Instrument Transformer, Div of GE JCS-0C Data Sheet

Grid Solutions
Model JCS-0C
Indoor/Outdoor Current Transformer
600 V, 10
Application
Designed for indoor service; suitable for operating meters, relays and control devices, on circuits not exceeding 600 V line-to-line. It may be used on higher voltage circuits with an insulated conductor; please refer to the Applications Information section of catalog GEP-9186.
kV BIL, 50-4,000 A Window Diameters 2.50”, 4.88”, 5.25”
Regulatory Agency Approvals
UL Recognized File E93779
Weight
(Approximate) Transformer,Cat No.750X110038 47 lbs Transformer,Cat No.750X110039-045 34 lbs Transformer,Cat No.750X110046-072 28 lbs Optional base plate 1.5 lbs
Reference Drawings
Outline 0121C33697
Insulation Level
0.6 kV; BIL 10 kV full wave
Frequency
50-60 Hz
Notes:
Other window diameters are available for special applications, consult factory.  Other ratios are available for special applications, consult factory.
** Non-standard taps 200/400/600/800/1200/1400/1600/1800/2000:5
JCS-0C Dimensions
Construction and Insulation
The core and coil are enclosed in a case molded with GE Valox thermoplastic polyester resin. This tough material has excellent electrical and mechanical properties over a wide temperature range, has low water absorption and is resistant to oil and a variety of chemicals.
Core and Coils
The core is made from high quality grain oriented silicon steel, annealed under rigidly controlled factory conditions. The secondary winding is made of heavy enameled copper wire. The secondary windings are evenly distributed around the core for maximum accuracy and resistance to stray fields from adjacent conductors.
Terminals
Secondary terminals are No. 10-32 brass screws with one flat washer and one lock washer. Because the transformer is used primarily in enclosed, switchgear compartments, which cannot be opened while the transformer is energized, a secondary shorting device and terminal cover are not provided.
Polarity
Primary and secondary polarity marks H1 and X1 are marked on the face of the transformer.
Primary Conductor
A bus or insulated cable forms the primary winding.
Nameplates
The nameplate is a polyester label attached to the face of the transformer.
Baseplate and Mounting
The transformer can be mounted in any position. The base plate is made of heavy steel plate. It is attached to the transformer with two bolts. If the base plate is not used, the 3/8-16 tapped holes in the bottom surface are used for mounting.
Maintenance
These transformers require no maintenance, other than occasional cleaning, if installed where air contamination is severe.