Instrument Transformer, Div of GE 613 Data Sheet

GE
Energy Connections
Model 613
Current Transformer Split Core / Clamp On Window Size 0.80” x 1.95”
Application
For energy management systems and instrumentation equipment having a high input impedance, eg. 14K ohms minimum..
Frequency
50-400 Hz.
Insulation Level
0.6 kV, BIL 10 kV full wave.
Continuous Thermal Current Rating Factor
Models 613-101 thru 613-401:
1.33 at 30 °C. amb.,
1.0 at 55 °C. amb.
Model 613-1000T:
330 A at 30 °C. amb., 250 A at 55 °C. amb.
Flexible leads UL 1015, 105 °C , CSA approved, #16 AWG, 24” long unless otherwise specified
Approximate Weight 1 lb.
Manufactured to meet the requirements of ANSI/IEEE C57.13. Classified by U.L. in accordance with IEC 44-1
*The Model 613—1000T is intended for use with high input impedance devices that require signal voltages up to 5 VAC. The output can be rectified and filtered for devices requiring DC in, the non­linearity and voltage drop of the rectifiers and filters must be considered in the choice of the loading impedance.
Model 613 Split Core / Clamp On
This transformer is designed for assembly to an existing electrical installation without the need for dismantling the primary bus or cables.
Caution:
Proper safety precautions must be followed during installation by a trained electrician. Never install while bus is energized.
The current transformer must have its secondary terminals short circuited or the burden connected, before energizing the primary circuit.