Instrument Transformer, Div of GE JAS-0C Data Sheet

GE
Grid Solutions
Model JAS-0C
Indoor Current Transformer 600 V 10 kV BIL, 150-2,000 A, Window Diameter 4.00”
Application
Designed for indoor service. Suitable for operating meters, relays and control devices, on circuits not exceeding 600 V line-to-line. It is intended for use in switchboards and in switchgear equipment. It may be used on higher voltage circuits with an insulated conductor. Refer to the Applications Information section of catalog GEP-9186.
Regulatory Agency Approvals
UL Recognized File E93779
Continuous Thermal Current Rating Factor
30 °C Ambient 1.33 55 °C Ambient 1.00
Weight
Transformer (approximate) 9 lbs
Reference Drawings
Outline 0121C33703
Insulation Level
0.6 kV; BIL 10 kV full wave.
Frequency
mechanical properties over a wide temperature range, and is resistant to
evenly distributed around the core for maximum accuracy and resistance
JAS-0C Dimensions
Construction and Insulation
The core and coil are enclosed in a case molded with GE Valox thermoplastic polyester resin. This material has excellent electrical and
oil and a variety of chemicals.
Core and Coils
The core is made from high quality grain oriented silicon steel, annealed under rigidly controlled factory conditions. The secondary winding is made of heavy enameled copper wire. The secondary windings are
to stray fields from adjacent conductors.
Terminals
Secondary terminals are No. 8-32 brass studs with one flatwasher, one lockwasher and a regular nut. Because the transformer is used primarily in enclosed switchgear compartments, which cannot be opened while the transformer is energized, a secondary shorting device and terminal cover are not provided.
Polarity
Primary and secondary polarity marks H1 and X1 are molded into the case.
Primary Conductor
A bus or insulated cable forms the primary winding.
Nameplates
The nameplate is a polyester label attached to the face of the transformer.
Mounting
The transformer can be mounted in any position.
Maintenance
These transformers require no maintenance, other than occasional cleaning, if installed where air contamination is severe.
Grid-AIS-L4-ITI_Model_JAS_0C-1394-2017_07-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.