GE
Energy Connections
Model 467
Voltage Transformer
Application
60 Hz.
Standard Secondary Voltage
120 Volts.
Insulation Level
600 Volt, 10 kV BIL full wave.
Accuracy Class:
± 1% at all burdens up to 5 VA at 1.0
and 0.95 P
Thermal Rating:
40 VA at 30 °C. amb.
27 VA at 55 °C. amb.
Terminals are No. 6-32 screws with one
lockwasher and one flatwasher.
Approximate weight 2.5 lbs.
Clear Plastic Cover
![](/html/e6/e6ca/e6cab7fce5d50592da229664975443690837ee85796836754fb19b8f2c246eb9/bg2.png)
Model 467
Refer to Model 3VT472 for 3-Phase 4 Wire connected version
The core and coil assembly is encased in a thermoplastic shell and filled with resin.
These transformers are designed for operation line-to-line. They may also be operated line-toground or line-to-neutral at reduced
voltage voltage, (58 % of rated volts).
It is desirable to use a 0.40 amp fuse in the secondary to protect the transformer.
With two exceptions these transformer are ANSI C57.13 group 1. Those marked * are group 2.
Models designed specifically for 50 Hz operations are available with reduced performance consult factory details.
Each transformer has a clear plastic cover