — Use this function to test the alarm relay.
Activate output relay — Type in the relay number associated with the output you want to test or type “0” to end this test.
Activate 0-10V test — Select “Yes” to enable the 0-10V test.
0-10V #x output value — Assign the desired voltage to the 0-10V output. The actual 0-10V reading is displayed below. If the assigned value does not match the output reading, make sure there is no electrical noise on the output and make sure that the load connected to the output does not exceed the allowable range (30 mA max). *T his parameter is accessible
if the 0-10V test is enabled above.
0-10V #x output reading — This is the actual voltage reading of the 0-10V output. It cannot be modified.
Update soft — Press this tab in order to load the software of the selected file into your PRO-VISION controller. This will affect the software of the controller without affecting your parameter settings.
Update settings — Press this tab in order to load the parameter settings of the selected file into your PRO-VISION controller. This transfer will affect the parameter settings of the controller without affecting the soft­ware.
Update all — Press this tab in order to load the software & parameter settings of the selected file into your PRO-VISION controller. This will affect the software and parameter settings of the controller.
4. Once the transfer is over the controller automatically reboots itself.
5. You can now remove the USB card from the connector.
Communication in use x% — This is the communication rate currently being used by your controller. If this value gets higher than 100%, the reaction time of your controller is likely to slow down. In order to decrease the communication rate, you can either remove some current sensors from the relay panels or switch to the high-speed communication mode (on condition that your application exclusively uses relay panels with the “CS” technology). *Refer to section 4.4 to change the
communication speed.
54
PRO-VISION rev.07
PRO-VISION

17. TECHNICAL SPECIFICATIONS

Typ e ..................................................................... PRO-VISION
Main supply fuse F1 ............................................... 1A, fast-blow
Main supply/frequency ...........................................115/230 VAC, 50/60Hz, 1 phase, 30W max.
Enclosure ..............................................................ABS, moisture and dust-tight
Operating temperature ...........................................32 to 104°F (0 to 40°C)
Storage temperature ..............................................5 to 122°F (-15 to 50°C)
Ambient relative humidity.......................................Max. 95%
Pollution degree.....................................................2
Altitude ................................................................Up to 2000m
Outputs:
14Vdc outputs ......................................................14 Vdc±10%, regulated, 350 mA max
0-10V outputs #1-2 ...............................................0 -10Vdc, 30mA source max
Precision on 0-10V outputs ....................................±1 %
Alarm contact .......................................................24 Vac or dc max, 0.15 A
Inputs:
Relative humidity input ..........................................4-20mA
Static pressure input ..............................................4 -20mA
Temperature inputs ................................................1K @ 77°F (25°C), NTC
Ammonia sensor ....................................................4-20mA
Wind speed sensor ................................................Pulse 2.5mph/Hz
Feeders 1-6 ..........................................................Dry contact
Water meters 1-6 ..................................................Input pulse width > 12ms, 60Hz max
PRO-VISION rev.07
55
PRO-VISION
18. INDEX
A
Age. See Animals
Alarms
Alarm conditions 46 Alarm LED 8 Alarm log 46 Backup thermostat warning 46 Feeder run time alarm 49 Static pressure alarms
Operation & settings 48
Temperature alarms
Breaker T°
Activation 13 Settings 47
Critical T°
Activation 10 Operation & settings 47
Ramp 48 Hi/Lo T° limits 47 Lo T° limit in non-brood zones 46 see Temperature zone
Water spill alarms 49
Ammonia sensor
Activation 11 Calibration 15 Current ammonia level 51
Amperage draw
Alarm limits 50 Current sensor
Activation 13 Sensor assignment 16
Current status
Output amperage draw 53 Output operation cost 53
Going rate 13
Anemometer. See Wind speed
Animals
Animal age
Current age 51 Settings 52
Animal count
Posting # of mortalities 52
Starting a new ock 52–54
Attic
Attic T° sensor
Activation 12 Current temperature 51 Sensor assignment 15
Attic vent
Activation 12 Amp draw & Operation cost. See Amperage
draw
Closing fan stage 25 Operation & settings 25–28
Output status 51 Relay assignment 16 Static pressure set points 28
Extracting air from the attic
Activation 12 Operation & settings 24
B
Backlight intensity 10
Backup
Backup relay
Amp draw & Operation cost. See Amperage
draw
Relay assignment 16 Backup thermostat warning 46 Making a controller backup 53–54
Beeper. See Keypad beeper Birds. See Animals
Breaker temperature
Activate breaker T° monitoring 13 Hi T° alarm limit 47 Sensor selection 13
Breeder facility. See Egg room
Broiler facility 10
Buttons 8
C
Calibration (Sensors & water meter) 15–16
Celsius units 10
Clean mode
Activate / deactivate 17 Clean mode T° set point 19 Low T° alarms in clean mode
Activating the alarm condition 17
Alarm limit 47 Operation & settings 17
Clock
Setting the time and date 9 Time format 10
Clock outputs. See Time clocks
Communication rate
% in use 54
Compensation
Attic min. vent. compensation. See Attic Relative humidity comp.. See Relative humidity
comp.
