GE
Energy Connections
Model 613
Current Transformer Split Core / Clamp On
Window Size 0.80” x 1.95”
Application
For energy management systems and
instrumentation equipment having a high
input impedance, eg. 14K ohms
minimum..
Frequency
50-400 Hz.
Insulation Level
0.6 kV, BIL 10 kV full wave.
Continuous Thermal
Current Rating Factor
Models 613-101 thru 613-401:
1.33 at 30 °C. amb.,
1.0 at 55 °C. amb.
Model 613-1000T:
330 A at 30 °C. amb.,
250 A at 55 °C. amb.
Flexible leads UL 1015, 105 °C , CSA
approved, #16 AWG, 24” long unless
otherwise specified
Approximate Weight 1 lb.
REGULATORY AGENCY APPROVALS
Manufactured to meet the requirements of ANSI/IEEE C57.13.
Classified by U.L. in accordance with IEC 44-1
*The Model 613—1000T is intended for use with high input impedance devices that require signal
voltages up to 5 VAC. The output can be rectified and filtered for devices requiring DC in, the nonlinearity and voltage drop of the rectifiers and filters must be considered in the choice of the loading
impedance.
![](/html/c6/c6a0/c6a0585073adaa19cdc81d074934d10cb826a4bd55e22140d0857a0a00b2553d/bg2.png)
Model 613 Split Core / Clamp On
This transformer is designed for assembly to an existing electrical installation without the need for dismantling the primary bus or cables.
Caution:
Proper safety precautions must be followed during installation by a trained electrician. Never install while bus is energized.
The current transformer must have its secondary terminals short circuited or the burden connected, before energizing the primary circuit.
Grid-AIS-L4-ITI_Model_613-1561-2017_06-EN. © Copyright 2017. General Electric Company
and Instrument Transformers LLC reserve the right to change specifications of described
products at any time without notice and without obligation to notify any person of such changes.