Model JAB-0CV (High Temp) Window: 4.50” x 3.50”
For High Ambient Temperature Applications
600 Volt Current Transformer
Model JAB-AC (High Accuracy) Window: 4.50” x 3.50”
Notes: Consult factory for base plate provisions.
Notes:
ψ A high temperature version is available for use in locations with unusually high ambient temperatures. Consult
factory for base plate provisions.
Current
Ratio
(Amps)
Pri : Sec
Burden
Continuous Thermal Current
Rating Factor
Catalog Number (With Secondary
Hardware and
Cover)
@ 85oC Amb.
200:5 B0.1 4.0 750X236202
300:5 B0.2 4.0 750X236203
400:5 B0.2 4.0 750X236204
500:5 B0.5 3.0 750X236205
600:5 B0.5 3.0 750X236206
800:5 B0.5 3.0 750X236208
1000:5 B0.5 2.0 750X236210
1200:5 B0.5 2.0 750X236212
1500:5 B0.9 2.0 750X236215
2000:5 B1.8 1.5 750X236220
3000:5 B1.8 1.33 750X236230
APPLICATION
Designed for indoor service. This special version of the JAB-0CV current transformer is designed for use on heavily loaded pad mount transformers
operating in high temperature environments up to 85
o
C. For mounting and application information, including use at higher voltages, and matching the current rating to the pad transformer thermal capability.
IEEE METER ACCURACY CLASS, 60 Hz
0.3% class from B0.1 to the burdens shown in the table.
WEIGHT & Dimensions
(approximate) Weight: 8.25 lbs Height: 8.75” Width: 6.00” Depth: 2.30”
REFERENCE DRAWINGS
Outline .......................................0121C33851
INSULATION LEVEL
0.6kV; BIL 10kV full wave
FREQUENCY
50-60 Hz
APPLICATION
Designed for indoor service; especially designed for installation over the secondary bushings of pad mounted transformers from 75 kVA TO 3000 kVA. For mounting and application information, including use at higher voltages, and matching the current rating to the pad transformer thermal capability.
WEIGHT & Dimensions
(approximate) Weight: 8.25 lbs Height: 8.75” Width: 6.00” Depth: 2.30”
REFERENCE DRAWINGS
Outline .................0121C33851
INSULATION LEVEL
0.6kV; BIL 10kV full wave
FREQUENCY
50-60 Hz
JAB-AC DATA TABLE
Current
Ratio
(Amps)
Pri : Sec
IEEE Accuracy Class
60 Hz Burden
Electronic
Burdens
Continuous Thermal Current
Rating Factor ψ
Catalog Number (With Secondary
Hardware and
Cover)
B0.1 B0.2 B0.5 E0.04 E0.2
@ 30oC Amb. @ 55oC Amb.
800:5 0.15 0.15 0.3 -- -- 3.0 2.2 750X136412
1000:5 0.15 0.15 0.3 0.15 -- 2.0 1.5 750X136413
1200:5 0.15 0.15 0.3 0.15 -- 1.5 1.1 750X136414
1500:5 0.15 0.15 0.3 0.15 0.15 2.0 1.5 750X136415
2000:5 0.15 0.15 0.15 0.15 0.15 1.0 0.7 750X136416
3000:5 0.15 0.15 0.15 0.15 0.15 1.0 0.7 750X136417
Model JAB-0W (Encompass) Window: 4.50” x 3.50”
Transformer rated meters must be investigated for use at the lower current range extension.
JAB-0W DATA TABLE
Current
Ratio
(Amps)
Pri : Sec
IEEE Accuracy Class
Burden 0.3 B0.5
Continuous Thermal Current
Rating Factor
Dimensions in inches
Catalog Number
@ 30oC Amb. @ 55oC Amb.
Height Width Depth
500:5 200:2 to 2000:20 4.0 3.0 8.75 6.00 2.30 750X136651
1500:5 600:2 to 3000:10 2.0 1.5 8.75 6.00 2.30 750X136652
JAB-0W HIGH TEMP DATA TABLE
Current
Ratio
(Amps)
Pri : Sec
IEEE Accuracy Class
Burden 0.3 B0.5
Continuous Thermal Current
Rating Factor
Dimensions in inches
Catalog
Number
@ 85oC Amb.
Height Width Depth
500:5 200:2 to 2000:20 4.0 9.37 6.38 2.50 750X136464
1500:5 600:2 to 3000:10 2.0 8.75 6.00 2.30 750X136463
APPLICATION
Designed for indoor service; especially designed for installation over the secondary bushings of pad-mounted transformers from 75 kVA to 3000 kVA. For mounting and application information, including use at higher voltages, and matching the current rating to the transformer thermal capability.
WEIGHT (approximate) Weight 4.0 lbs
REFERENCE DRAWINGS
Outline ....................0121C33851
Outline (cast resin) ....................0121C40890
INSULATION LEVEL
0.6kV; BIL 10kV full wave
FREQUENCY
50-60 Hz
6
7
Brochure Availabale at
www.GEITI.com
Loading...