Connections 7
Contrast (LCD screen) 10
Controller
Communication rate
% in use 54 Diagnostic 54 Features 6 Location of the controls 8 Mounting instructions 7 Programs 10 Screen contrast 10 Set-up menu 10–13
Software
Language selection 10 Upgrade 53–54
Version 18 Technical specications 55 Update / Backup 53–54
Cooling outputs
Activation 11 Amp draw & Operation cost. See Amperage
draw
Egg room cooling output. See Egg room Hi/Lo RH compensation on the cooling output
Activation 11
Operation & settings 45 Operation & settings 35–36 Output status 51 Relay assignment 16
Copy & Paste function 10 Critical temperature alarm. See Alarms
Current conditions
Input & outputs conditions 51 Menu information 13 Screen saver 51
Current sensor. See Amperage draw Curtains. See Tunnel inlet or Natural curtain Curves. See Ramping
D
Date 9
Day / Night
Day/night times 12 Minimum ventilation night ramp
Activation 12
Operation & settings 21 Night set point
Activation 12
Settings 19
Diagnostic 54
Digital inputs
Assignment 14
Digital keypad 8
E
Egg room (breeder facility)
Egg count menu 53 Egg room activation 10 Egg room cooling output
Amp draw & Operation cost. See Amperage
draw
Operation & settings 43
Relay assignment 16 Egg room heater
Amp draw & Operation cost. See Amperage
draw
Operation & settings 43
Relay assignment 16 Egg room humidity output
Amp draw & Operation cost. See Amperage
56
PRO-VISION rev.07
PRO-VISION
draw
Operation & settings 43 Relay assignment 16
Egg room time clocks
Activation 11 Amp draw & Operation cost. See Amperage
draw
Operation & settings 41
Egg room T° sensors 43
Electrical current sensor. See Amperage draw
Electrical specications 55 Empty zones. See Non-brood zones
English software 10
F
Fahrenheit units 10
Fans / Tunnel fans
Amp draw & Operation cost. See Amperage
draw
Fan shutoff in tunnel mode 31 Fan / Tunnel fan outputs
Activation 11 Current status 51 Relay assignment 16
Minimum ventilation fans. See also Minimum
vent.
Fan cycling 23 Lateral fan selection 25–26 Tunnel fan selection 31–32
Operation & settings
Lateral fans 25–26 Tunnel fans 31–32
Feeders
Cut-off clock output 12 Cut-off relay
Output status 51
Relay assignment 16 Digital input assignment 14 Feeder run time
Activation of feeder inputs 12
Run time alarm 49
Run time history 52
Flock. See Animals
Foggers
Activation 12 Operation & settings 36 Relay assignment 16 Sensor assignment 14 Settings 12
G
Gallons 11
H
Heaters
Activation 11 Amp draw & Operation cost. See Amperage
draw
Egg room heaters. See Egg room Heater run time
History 52 Today’s run time 51
Heaters in non-brood zones. See Non-brood
zones
Hi Fire heaters. See also Heaters
Activation 11
Operation & settings 37 Operation & Settings 37 Output status 51 Relay assignment 16 RH compensation with heaters
Activation 11
Settings 44 Sensor assignment 14 Shutoff 37
History menus 52
Home key 8 Humidity. See Relative humidity
I
Index 56 Inlets. See Sidewall vent, attic vent or tunnel inlet Inputs. See also Sensors
Activation 10–13 Input status 51 List of available inputs 6
Installation (Set-up menu)
Parameter settings 10–13 Worksheet 63
Installer password. See Password
K
Keypad
Beeper volume 10 Location 8
L
Language selection 10 Lateral ventilation. See also Sidewall vents & Fans
Operation & settings 25–28 Overview of the ventilation concepts 20
Layer facility
Activation 10 Clock outputs in a layer facility 40
LCD screen 8
Contrast & backlight 10 Diagnostic 54
LED (Alarm) 8
Lights
Lights on the 0-10V output
0-10V Wiring 8
Activation 12
Current intensity 51
Diagnostic 54
Operation & Settings 38–41 On/off lights
Activation 16
Amp draw & Operation cost. See Amperage
draw
Principle of operation 38 Relay assignment 16
Liters 11
M
Main menu shortcut key 8
Measuring units 10
Memory cards (USB) 53–54
Menu selectors 8
Minimum ventilation
Compensation of the “On Time”
According to the attic temperature 24 According to the RH level
Activation 10
Settings 44 Fan cycling 23 Fan selection
Lateral fans 25–26
Tunnel fans 31 Operation & settings 21–24 Overview of the ventilation concepts 20 Pre-opening of sidewall vents in min. vent.
