GE
For load currents which are greater than 600 A the
Grid Solutions
Model PCL 0-600
AC Current Transducer
0-600 Amps ac to produce 4-20 mA dc
Operating Range
Input 0 to 100 thru 600 Amps ac.
Output: 4-20 mA dc.
Frequency
50-400 Hz.
Accuracy
±0.05 % F.S. maximum.
1 % max. peak ripple on output.
Response Time: <150 ms (10 % to 90 %)
Output load (RL): 0-1,000 .
Ambient Temperature Range
Effect on accuracy ±0.02 %/ oC
Operating: -30
Storage: -55
oC to +60 oC
oC to +85 oC
Insulation level
600 Volts, 10 kV BIL full wave
The PCL transducers accurately converts a sinusoidal ac input current to a proportional dc output current. The high performance
integrated circuit amplifiers achieve a content current output, insensitive to a variable impedance load. This allows the PCL to be easily
applied to remote instrumentation, motor control and energy management installations. The output signal (4 to 20mA dc) can be
transmitted over long distances with no loss accuracy
Maximum output: 30 mA dc.
Supply Voltage Range: 120 Vac ±10 %.
Terminal are brass studs No. 8-32
with one flatwasher, lockwasher
and regular nut.
Approximate weight 3.0 lbs.
REGULATORY AGENCY APPROVALS
317008
CANADIANC
CANADIANC
C
CC
C 317008
CC
PCL-5 may be used in conjunction with separate
higher ratio C.T.’s having a rated 5A secondary.

Model PCL 0-600 - Typical Connection Diagram
Do not apply around or remove
from Hazardous LIVE conductors.
Cleaning:
Remove dust with a damp cloth. Do not spray with any chemicals.
Caution:
Proper safety precautions must be followed during installation
by a trained electrician. Never install or remove while bus is
energized. Protective equipment must be used if hazardous parts
in the installation where measurement is tobe carried out could
be accessible.