Instrument Transformer, Div of GE LPVRB Data Sheet

GE
Grid Solutions
Model LPVRB
Three Phase Voltage Monitor
Protection
Protects 3-power system loads from:
• Loss of any Phase
• Low Voltage
• High Voltage
• Voltage Unbalance
• Phase Reversal
• Rapid Cycling
Additional Features
• Compact Design
• UL and cUL listed
• CE Compliant
• Finger Safe terminals
• Standard Surface or DIN Rail Mount
• Standard 1-500 Sec. Variable Restart Delay
• Standard 2-8 % Variable Voltage Unbalance
• One 10 Amp General purpose Form C relay
• Standard 1-30 % Variable Trip Delay
• Optional Manuel Reset
Trip Delay Time
• Low, high and Unbalance Voltage:
• 1-30 seconds adjustable
Note 50 Hz will increase all delay timers by 20 %
*
Restart Delay Time
• After fault - 1 - 500 seconds
• After a Complete Power loss (When manuel reset pins are shorted)
Specifications
• 3-phase Line Voltage: 190 - 480 VAC
• Frequency: 50* or 60 Hz
• Low Voltage (% of set Point) *
• Trip: 90 % ± 1 %
• Reset: 93 % ± 1 %
• High Voltage (% of set Point)
• Trip: 110 % ± 1 %
• Voltage Unbalance (NEMA)
• Trip: 2-8 %
• Reset: Trip setting minus 1 % (5-8 %) Trip setting minus .5 % (2-4 %)
Standard Passed:
• Electrostatic Discharge (ESD)
Radio Frequ. Immunity, Radiated:
• 150 MHz V/m, 10 V/m
Fast Transient Burst:
IEC 1000-4-5,
• Level 3, 3.5 kV input power & controls Surge: IEC 1000-4-5. Level 3,
Surge:
IEC 1000-4-5. Level 3,
• 4 kV line-to-line, Level 4, 4 kV line-to-ground
Weight: 14 oz.
Terminal Torque: 6 in. lbs.
ANSI/IEEE
C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line
Hi-Potential Test:
Meets UL508 (2 x rated V +1,000 V for 1 min)
Class Protection:
IP20, NEMA 1 (Finger Safe)
Output Contact Rating: 1-Form C
• 10 A General purpose @ 240 VAC
• Pilot Duty 480 VA @ 240 VAC, B300
Power Consumption: 6 Watts (max)
Enclosure: Polycarbonate
Wire Type:
Stranded or solid 12-20 AWG, one per terminal
• The Model LPVRB is designed to protect 3­phase loads from damaging power conditions.Its wide operating range combined with UL and CE compliance insures worldwide acceptance.
LPVRB Typical Wiring Diagram
a 190 to 240 V 60 Hz system, a 440 to 480 V 60 Hz system, or a 380
Two LEDs indicate the status of the Model LPVRB; Run Light, Under
Unbalance Adjust
Pick-up Adjust
Features
Four adjustment pots provide versatility for all kinds of applications. Provides the versatility needed to handle global applications. Diagnostic LEDs indicate trip status and provide simple trouble shooting. Microcontroller based based circuitry provides better accuracy and higher than analog designs. Transient protected to meet IEEE and IEC standards and operate under tough conditions. Will detect single phase condition regardless of regenerated voltages.
Environmental:
Ambient Operating: -20 oC to +70 oC (-4 to +158 o F)
Ambient Storage: -40 oC to + 85 oC (-4 to +176 o F)
Relative Humidity: 10-95 %, non-condensing per IEC 2-3
Special Options:
Manual Reset: External momentary push button required
Safety Marks: UL508, IEC 60947-6-2
Restart Adjust
Trip Delay Adjust
Status Indication
LPVRB Operation with Options
A unique microcontroller-based voltage and phase sensing circuit constantly monitors the three phase voltages to detect harmful power line conditions. When a harmful condition is detected, the LPVRB’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (Restart Delay) or after a manual reset. The trip and restart delays prevent nuisance tripping due to rapidly fluctuating power line conditions.
The Model LPVRB automatically senses whether it is connected to
to 416 V 50 Hz system. An adjustment is provide to set the normal line voltage from 190-240 or 380-480 VAC. Other adjustments include a 1-30 second trip delay, a 1-500 second restart delay, and a 2-8 % voltage unbalance trip adjustment.
Voltage, Over Voltage, Phasing Fault/Reverse Phase, and Manual Reset. The LPVRB ships with a jumper installed for automatic restart. A connector with 12” wires is included for manual reset switch.formation, item 7.1.
Grid-AIS-L4-ITI_Model_LPVRB-1581-2017_08-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.