Mode: Automatic or programmable delay 12
Principle of operation 24
Settings 26, 28 Stir fans in min. vent. 12, 22, 34
Minimum ventilation ramp
Night ramp 13 Operation & settings 22–24
Mortality
History 52 Posting new mortalities 52
Mounting instructions 7
N
Natural ventilation
Natural curtain
Activation 11
Sensor assignment 14 Operation & settings 29
Non-brood zones
Low T° alarms in clean mode
Activating the alarm condition 17
Alarm limit 47 Making a non-brood zone 14 Principle of operation 17 T° alarms in non-brood zones 46 T° set point in non-brood zones 19
O
Operation costs 53. See also Amperage draw
Outdoor temperature
see Temperature zones
Outputs. See also Relays
PRO-VISION rev.07
57
PRO-VISION
Activation 10–13 Amp draw & Operation cost. See Amperage
draw
Diagnostic 54 List of available outputs 6 Output status 51
Outside temperature. See Temperature
P
Parameter adjustment 8
Password
Enable/disable the password 13 Entering/changing the password 9 Retrieving a lost password 9
Pilot light (Alarm) 8
Programs
Copy/paste program settings 10 Enabling programs 10 Principle of operation 10 Program selection 10
R
Ramping
Critical T° alarm limits 48 Minimum ventilation - On Time ramp 22 Temperature set point ramp 19 Water spill alarm limits 49
Relative humidity (RH)
RH Compensation (broiler/layer only)
Hi RH Comp. on the min. ventilation timer
Activation 10 Settings 44
Hi RH Comp. with the cooling outputs
Activation 11 Settings 45
Hi RH Comp. with the heaters
Activation 11 Settings 44
Lo RH Comp. with foggers
Activation 12 Settings 45
Lo RH Comp. with the cooling outputs
Activation 11 Settings 45
RH sensor
Activation 10 Calibration 15 Current sensor reading 51 History 52
RH Set point 19. See
Relays
Relay assignment 16 Relay assignment worksheet 61 Relay panel ID numbers 16 Relays with current sensors 16 Total number of relays 13
S
Screen saver 51
Screens (LCD)
Contrast 10 Location 8
Sensors
Connection 8 Electrical current sensor. See Amperage draw Extension 8 Relative humidity sensor. See Relative humidity Static pressure. See Static pressure (S.P.) Temperature sensors. See Temperature
Set points
Night set point
Activation 12 Settings 19
RH set point. See Relative humidity Static pressure set points. See Static pressure Temperature set point. See Temperature
Set-up menu
Parameter settings 10–13 Worksheet 63
Sidewall ventilation. See also Fans & Sidewall
vents
Operation & settings 25–28 Overview of the ventilation concepts 20
Sidewall vents
Activation 12 Amp draw & Operation cost. See Amperage
draw
Closing the vents in tunnel mode 31 Operation & settings 25–28 Output status 51 Pre-opening of the vents in min. vent.
Automatic/manual mode 12 Principle of operation 24 Settings 26, 28
Relay assignment 16 Static pressure alarms in sidewall vent. 48 Static pressure set points 28
Simulation (temperature) 18
Spanish software 10
Static pressure (S.P.)
