Instrument Transformer, Div of GE 500 Data Sheet

Page 1
GE
Energy Connections
Model 500
Split Core Current Transformer Window Sizes Available up to 10”x 30”
Application
Metering.
Frequency
50-400 Hz
Insulation Level
0.6 kV, BIL 10 kV full wave.
Continuous Thermal Current Rating Factor
1.33 at 30 °C. amb.
1.0 at 55 °C. amb.
The accuracy table below is for 500T041 X 117. Accuracy for other sizes are available from the factory. The dimensions in the table at right are standard sizes. Other window lengths (B1) may be accommodated on special order. Window widths (A1) other than those listed are not available.
Terminals are 8-32 brass studs with one flatwasher, lockwasher, and regular nut.
Flexible leads are UL 1015, 105°C , CSA approved, #16 AWG, 24” long are available.
Approximate Weight 8 to 18 lbs.
Page 2
Model 500 Split Model 500 Split Core
This transformer is designed for assembly to an existing electrical installation without the need for dismantling the primary bus or cables.
Caution:
Proper safety precautions must be followed during installation by a trained electrician. Never install while bus is energized. The current transformer must have its secondary terminals short circuited or the burden connected, before energizing the primary circuit
How to Order Rectangulary CTs
Grid-AIS-L4-ITI_Model_500-1554-2017_05-EN. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.
Loading...