Instrument Transformer, Div of GE 603-500T, 603D-500T Data Sheet

GE
Energy Connections
Models 603-500T & 603D-500T
Current Transformers Split Core Window Size 2.00” x 1.00”, 2.00”x 2.00”
Application
For energy management systems and instrumentation equipment having a no return high input impedance, eg. 14 K ohms minimum.
Frequency
50-400 Hz.
Insulation Level
0.6 kV, BIL 10 kV full wave.
Continuous Thermal Current Rating Factor
Model 603: 350 A at 30 °C. amb., 260 A at 55 °C. amb.
603-500T
Flexible leads UL 1015, 105 °C , CSA approved, #22 AWG, 24” long unless otherwise specified.
Approximate Weight:
Model 603-500T.....0.63 lbs.
Model 603D-500T.....0.75 lbs
603D-500T
Models 603-500T & 603D-500T Split Core
These transformers are designed for assembly to an existing electrical installation without the need for dismantling the primary bus or cables.
These transformers is intended for use with high input impedance devices that require signal voltages up to 5 VAC.
The output can be rectified and filtered for devices requiring DC input. The non-linearity and voltage drop of the rectifiers and filters must be considered in the choice of the loading impedance.
Caution:
Proper safety precautions must be followed during installation by a trained electrician. Never install while bus is energized.
The current transformer must have its secondary terminals short circuited or the burden connected, before energizing the primary circuit.
Model 603-500T
Model 603D-500T
Grid-AIS-L4-ITI_Model_603_603D-1555-2017_06-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.