Low S.P. Fan 48 S.P. alarm limits 48 S.P. Measuring units 10 S.P. Sensor
Activation 10 Calibration 15 Current sensor reading 51 History 52
Static pressure set points
Attic vent S.P. set points 28 Sidewall vent S.P. set points 28 Tunnel inlet S.P. set points 33
Stir fans
Activation 12 Amp draw & Operation cost. See Amperage
draw
Min.vent stir fan timer 22 Operation & settings 34
Output status 51 Relay assignment 16 Stir fan mode 12
T
Technical specications 55
Temperature
Average room temperature
Current average T° 51 History 52 Sensor assignment 14
Inside temperature sensors
Activation 11 Current sensor readings 51 History 52 Sensor assignment 14–16 Sensor calibration 15
Outside temperature sensor
Activation 10 Current sensor reading 51 History 52 Hot & Cold T° (for pressure set points) 28 Sensor calibration 15
Temperature alarm limits
Breaker’s temperature limit 47 Critical T°
Critical T° ramp 48
Operation & settings 47 Hi/Lo Temperature limits 47 Non-brood zone’s low T° limit 46
Temperature set point
Clean mode T° set point 19 Current set point 51 Night set point 12, 19 Operation & settings 19 Set point ramp 19
Temperature simulation 18 Temperature units 10
Temperature zones
Outdoor temperature
Outdoor T° compensation 47
Test mode 18
Thermostat warning 46
Time
Setting the time and date 9 Time format 10
Time clocks
Activation 11 Amp draw & Operation cost. See Amperage draw Clock mode selection (Start-Run/Stop) 12 Fans following time clocks 25 Operation & settings
In a breeder facility 41 In a broiler facility 40 In a layer facility 40
Output status 51 Relay assignment 16
58
PRO-VISION rev.07
PRO-VISION
Stop on feeder run time alarm 12 Tunnel fans following time clocks 31
Tunnel fans. See Fans / Tunnel fans
Tunnel inlet
Amp draw & Operation cost. See Amperage
draw
Output status 51 Pressure-based tunnel inlet
Activation 12 Operation & settings 33 Relay assignment 16 Standby mode 30 Static pressure set points 33
Temperature-based tunnel inlet
Activation 12 Principle of operation 32 Relay assignment 16 Standby mode 30 Tunnel openings 32
Tunnel ventilation
Before ofcial tunnel v. startup (transition)
Principle of operation 30
Settings 31 Closing sidewall vents in tunnel mode 31 Fan shutoff in tunnel mode 31
Ofcial start-up of tunnel ventilation
Principle of operation 30
Settings 31 Overview of the ventilation concepts 20 Pre-opening the tunnel inlet
Pre-opening mode : auto/manual 12
Pre-opening of the pressure-based inlet 33
Pre-opening of the temperature-based inlet
32
Settings 33 Static pressure alarms in tunnel vent. 48 Tunnel on standby 30 Tunnel sensors
Principle of operation 30
Sensor assignment 14
Amp draw & Operation cost. See Amperage
draw
Operation & settings 42 Output status 51 Relay assignment 16
Water meter
Activation 11 Calibration 15 Consumption history 52 Digital input assignment 14 Measuring units 11 Water consumption
Today 51
Water spill alarm 49–50
Weedon foggers
see Foggers
Wind speed sensor
Activation 11 Current wind speed 51
Wiring 7
Worksheet
Contact names & addresses 60 Relay assignment 61 Set-up menu 63
U
Units of measurement 10
USB memory stick 53–54 User password. See Password
V
Ventilation
Fans. See Fans / Tunnel fans Min. ventilation. See Minimum ventilation Stir fans. See Stir fans
Ventilation concepts 20 Vents. See Sidewall vent, Attic vents or Tunnel inlet
Version (software) 18 Voltage. See Amperage draw
Volume (keypad) 10
W
Water line ush outputs
Activation 11
PRO-VISION rev.07
59
[ES] HOJAS DE TRABAJO
CLIENTE
Nombre: ___________________________________________________________
Dirección: ___________________________________________________________
___________________________________________________________
___________________________________________________________
Ciudad: ___________________________________________________________
Teléfono: ___________________________________________________________
Fax: ___________________________________________________________
Email: ___________________________________________________________
INSTALADOR
Nombre: ___________________________________________________________
Dirección: ___________________________________________________________
