Instrument Transformer, Div of GE JAD-0W Encompass Data Sheet

GE
insulated primary conductor, refer to the Applications Information
Grid Solutions
MODEL JAD-0W EncompassTM
Revenue Metering Current Transformer
Application
EncompassTM is an extended range revenue metering current transformer. Model JAD-0W is designed for both indoor and outdoor service. Suitable for operating meters, instruments and control devices. For use on higher voltage circuits with an
section of catalog GEP-9186.
Features
Voltage Class: 0.6 kV
Frequency: 50-60 Hz
Window Size: 5.75”
Insulation Level: 10 kV BIL
Application: Indoor/Outdoor
Benefits
Light load test points extended beyond IEEE requirements plus
high rating factors allow for one Encompass unit to functionally replace multiple standard ratios
Simplify CT selection and billing multipliers, improving
productivity and minimizing risk of error
Reduce inventory and part number requirements, reducing
asset and operational costs
(1) Exceeds IEEE definition for standard revenue metering accuracy. Maintains 0.6 Accuracy Class from 4% to 40% of rated current and 0.3 Accuracy Class from 40% through Rating Factor. (2)Primary-baroptionsavailable,uponrequest. ContactGEformoredetails. (3) Other designs available, upon request. Contact GE for more details.
Weight
water absorption and is resistant to oil and a variety of chemicals.
Secondary terminals are tin plated brass, compression type with a
0.275” diameter cross-hole for wiring and a 1/4-28 clamp screw. A
The terminal cover is made of a clear plastic. Provision is made for
The transformer can be mounted in any position. An optional base
Transformer, Window Type 13 lbs Primary Bar, add 4 lbs Mounting Base, add 2 lbs
Reference Drawings
Outline 0121C34994 Primary Bar Assembly 0821C35021 Base Assembly 0221A36647
Construction and Insulation
The core and coil assembly is encapsulated in resin within a molded case. The case is molded with GE Valox thermoplastic polyester resin. This tough material has excellent electrical and mechanical properties over a wide temperature range, has low
The polyurethane resin filling completely encapsulates the winding, leads and terminals to form a waterproof unit.
Core and Coils
The core is made from high quality grain oriented silicon steel, annealed under rigidly controlled factory conditions. The secondary winding is made of heavy enameled copper wire. The secondary windings are evenly distributed around the core for maximum accuracy and resistance to stray fields from adjacent conductors.
Terminals
shorting device is provided and interlocked to the terminal cover.
sealing the cover.
Polarity
Primary and secondary polarity marks H1 and X1 are molded into the case.
Nameplates
The nameplate is laser engraved aluminum and is attached to the top of the unit. The nominal current rating is marked on both sides of the unit in large numerals.
Primary Conductor
Removable primary bars are formed from 1/4”x 4”tin-plated, flat copper bar, with 1/4”spacing between bars on multiple bar assemblies. The bars are retained by insulated and ventilated end caps, which permit the bars to be rotated to any desired orientation and allow the transformer to be supported in a vertical primary arrangement. A potential connector is provided adjacent to one end cap. Primary bars are available in 11 7/8”and
14 1/4”lengths, each provided with four bolt holes at each end.
Baseplate and Mounting
plate is available, made of stainless steel. It is attached to the
transformer with two bolts.
Maintenance
These transformers require no maintenance, other than occasional cleaning, if installed where air contamination is severe.
Grid-AIS-L4-ITI_Model_JAD_OW-1385-2017_10-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.