Instrument Transformer, Div of GE JAB-AC Data Sheet

GE
Energy Connections
Model JAB-AC
Indoor Current Transformer 600 V, 10 kV BIL, 200-3,000 A Window Size 4.50” X 3.50
Application
Designed for indoor service; especially designed for installation over the secondary bushings of pad mounted transformers from 75 kVA to 3,000 kVA. For mounting and application information, including use at higher voltages, and matching the current rating to the pad transformer thermal capability, please refer to the Applications Information section of catalog GEP-9186.
Weight
Approximately .......................8.25 lbs
Reference Drawings
Outline .................0121C33851
Insulation Level
0.6 kV; BIL 10 kV full wave
Frequency
50-60 Hz
Notes:
A high temperature version is available for use in locations with unusually high ambient temperatures.
Consult factory for base plate provisions.
chemicals. The polyurethane resin filling completely encapsulates
JAB-AC Dimensions
Construction and Insulation
The core and coil assembly is encapsulated in resin within a molded case. The case is molded with GE Valox thermoplastic polyester resin. This tough material has excellent electrical and mechanical properties over a wide temperature range, has low water absorption and is resistant to oil and a variety of
the winding, leads and terminals to form a waterproof unit.
Core and Coils
The core is made from high quality grain oriented silicon steel, annealed under rigidly controlled factory conditions. The secondary winding is made of heavy enameled copper wire. The secondary windings are evenly distributed around the core for maximum accuracy and resistance to stray fields from adjacent conductors.
Terminals
Secondary terminals are tin plated brass, compression type with a 0.275” diameter cross-hole for wiring and a 1/4-28 clamp screw. A shorting device is provided and interlocked to the terminal cover. The terminal cover is made of a clear plastic. Provision is made for sealing the cover.
Polarity
Primary and secondary marks H1, H2 and X1, X2 are molded into the case. In addition, H1 and X1 are identified by white dots.
Primary Conductor
These transformers are primarily intended for installation over the bushing and terminal blade of pad mount transformers, which then forms the primary conductor.
Nameplates
The nameplate is laser engraved aluminum. It is attached to the side of the unit and has provision for attaching the user’s identifying tag. The nominal current rating is on both faces of the unit in large numerals.
Mounting
The transformer can be mounted in any position but is usually installed on the pad mount tranformer terminal blade using the “grabbers”. The transformer also has two mounting holes allowing it to be attached to a mounting bracket.
Maintenance
These transformers require no maintenance, other than occasional cleaning, if installed where air contamination is severe.
Grid-AIS-L4-ITI_Model_JAB-AC-1380-2017_05-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.