___________________________________________________________
___________________________________________________________
Ciudad: ___________________________________________________________
Teléfono: ___________________________________________________________
Fax: ___________________________________________________________
Email: ___________________________________________________________
PRO-VISION
[EN] WORKSHEET
CLIENT
Name: ___________________________________________________________
Address: ___________________________________________________________
___________________________________________________________
___________________________________________________________
City: ___________________________________________________________
Tel.: ___________________________________________________________
Fax: ___________________________________________________________
E-mail: ___________________________________________________________
INSTALLER
Name: ___________________________________________________________
Address: ___________________________________________________________
___________________________________________________________
___________________________________________________________
City: ___________________________________________________________
Tel.: ___________________________________________________________
Fax: ___________________________________________________________
E-mail: ___________________________________________________________
Plantilla de asignación de relés
• VL- C (vent. lateral se cierre)
• VL-A (vent. lateral se abre)
• VA-C (vent. ático se cierre)
• VA-A (vent. ático se abre)
• CNx-C (Cortina natural x se cierre)
• CNx-A (Cortina natural x se abre)
• TN1-A (p. túnel 1 se abre)
• TN1-C (p. túnel 1 se cierre)
• TN2-A (p. túnel 2 se abre)
• TN2-C (p. túnel 2 se cierre)
• Nebulizador
Prog. 1 Prog. 2 Prog. 3 Prog. 4 Prog. 5
• Calentador 1-32
• Cal. fuego máx 1-16
• Ventilador 1-5
• Ventil. túnel 1-20
• Alimentador 1-4
• Enfriamiento 1-6
• Reloj 1-8
• Purga agua 1-8
• Ventil. de circulación
• Luces
• Relé de respaldo
Escriba la función de cada relé. Esta función debe configurarse por
separado para cada programa en uso. A seguir una tabla con todas
las posibles funciones de relé:
• Dispositivo de PE Baja
293031323334353637383940414243444546474849505152535455
Rel. Relay function / Función de relé
56
PRO-VISION
Relay Assignment Worksheet
Write down the function of each relay. This function must be set
separately for each program in use. Below is a table showing all
possible relay functions:
• SV-C (sidewall vents close)
• SV-O (sidewall vents open)
• AV-C (attic vents close)
• AV-O (attic vents open)
• NTx-C ( Natural curtain x closes)
• NTx-O (Natural curtain x opens)
• TN1-O (tunnel inlet 1 opens)
• TN1-C (tunnel inlet 1 closes)
• TN2-O (tunnel inlet 1 opens)
• TN2-C (tunnel inlet 1 closes)
• Fogger
Prog. 1 Prog. 2 Prog. 3 Prog. 4 Prog. 5
• Heater 1-32
• Hi Fire 1-16
• Fan 1-5
• Tunnel Fan 1-20
• Feeder 1-4
• Cooling 1-6
• Clock 1-8
• Flush output 1-8
• Stir fan
• Lights
• Backup relay
• Low SP
123456789
Rel. Relay function / Función de relé
10111213141516171819202122232425262728
Prog. 1 Prog. 2 Prog. 3 Prog. 4 Prog. 5
99
100
101
102
103
104
105
106
Rel. Relay function / Función de relé
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
Prog. 1 Prog. 2 Prog. 3 Prog. 4 Prog. 5
PRO-VISION
5758596061626364656667686970717273747576777879808182838485868788899091929394959697
Rel. Relay function / Función de relé
98
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Su parámetro para el programa n°
1 2 3 4 5
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Parámetros Campo de valores
[ES] Plantilla del menú de instalación
for program #
Contraste 10-100%
Intenidad luz de fondo 3-5
Volumen teclado 0-100%
Idioma English / Español
Common to all programs
Common to all programs
Common to all programs
1 2 3 4 5
Pavos / Ponedoras
Unidades de temperatura Celsius o Fahrenheit
Formato de hora AM/PM o 24-hour
Tipo de producción Reproducción /Engorde/
Utilizar sensor presión estát. Sí / No
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Sí / No
Utilizar rampa de vent. mín Sí / No
Unidades de presión “WC o Pascal (Pa)
Utilizar sensor humedad
rel.
