GE
is a revenue metering current transformer which
Energy Connections
Model JAB-0S RevenueSenseTM
Revenue Metering Current Transformer
Application
RevenueSenseTM
maintains IEEE 0.15 accuracy class from 1% of rated current up
through rating factor. This is accomplished using the specialized
amorphous core material which minimizes electrical core losses.
The result is an extremely accurate CT that can maintain high
accuracy over a extended range of current. Model JAB-0S is
designed for indoor service; specifically designed for installation
over the secondary bushings of pad-mounted transformers.
Features
Voltage Class: 0.6 kV
Frequency: 50-60 Hz
Window Size: 4.5” x 3.5”
Insulation Level: 10 kV BIL
Application: Indoor
Benefits
Maximize revenue metering accuracy with special high
accuracy rating extended beyond IEEE requirements
Simplify CT selection and billing multipliers, improving
productivity and minimizing risk of error
Reduce inventory and part number requirements, reducing
asset and operational costs
(1) Exceeds IEEE definition for special high accuracy. Maintains 0.15 Accuracy from 1 % to Rating Factor.
(2) Other designs available, upon request. Contact GE for more details.
![](/html/d9/d9fa/d9fa7acad5ab19ba51972f5830150d08627e2ea9f7d7d6ea415eb8e1aa2b70ed/bg2.png)
Reference Drawings
Outline 0121C33851
Weight
Transformer 8.25lbs
Construction and Insulation
The core and coil assembly is encapsulated in resin within a
molded case. The case is molded with GE Valox thermoplastic
polyester resin. This tough material has excellent electrical and
mechanical properties over a wide temperature range, has low
water absorption and is resistant to oil and a variety of
chemicals. A polyurethane resin filling completely encapsulates
the winding, leads and terminals to form a waterproof unit.
Core and Coils
The core is manufactured with high-efficiency material that
reduces energy losses, allowing from higher accuracy over a
wider range. The secondary winding is made of heavy enameled
copper wire. The secondary windings are evenly distributed
around the core for maximum accuracy and resistance to stray
fields from adjacent conductors.
Terminals
Secondary terminals are tin plated brass, compression type with
a 0.275” diameter cross-hole for wiring and a 1/4-28 clamp
screw. A shorting device is provided and interlocked to the
terminal cover. The terminal cover is made of a clear plastic.
Provision is made for sealing the cover.
Polarity
Primary and secondary marks H1, H2 and X1, X2 are molded into
the case. In addition, H1 and X1 are identified by white dots.
Primary Conductor
These transformers are primarily intended for installation over
the bushing and terminal blade of pad mount transformers,
which then forms the primary conductor.
Nameplates
The nameplate is laser engraved aluminum. It is attached to the
top of the unit and has provision for attaching the user’s
identifying tag. The nominal current rating is on both faces of the
unit in large numerals.
Mounting
The transformer can be mounted in any position but is usually
installed on the pad mount transformer terminal blade using the
Valox “grabbers”. The grabbers are removable and the
transformer also has two mounting holes allowing it to be
attached to a mounting bracket.
Maintenance
These transformers require no maintenance, other than
occasional cleaning,