Instrument Transformer, Div of GE JAI-0C 600V, JAU-0C 600V Data Sheet

GE
Grid Solutions
Model JAI-0C & JAU-0C 600V
Indoor Current Transformer, 10 kV BIL, 50-800 A Window Diameter 1.05”/1.10”/2.06”/3.00”
Application
Designed for indoor service. Suitable for use with indicating instruments and energy management systems. Due to their very low burden capability, these transformers are not normally used with watthour meters for revenue billing.
Regulatory Agency Approvals
UL Recognized File ........................E93779
Rating Factor
1.0 @ 30 °C
Weight
(approximate)
Transformer with 1.05” window ........0.5 lbs
Transformer with 2.06” window ........0.6 lbs
Transformer with 3.00” window ........0.9 lbs
Reference Drawings
Outlines
JAI-0C .............0121C33705
JAU-0C ...........0121C33701
Insulation Level
0.6 kV; Designed for use with insulated conductors.
Frequency
Model JAI-0C & JAU-0C 600V
Dimensions - Refer to Data Table
JAU-0C
Construction and Insulation
The core and coil are enclosed in a case molded with GE Noryl thermoplastic PPO resin. This material has excellent electrical and mechanical properties over a wide temperature range, low water absorption and is flame resistant .
Core and Coils
The core is made from high quality grain oriented silicon steel, annealed under rigidly controlled factory conditions. The secondary winding is made of heavy enameled copper wire. The secondary windings are evenly distributed around the core for maximum accuracy and resistance to stray fields from adjacent conductors.
Terminals
Secondary terminals on Model JAI-0C are No. 8-32 brass studs with one flat washer and one lock-washer and a regular nut. Model JAU­0C has 24” flexible leads of #16 stranded wire.
Polarity
The H1 polarity mark is molded into the case, at the side of the window on one face. The X1, X2 polarity marks are also molded into the case adjacent to the secondary terminals. On Model JAU-0C, the polarity X1 lead is white and the non- polarity X2 lead is black.
JAI-0C
Primary Conductor
These units are designed to be placed over an insulated cable which forms the primary winding.
Nameplates
The nameplate is a polyester label attached to the side of the transformer.
Mounting
The transformer can be mounted in any position. And, may be suspended from the bus-bar or cable.
Maintenance
These transformers require no maintenance, other than occasional cleaning, if installed where air contamination is severe.