Common to all programs
Common to all programs
Utilizar comp. HR en vent. mín Sí / No
Utilizar sensor T° exterior Sí / No
Utilizar alarma T° crítica Sí / No
N° de programas 1-10
Guardar programa en 1-10
Common to all programs
Common to all programs
Common to all programs
Marcha
Confirme Sí / No
N° de medidores de agua 1-6
Unidades medición agua Galón / Litro
N° de salidas de reloj 1-8
Modo de reloj Inicio/Paro o Inicio/
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Common to all programs
N° de sensores de T° 1-32 (9-32=opcional)
Utilizar velocidad del viento Sí / No
Utilizar sensor de amoniaco Sí / No
Utilizar purga de agua Sí / No
N° de cortinas naturales 0-8
Common to all programs
Common to all programs
Common to all programs
Usar cortina en Vent. Lateral Sí / No
N° de líneas de agua 1-8
N° de calentadores 1-32
Utilizar comp. HR con calent. Sí / No
Utilizar calentador fuego máx Sí / No
N° de ventiladores 1-5
PRO-VISION
Parameter Range Your setting
[EN] Set-up Menu Worksheet
Backlight intensity 3-5
Contrast 10-100%
Key beeper tone 0-100%
Language English / Español
Temperature Unit Celsius or Fahrenheit
Turkey/ Layer
Yes / No
Time mode AM/PM or 24-hour
Controller used for Breeder /Broiler /
Use static pressure
sensor?
(“WC) or Pascal (Pa)
Yes / No
Use min vent ramping Yes / No
Pressure Unit Inches of water column
Use relative humidity
sensor?
Yes / No
Use RH min vent. compensation?
Use critical alarm ? Yes / No
Number of programs 1-10
Use outside T° sensor? Yes / No
Save current program to 1-10
Confirm? Yes / No
Number of water meter 1-6
Water meter unit Gallon / Liter
Number of time clock 1-8
Number of T° sensors 1-32 (#9-32=optional)
Clock Mode Start/Stop or Start/Run
Use ammonia sensor? Yes / No
Use wind speed? Yes / No
Use water flush? Yes / No
Number natural curtains 0-8
Use curtain inlet ? Yes / No
Number of water lines 1-8
Yes / No
Number of heaters 1-32
Use heater RH compensation ?
Use hi fire heaters? Yes / No
Su parámetro para el programa n°
1 2 3 4 5
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Parámetros Campo de valores
N° de ventiladores túnel 1-20
N° de salidas de enfriamiento 1-6
for program #
Sí / No
Parar enfriamiento si HR alta Sí / No
Activar enfriamiento si HR
baja
Usar Nebuliz. Weedon Sí / No
N° de zonas de nebulización 1-6
Usar Nebuliz si HR baja Sí / No
N° de alimentadores 1-6
Alimentad 1 detiene Reloj Reloj 1-8 (o Sin)
Alimentad 2 detiene Reloj Reloj 1-8 (o Sin)
Alimentad 3 detiene Reloj Reloj 1-8 (o Sin)
Alimentad 4 detiene Reloj Reloj 1-8 (o Sin)
Alimentad 5 detiene Reloj Reloj 1-8 (o Sin)
Alimentad 6 detiene Reloj Reloj 1-8 (o Sin)
Utilizar circuladores de aire Sí / No
Cicrulador según Temperatura/ Vent.
Mín
Utilizar luces Sí / No
N° de programas de luz 1-9
Utilizar ventanas laterales Sí / No
Utilizar puertas de túnel Sí / No
(P.E.)
N° de puertas del túnel 1-2
Operación puertas del túnel Temperat. / Presión
Control de ventana Temperat. / Presión
(P.E.)
Ajuste P.E. ventana lateral Interior/Exterior/Sin
Utilizar ventana de ático Sí / No
Utilizar sensor T° en ático Sí / No
Common to all programs
Sí / No
Man. / Auto.
Utilizar compensación de
ático
Modo preapertura de
ventanas
Utilizar mín vent de noche Sí / No
Día comienza a 0:00AM a 12:59PM
Noche comienza a 0:00AM a 12:59PM
Common to all programs
Common to all programs
PRO-VISION
Parameter Range Your setting
[EN] [ES]
1 2 3 4 5
Yes / No
Use attic min vent.
Use attic vent? Yes / No
Use attic T° sensor? Yes / No
Yes / No
compens?
Pre-opening mode Manual / Automatic
Use min vent. night on
Day starts at 0:00AM to 12:59PM
time?
Number of fans 1-5
Number of tunnel fans 1-20
Number of coolings 1-6
RH shutoff cooling? Yes / No
Activate cooling on low RH? Yes / No
Use Weedon foggers Yes / No
Number of fogger zones 1-6
Activate foggers on low RH Yes / No
Number of feeders 1-6
Feeder 1 Clock to Stop Clock 1-8 (or None)
Feeder 2 Clock to Stop Clock 1-8 (or None)
Feeder 3 Clock to Stop Clock 1-8 (or None)
Feeder 4 Clock to Stop Clock 1-8 (or None)
Feeder 5 Clock to Stop Clock 1-8 (or None)
Feeder 6 Clock to Stop Clock 1-8 (or None)
Vent.
Use stir fan? Yes / No
Stir fan base on Temperature/ Min
Use light? Yes / No
Number of light program 1-9
Use sidewall vent? Yes / No
Use tunnel inlet? Yes / No
(S.P.)
Number of tunnel inlet 1-2
Tunnel inlet mode Temperat. / Pressure
Vent inlet mode Inside/Outside/None
Vent Inlet SP adjustment
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Su parámetro para el programa n°
1 2 3 4 5
1 RP-32,
1 RP-40,16
2 RP-32,
1 RP-40,32
2 RP-40
3 RP-32
Común en todos los programas
Común en todos los programas
Común en todos los programas
3 RP-40
4 RP-32
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
Común en todos los programas
-calent, -T°
Parámetros Campo de valores
Supervisar T° del disyuntor Sí / No
Common to all programs
for program #
1 2 3 4 5
Sensor del disyuntor Sensor 1-8
Utilizar contraseñas Sí / No
N° de relés 1 RP-40,
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Yes / No
Utilizar sensor corriente Sí / No
Costo operación aprox. 0.00 a 99.99$/KWH
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Tensión Ventil. 108 V, 120 V o 240 V
Tensión V.túnel 108 V, 120 V o 240 V
Tensión Calent. 108 V, 120 V o 240 V
Tensión Calent. 108 V, 120 V o 240 V
Tensión Enfri. 108 V, 120 V o 240 V
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Tensión Reloj 108 V, 120 V o 240 V
Tensión Circul. 108 V, 120 V o 240 V
Tensión Luces 108 V, 120 V o 240 V
Tensión Purga agua 108 V, 120 V o 240 V
Tensión respaldo 108 V, 120 V o 240 V
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Common to all programs
Tensión V.Lateral 108 V, 120 V o 240 V
Tensión cortina naturall 108 V, 120 V o 240 V
Tensión Puerta Túnel 108 V, 120 V o 240 V
Tensión Atico 108 V, 120 V o 240 V
Tensión Hu.Enfri 108 V, 120 V o 240 V
Common to all programs
Common to all programs
1 RP-32,
1 RP-40,16
2 RP-32,
1 RP-40,32
Tensión Hu.Calent. 108 V, 120 V o 240 V
Tensión HR 108 V, 120 V o 240 V
2 RP-40
3 RP-32
Tensión dispos.PE baj 108 V, 120 V o 240 V
Velocidad de comunicación Alta / Baja
Condicion actual muestra Todo, – calent.,
Common to all programs
Common to all programs
3 RP-40
4 RP-32
Common to all programs
Common to all programs
w/o heat run time & T°
sensors
PRO-VISION
Parameter Range Your setting
[EN] [ES]
Night starts at 0:00AM to 12:59PM
Monitor breaker tempera-
ture?
Breaker sensor Sensor 1-8
Approx. Operation cost 0.00 to 99.99$/KMH
Fan voltage 108 V, 120 V or 240 V
Tun fan voltage 108 V, 120 V or 240 V
Heat voltage 108 V, 120 V or 240 V
Feed voltage 108 V, 120 V or 240 V
Cool voltage 108 V, 120 V or 240 V
Clock voltage 108 V, 120 V or 240 V
Sitr fan voltage 108 V, 120 V or 240 V
Light voltage 108 V, 120 V or 240 V
Water flush voltage 108 V, 120 V or 240 V
Backup voltage 108 V, 120 V or 240 V
Sidewall voltage 108 V, 120 V or 240 V
Tun inlet voltage 108 V, 120 V or 240 V
Natural curtain voltage 108 V, 120 V or 240 V
Attic voltage 108 V, 120 V or 240 V
Egg cool voltage 108 V, 120 V or 240 V
Egg heat voltage 108 V, 120 V or 240 V
Egg RH voltage 108 V, 120 V or 240 V
Low SP device voltage 108 V, 120 V or 240 V
Number of relays 1 RP-40,
Use current sensor ? Yes / No
Use passwords? Yes / No
Communication speed Low / High
Current condition display All, w/o heat run time,
PRO-VISION
NOTES / NOTAS
PRO-VISION
NOTES / NOTAS
Loading...